5009 Installation/Hardware
Manual 85580V2
34
Woodward
Table 4-1 also provides each power supply’s holdup time specification, which is
the time the supply will continue to operate within specification after its input
power is interrupted. This information may be useful in specifying Uninterruptible
Power Supply (UPS) systems.
Table 4-1. Fuse/Breaker Requirements
Input Voltage
and Frequency
Range
Rated
Maximum
Current
Actual
Maximum
Current
Maximum
Power
Maximum
Fuse/C.B.
Rating
Wire Size
mm²/AWG
Wire
Temp. Rating
(°C)*
Hold Up Time
(Minimum)
18–32 Vdc
32 A
22 A
400 W
30 A
8 / 10
90
7 ms @ 24 V
100–150 Vdc
5.8 A
4.0 A
400 W
10 A
2.5 / 14
90
7 ms @ 120 V
88–132 Vac
47–63 Hz
13 A
9.1 A
800 VA
15 A
2.5 / 14
90
1 cycle @ 120 V
180–264 Vac
47–63 Hz
6.5 A
4.4 A
800 VA
10 A
2.5 / 14
90
1 cycle @ 220 V
200–300 Vdc
2.9 A
2.9 A
600 VA
10 A
2.5 / 14
90
7 ms @ 200 V
*Wire Temp ratings specified are for 55 °C cabinet ambient.
All fuses listed above are “slow blow”.
Significant inrush currents are possible when current is applied to the main
power supply. The magnitude of the inrush current depends on the power source
impedance, so Woodward cannot specify the maximum inrush current. Time-
delay fuses or circuit breakers must be used to avoid nuisance trips.
The 5009 control includes a set of two main power supplies. Input power ratings
are identified in Table 4-1 and on each power supply’s front panel. Refer to
Chapter 6 of this Volume for all power supply specifications.
When a cabinet is supplied with the system, input power connections and PE
ground are made through panel mounted Phoenix type terminal blocks. These
terminal blocks accept wires from 0.08–2.5 mm² (20–8 AWG). For a good
connection the inserted wires should have the insulation stripped back by about
6 mm (1/4”). Refer to Figure 4-20 for a wiring diagram of the cabinet’s input
power terminals.
When a cabinet is not supplied with the system, input power connections and PE
ground are made through terminals on the front of each main power supply.
These terminals accept wires from 0.08–2.5 mm² (20–8 AWG) wire. For a good
connection the inserted wires should have the insulation stripped back by about
8 mm (1/3”). Figure 4-20 displays a 120 Vac/150 Vdc or a 220 Vac power
supply’s input terminals. The 24 Vdc power supply model uses larger copper
input terminals to accommodate the required 10 mm² (8 AWG) wire. A
green/yellow wire must be used for PE ground connection. Fixed wiring
installation is required for power supplies.
Содержание MicroNet TMR 5009
Страница 8: ...5009 Installation Hardware Manual 85580V2 vi Woodward...
Страница 23: ...Manual 85580V2 5009 Installation Hardware Woodward 15 Figure 3 1 Hardware Identification...
Страница 28: ...5009 Installation Hardware Manual 85580V2 20 Woodward Figure 3 4a Outline Drawing of 5009 Main Chassis...
Страница 29: ...Manual 85580V2 5009 Installation Hardware Woodward 21 Figure 3 4b Outline Drawing of 5009 Main Chassis...
Страница 30: ...5009 Installation Hardware Manual 85580V2 22 Woodward Figure 3 4c Outline Drawing of 5009 Power Chassis...
Страница 33: ...Manual 85580V2 5009 Installation Hardware Woodward 25 Figure 3 7 DIN Rail ATM Outline Drawing...
Страница 35: ...Manual 85580V2 5009 Installation Hardware Woodward 27 Figure 3 9 DTM Outline Drawing...
Страница 36: ...5009 Installation Hardware Manual 85580V2 28 Woodward Figure 3 10 DTM Mounting Configuration...
Страница 59: ...Manual 85580V2 5009 Installation Hardware Woodward 51 Figure 4 13 Jumper and Relay Location Diagram...
Страница 66: ...5009 Installation Hardware Manual 85580V2 58 Woodward Figure 4 18a Cabinet Device Location Diagram...
Страница 67: ...Manual 85580V2 5009 Installation Hardware Woodward 59 Figure 4 18b Cabinet Device Location Diagram...
Страница 68: ...5009 Installation Hardware Manual 85580V2 60 Woodward Figure 4 19 System Cable Layout Diagram...
Страница 69: ...Manual 85580V2 5009 Installation Hardware Woodward 61 Figure 4 20 Power Supply Wiring Diagram...
Страница 70: ...5009 Installation Hardware Manual 85580V2 62 Woodward Figure 4 21 ATM 1 Wiring Diagram...
Страница 71: ...Manual 85580V2 5009 Installation Hardware Woodward 63 Figure 4 22 ATM 2 Wiring Diagram...
Страница 72: ...5009 Installation Hardware Manual 85580V2 64 Woodward Figure 4 23 DTM 1 Wiring Diagram...
Страница 73: ...Manual 85580V2 5009 Installation Hardware Woodward 65 Figure 4 24 DTM 2 Wiring Diagram...
Страница 74: ...5009 Installation Hardware Manual 85580V2 66 Woodward Figure 4 25 DTM 3 Wiring Diagram...
Страница 75: ...Manual 85580V2 5009 Installation Hardware Woodward 67 Figure 4 26 DTM 4 Wiring Diagram...
Страница 89: ...Manual 85580V2 5009 Installation Hardware Woodward 81 Table 5 3 Discrete In Cable Connections...
Страница 90: ...5009 Installation Hardware Manual 85580V2 82 Woodward Table 5 4 Relay Cable Connections...
Страница 91: ...Manual 85580V2 5009 Installation Hardware Woodward 83 Table 5 4 Relay Cable Connections cont...
Страница 92: ...5009 Installation Hardware Manual 85580V2 84 Woodward Table 5 5 Analog Combo Module...
Страница 93: ...Manual 85580V2 5009 Installation Hardware Woodward 85 Table 5 6 DTM Interconnect Cables W14 W15 W16...
Страница 103: ...Manual 85580V2 5009 Installation Hardware Woodward 95 Figure 8 2 Operator Control Panel...
Страница 108: ...5009 Installation Hardware Manual 85580V2 100 Woodward Figure 8 6 Real Power Sensor...
Страница 109: ...Manual 85580V2 5009 Installation Hardware Woodward 101 Figure 8 7 Plant Wiring Diagram for the Real Power Sensor...
Страница 115: ......
Страница 116: ...Declarations...
Страница 117: ......