Manual 85204
ProTech 203 Overspeed Protection System
Woodward
21
Chapter 5.
Troubleshooting and User Repairs
Troubleshooting
The following troubleshooting guide will help isolate problems in the ProTech
®
203 device, actuating system, plant wiring, MPUs, or elsewhere. Make the
checks in the order indicated.
To check the ProTech control thoroughly, troubleshoot each unit (A,
B, and C) separately. A unit consists of one complete speed-sensing
circuit, including the power supply, I/O module, and display board.
Symptom
Cause
Remedy
Prime mover
overspeeds after
operating at rated
speed for some
time
Prime mover
Check for proper operation of
the prime-mover fuel system.
If actuator moves toward
minimum fuel during
overspeed, problem is in the
fuel system.
Prime mover
does not trip on
overspeed
Power is not applied to an
energized-to-trip ProTech
model
Apply power to all ProTech
units.
The ProTech device is not
connected or is incorrectly
connected to the external
actuating system
Check that the ProTech
device is installed properly.
Incorrect set point values
configured for one or more
units
Check the MPU GEAR
TEETH and TRIP SPEED
SETPOINT configurations for
each unit to verify that they
are appropriate for prime
mover and the individual
MPUs.
If two or more units show a
TRIPPED indication, the
cause is the external actuating
system down-line from the
ProTech device
Check for incorrect field wiring
and inoperable or incorrectly
calibrated actuating
equipment.
Prime mover trips
inappropriately
More than one unit has been
overspeed tested at one time
Reset the units.
Incorrect set point values
configured for one or more
units
Check the MPU GEAR
TEETH and TRIP SPEED
SETPOINT configurations for
each unit to verify that they
are appropriate for prime
mover and the individual
MPUs.
Содержание ProTech 203