3.4.1
Start engine to supply load
General notes
Pre-Condition
Mode
Energy
Breakers
Genset
AUTO
Mains is "normal"
GCB is open
Not running
Ready for operation
MCB is closed
Situation
• Mains becomes abnormal when one or more parameter are outside their working
range and one of the following occurs:
◦ »Overvoltage«
◦ »Undervoltage«
◦ »Overfrequency«
◦ »Underfrequency«
◦ »Mains voltage asymmetry«
◦ »Mains phase rotation fail«
The AUTO Start procedure runs sub procedures with own timers.
If the mains is back during the process, re-connecting the mains has priority.
The remaining time of each of the timers initiated displays.
When started via “Remote Start (off Load)” input, the starting procedure is the same as
shown below but the generator close relay is deactivated.
Because there is no mains control, only the "Start engine" section (green background) is
relevant.
18
easYgen-1700
37888A
3 Operation
3.4 START/STOP Operation