No
Type
Description
10
Charge alternator low voltage When the controller detects that charger voltage has fallen below the pre-set
value, it will initiate a warning alarm.
11
Battery undervoltage
When the controller detects that start battery voltage has fallen below the pre-
set value, it will initiate a warning alarm.
12
Battery overvoltage
When the controller detects that start battery voltage has exceeded the pre-set
value, it will initiate a warning alarm.
13
Maintenance due
When count down time is 0 and the selected action ist “Warn”, it will initiate a
warning alarm.
14
Gen. reverse power
If reverse power detection is enabled, when the controller detects that the
reverse power value (power is negative) has fallen below the pre-set value and
the selected action is “Warn”, it will initiate a warning alarm.
15
Overload
If over power detection is enabled, when the controller detects that the over
power value (power is positive) has exceeded the pre-set value and the
selected action is “Warn”, it will initiate a warning alarm.
16
ECU warning alarm
If an error message is received from ECU via J1939, it will initiate a warning
alarm.
17
Gen. loss of phase
If loss of phase detection is enabled, When controller detects the generator loss
phase, it will initiate a warning alarm.
18
Gen. phase rotation
mismatch
When the controller detects a phase rotation error, it will initiate a warning
alarm.
19
Breaker open/close fail
When the controller detects that the breaker close or open failure occurs, and
the selected action is “Warn”, it will initiate a warning alarm.
20
Temperature sensor wire
break
When the controller detects that the temperature sensor is open circuit and the
selected action is “Warn”, it will initiate a warning alarm.
21
High temperature
When the controller detects that engine temperature has exceeded the pre-set
value, it will initiate a warning alarm.
22
Low temperature
When the controller detects that engine temperature has fallen below the pre-
set value, it will initiate a warning alarm.
23
Oil pressure sensor wire
break
When the controller detects that the oil pressure sensor is open circuit and the
selected action is “Warn”, it will initiate a warning alarm.
24
Low oil pressure
When the controller detects that the oil pressure has fallen below the pre-set
value, it will initiate a warning alarm.
25
Fuel level sensor wire break
When the controller detects that the level sensor is open circuit and the
selected action is “Warn”, it will initiate a warning alarm.
26
Low fuel level
When the controller detects that the fuel level has fallen below the pre-set
value, it will initiate a warning alarm.
27
Analog input 4 Wire break
When the controller detects that the flexible sensor 1 is open circuit and the
selected action is “Warn”, it will initiate a warning alarm.
28
Analog input 4 High limit
When the controller detects that the sensor 1 value has exceeded the pre-set
value, it will initiate a warning alarm.
29
Analog input 4 Low limit
When the controller detects that the sensor 1 value has fallen below the pre-set
value, it will initiate a warning alarm.
30
Analog input 5 Wire break
When the controller detects that the flexible sensor 2 is open circuit and the
selected action is “Warn”, it will initiate a warning alarm.
31
Analog input 5 High limit
When the controller detects that the sensor 2 value has exceeded the pre-set
value, it will initiate a warning alarm.
32
Analog input 5 Low limit
When the controller detects that the sensor 2 value has fallen below the pre-set
value, it will initiate a warning alarm.
33
Discrete input xyz
When digit input port is set as warning and the alarm is active, it will initiate a
warning alarm.
27
easYgen-1700
37888A
4 Appendix
4.1 Alarms and Warnings