VENT INSTALLATION 

4. Connect a section of pipe and extend up through the hole.

NOTE: If an offset is needed to avoid obstructions, you must support the vent pipe every three (3) feet. Use wall 
straps for this purpose. See Figure 25, page 22. Whenever possible, use 45

°

 elbows instead of 90° elbows. The 45° 

elbow offers less restriction to the flow of the flue gases and intake air.

5. Place the flashing over the pipe section(s) extending through the roof. Secure the base of the flashing to the roof and framing

with roofing nails. Be sure roofing material overlaps the top edge of the flashing. There must be a 1" clearance from the vent
pipe to combustible materials.

6. Continue to add pipe sections until the height of the vent cap meets the minimum building code requirements.

NOTE: You must increase vent height for steep roof pitches. Nearby trees, adjoining roof lines, steep pitched roofs, 
and other similar factors may cause poor draft or down-drafting in high winds. Increasing the vent height may solve 
this problem.

NOTE: If the vent pipe passes through any occupied areas above the first floor, including storage spaces and closets, 
you must enclose pipe. You may frame and sheetrock the enclosure with standard construction material. Make sure 
to meet the minimum allowable clearances to combustibles. Do not fill any of the required clearance spaces with 
insulation.  

Figure 30 - Cathedral Ceiling Support Box Installation 

Figure 31 - Installed Cathedral Ceiling 

Support Box

CATHEDRAL CEILING INSTALLATION

IMPORTANT:  Review  all  information  on  previous  page 
before  planning  this  installation.  Cathedral  ceiling 
installations can be very tricky. 

1. Remove shingles or other roof covering as necessary to cut

the rectangular hole for the support box. Mark the outline
of the cathedral ceiling support box on the roof sheathing
using the locating hole as a center point.

2. Cut the hole 

1

/

8

" larger than the support box outline. 

See

Figure 30.

3. Lower the support box through the hole in the roof until

the bottom of the box extends at least 2" ( mm) below the
ceiling. 

See Figure 30.

 Align the support box vertically and

horizontally using a level. Temporarily tack the support box
in place through the inside walls and into the roof sheet-
ing.

4. Using tin snips, cut the support box from the top corners

down to the roofline and fold the resulting flaps over the
roof sheeting. 

See Figure 31. 

Apply a bead of non-hardening

mastic around the top edges of the support box to make a
seal between the box and the roof. Nail in place with roof-
ing nails. Remove any combustible material that might be
inside the support box.

5. Complete  the  cathedral  ceiling  installation  by  following

the same procedures outlines in steps 2 through 6 for 

Flat

Ceiling Installation

, page 23 and above.

Level 

Cathedral 

Ceiling Support 

Box 

2" Minimum 

Below 

Finished 

Ceiling 

Cut Hole 1/8" Larger 

than Support Box 

when Projected onto 

Roofline.

Apply Non-hardening 

Mastic Under all Edges of 

Support Box before Nailing 

24

25

Содержание DV36CV-E

Страница 1: ...se any phone in your building Do not try to light any appliance phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire WARNING Improper installation adjustmen...

Страница 2: ...rmination Configuration 19 Below Grade Installation 21 Vertical Through the Roof Installation 22 Installation for Vertical Termination 23 Cathedral Ceiling Installation 24 Operating Instructions 34 Wh...

Страница 3: ...MONOXIDE POISONING Early signs of carbon monoxide poisoning are similar to the flu with headaches diz ziness and or nausea If you have these signs the fireplace may not have been installed properly Ge...

Страница 4: ...own cycle Similar noises are found with your furnace heat exchanger or car engine IMPORTANT PLEASE READ THE FOLLOWING CAREFULLY It is not unusual for gas fireplace to give off some odor the first time...

Страница 5: ...he vent pipe CODE APPROVAL FIREPLACE HEATERS in the USA and Canada as follows These appliances have been listed by OMNI and found to comply with the established standards for DIRECT VENT GAS 5 This ap...

Страница 6: ...is found Do not install any unit with damaged incomplete or substitute parts Check your packing list to verify that all listed parts have been received You should have the following Fireplace Firebox...

Страница 7: ...r raised on a platform of an appropriate height When the firebox is installed directly on carpeting tile or other combustible material other than wood flooring the firebox shall be installed on a meta...

Страница 8: ...PRE INSTALLATION INFORMATION 8 Figure 3 Fireplace Dimensions Right side view Front view Top view 43 25 23 25 48 43 25 37 38 14 7 5 8 75 23 25 31 7 1 75 2 25 25 10 53 25 25 25 31 25...

Страница 9: ..._ __ __ __ __ __ __ _ _ _ _ _ _ __ to opening COVERING FACE Firebox framing can be built before or after the appliance is set in place Construct firebox framing following Figure 2 and the chart below...

Страница 10: ...Woodbridge Foreplace is not respon sible Figure 5 Covering Fireplace face allow for or glass door removal A 1 4 reveal must be provided all the way around the fireplace opening NON COMBUSTION MATERIAL...

Страница 11: ...xtending full width and depth of the appliance CLEARANCES CLEARANCES TO COMBUSTIBLES MANTEL CLEARANCES NOTE The combustible area above the facing must not protrude more than 3 4 from the facing If it...

Страница 12: ...SHING MATERIAL NOTE Any remote wiring i e remote control wall switch and optional fan must be done prior to nal nishing to avoid costly reconstruction INSTALLATION INFORMATION Only noncombustible mate...

Страница 13: ...Do not use common vent systems WARNING Horizontal sections of this vent system require a minimum clearance of 3 from the top of the pipe and 1 minimum to the sides and bottom Vertical sections of thi...

Страница 14: ...he attic additional pipe and elbows will be required You may use a chase with a vent termination with exposed pipe on the exterior of the house See Installing Vent System in a Chase below If pipe is e...

Страница 15: ...extend a minimum of 24 610mm above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18 457mm As specified in CAN CGA B149 Installati...

Страница 16: ...ne to the bottom of the graph 3 Select the indicated dimension and position the fireplace in accordance with same Example If the vertical dimension from the floor of the fireplace is 11 3 4m the horiz...

Страница 17: ...or with pipe seams oriented towards the wall or floor Twist lock Procedure The female ends of the pipes and fittings have three locking lugs indentations These lugs will slide straight into matching s...

Страница 18: ...imble over the vent pipe before connecting the horizontal run to the vent cap See Figure 16 6 Carefully move the fireplace with vent assembly attached toward the wall and insert the vent pipe into the...

Страница 19: ...s than 20 below siding outcrop the vent pipe must flush up with the sid ing It is best to locate the fireplace in such a way that minimizes the number of offsets and horizontal vent length The horizon...

Страница 20: ...the vent graph page 16 the maximum and if a 90 elbow is required in the horizontal vent it must In Figures 20 and 21 Dimension A plus B must not be greater The maximum number of 45 elbows permitted p...

Страница 21: ...ve soil to a depth of approximately 16 below base of snorkel Install drain pipe Install window well not supplied Refill hole with 12 of coarse gravel leaving a clearance of approximately 4 below snork...

Страница 22: ...d within the vertical sections From 0 to a maximum of 8 2 5 m of vent pipe can be used between elbows See Figure 26 application will require that you first determine the roof pitch and use the appropr...

Страница 23: ...x101 2 267mm x 267mm inside dimensions as shown in Figure 12 page 17 using framing lumber the same size as the ceiling joist If the area above the ceiling is an insulated ceiling or a room nail fires...

Страница 24: ...g Support Box Installation Figure 31 Installed Cathedral Ceiling Support Box CATHEDRAL CEILING INSTALLATION IMPORTANT Review all information on previous page before planning this installation Cathedra...

Страница 25: ...ncoming gas pressure You must reduce incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could occur Install external r...

Страница 26: ...aps moisture and contaminants This keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly Figure...

Страница 27: ...34 After taking pressure reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks 2 The appliance and its appliance main gas valve must be...

Страница 28: ...ocal codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition and Canadian Electrical Code CSA C22 1 WARNING Label all wires before disconnecting when servi...

Страница 29: ...e controls in the lower cavity surface and be careful to not damage and controls in the lower cavity of the fireplace Completely remove the glass frame and set aside GLASS REMOVAL 2 Lean the top of th...

Страница 30: ...one layer of material to cover the entire Do not use the entire bag of material to cover Ember Materiall Figure 37 Placement of Ember Material IMPORTANT Avoid ports when ember material to ensure that...

Страница 31: ...to refresh when cleaning later Too much ember material can disturb the flame and cause sooting on the glass or logs Figure 42 Placing Side Logs Figure 43 Log Set complete assembly 8 Light the fireplac...

Страница 32: ...r shall be replaced with the manufacturer s barrier for this appliance Any safety screen guard or barrier removed for servicing the appliance must be replaced prior to operating the appliance WARNING...

Страница 33: ...d slide downward Make sure the Side Panel is secured properly Repeat with opposite side panel into the opening angling in at the top to rest on the face support as shown STEP 4 Support the Air Flow Pa...

Страница 34: ...upply to the DFC board please verify that the electrical connections illustrated parts list or mounted in adjacent wall Make sure that the remote receiver switch is in REMOTE middle position Initializ...

Страница 35: ...Note the polarity of the batteries and insert into the battery bay as indicated on the battery covel 2 Place the 3 posilion slider switch in the REMOTE position 3 Insert the end of a paper clip into...

Страница 36: ...ll ignite A single beep from the receiver will confirm the command Turning OFF the Appliance 1 Press the ON OFF button 011 the transmitter The A single beep from the receiver will confirm the command...

Страница 37: ...eiver or transmitter batteries are low or de pleted the appliance can still be turned on manually 1 Move the receivers three position slider to the ON position This will bypass the remote control feat...

Страница 38: ...t is recommended that a qualified service technician perform these check ups at the beginning of each heating season WARNING Keep the control compartment logs and burner areas surrounding the logs cle...

Страница 39: ...using a nontoxic non corrosive non abrasive mild cleaning solution Simply apply an adequate amount to the glass and wipe off with a damp cloth After all maintenance has been completed re install glas...

Страница 40: ...t the glass is properly secure and latch Frequent pilot outage A Pilot flame may be too high or A Clean and adjust the pilot flame for maximum flame impingement The pilot and main A Inner vent pipe le...

Страница 41: ...41 ILLUSTRATED PARTS LIST 11 1 2 3 4 5 6 7 8 9 10 LOG SET P N M100513...

Страница 42: ...06 3 4 9 Pipe Length 58DVA 09 3 4 12 Pipe Length 58DVA 12 3 4 24 Pipe Length 58DVA 24 3 4 36 Pipe Length 58DVA 36 3 4 48 Pipe Length 58DVA 48 4 4 8 1 2 Pipe Extension 58DVA 08A 4 4 16 Pipe Extension 5...

Страница 43: ...appliance may result in property damage or personal injury ILLUSTRATED PARTS LISTS continued 6 15 This list contains replaceable parts used in your Fireplace All replacement parts should be ordered fr...

Страница 44: ...E 120 Vac INPUT 7 Vdc STABILIZED SUPPLY OUTPUT MOTOR IPI CPI RECEIVER DC SUPPLY SPLIT FLOW ON OFF TPTH TH DFC SUPPLY DC SUPPLY GROUND 885 PROFLAME Orange Green Chassis connection 12 1 5 13 6 14 11 155...

Страница 45: ...18 FLEX CONNECTOR WITH SHUTOFF VALVE 1 6 A100075 A100075 BRICK LINER SET 8 S700002 S700002 VALVE BRACKET 1 17 M100513 M100513 CERAMIC LOGS 10 PCS SET D300015 D300016 NG ORIFICE LP AIR MIXER 1 S700018...

Страница 46: ...127 6...

Страница 47: ...127 6...

Страница 48: ...w limitations on how long an implied warranty lasts or do not allow exclusion of indirect damage those limitations of exclusions may not apply to you You may also have additional rights not covered in...

Отзывы: