◦ »Overfrequency«
◦ »Underfrequency«
◦ »Mains voltage asymmetry«
◦ »Mains phase rotation fail«
The start procedure includes breaker handling, engine start, and signaling/warning.
Load supply transition from genset (back) to mains
All of the above listed parameters are (back) in normal range.
The stop procedure includes breaker handling, engine stand-by, and signaling/warning.
3.3.2
Operation Mode MANual
General notes
In operation mode MANual, both genset and breakers are independent of each other
under easYgen control.
The starting and stopping of the engine are managed using the same procedure as in
AUTO mode but without breaker control. Breakers can be opened and closed without
taking care of load, genset, or mains state!
CAUTION!
Take care for genset and supply.
3.3.3
Operation Mode STOP
General notes
In operation mode STOP, the breakers are open and the engine is not running.
This is a configurable operation mode, only. This is NO emergency STOP!
3.4
START/STOP Operation
17
easYgen-1700
37888A
3 Operation
3.4 START/STOP Operation