Unload
One of the breakers is closed - open this breaker.
Press the breaker switch
of the closed breaker
The respective breaker will be opened.
The opening signal will last for the »Opening time«
During this time, all other breaker signals are suppressed.
Transfer load
One of the breakers is closed - close the other breaker.
Press the breaker switch
of the open breaker
The other (closed) breaker is opened.
The opening signal will last for the »Opening time«
During this time, all other breaker signals are suppressed.
After this, the other breaker (selected by pressed button) will be closed
Closing signal will last for the »Closing time«
During this time, all other breaker signals are suppressed.
3.6
Trouble Shooting
Symptoms
Possible Solutions
Controller has no power.
Check starting batteries; Check controller connection wiring; Check DC
fuse.
Genset shutdown
Check if the water/cylinder temperature exceeds the limits; Check the
genset AC voltage; Check DC fuse.
Controller emergency stop
Check if emergency stop button works properly; Check whether the
starting battery's positive pole is connected to the emergency stop input;
Check whether the circuit is open.
Low oil pressure alarm after crank disconnect
Check the oil pressure sensor and its connections.
24
easYgen-1700
37888A
3 Operation
3.6 Trouble Shooting