Problem or maloperation in…
Problem Description
Corrective Action
•
Fiber optic lines are too long
•
Fiber optic lines are damaged
•
Fiber optic connectors are damaged
•
You can do a test of the fiber optic port
(see under “Troubleshooting – Hardware”,
Loopback Test)
•
OK (some errors)
Some errors occurred during normal protection
communication, see <Operation/ Status Display/
Prot-Transfer/ ProtCom/ State/ 24h Err Cr>. Errors
may occur when plugging in/ out the connection
line. The counter can be reset via <Operation/
Reset/ ProtCom.Res all Cr/Err>. You can adjust
the warning level under <Protection Para/ Global
Prot Para/ Prot-Transfer/ ProtCom/ 24h Err
WarnLev>.
•
Eth.Switch det.
Devices are connected via a switch. Proper
operation can only be guaranteed for direct device
connection. Please adjust.
•
OK (stable)
Protection communication is running stable.
Line Differential: Protection Communication not
working as expected.
Protection Communication is working, but not
correctly.
If <Operation/ Status Display/ Prot-Transfer/ ProtCom/
Advanced States/ Operating Mode> shows <Loopback>,
HighPROTEC Troubleshooting Guide DOK-HB-TSE Rev. B
20