37
The
KD150
is designed for continuous duty, with
little maintenance. However, when a problem
does arise prompt repair will ensure long life for
the machine.
The blower system is direct drive and the motor has
sealed high temperature ball bearings. This unit does
not need regular maintenance.
The air filter should be washed when dirty and
replaced when necessary. If the filter becomes
clogged, the air supply will be drastically reduced,
causing the heater to overheat and the refrigeration
system to overload. Evap coil should be kept clean.
Clean with dish soap and water.
The refrigeration system is a sealed system with its
own oil supply. Again regular maintenance is not
required. However, if the system is not removing
the normal amount of water at the appropriate
conditions, the refrigeration system should be
looked at by a reputable refrigeration mechanic.
When the system experiences reduced water
output, this is generally associated with a leak in the
refrigeration system. If the leak is found and repaired
before the system is empty, there is little chance
that the system will be contaminated with moisture.
If the system is ignored for a long period of time,
moisture can enter the system and combine with the
refrigerant to form acid. The system will then corrode
from the inside-out if not corrected properly.
The circulating fan system is also direct drive with
a ball bearing motor. The motor does not require
lubrication.
The refrigeration system is a closed loop system
with its own lubrication oil supply.
We use
only the
best trade practices when assembling these
systems. The system should give years of trouble
free service. However, if the system is not removing
the right amount of water, or if a problem should
arise from rough shipping or a refrigeration leak,
the system should only be worked on by a
qualified refrigeration mechanic.
Warning: Refrigeration professionals should
use caution, these refrigeration conditions are
uncommon.
These systems operate over a very wide temperature
and humidity range. The pressures will be relatively
high when compared to air conditioners and heat
pumps. For these reasons, you cannot charge by
the sight glass, the sight glass will eventually clear
at certain conditions but it is unlikely that those
conditions will exist when servicing.
If the kiln is loaded with lumber, it will be very
dangerous to run the kiln at extreme limits, as the
lumber will degrade severely. With this danger
factor and the factor of time involved of heating the
kiln,
Wood-Mizer
insists that these machines have
weighed in charge. The amount is as follows:
KD150
20 oz. RS24
CALL
WOOD-MIZER
IF YOUR TECHNICIAN
LACKS THE RECOMMENDED REFRIGERANT.
We can recommend alternatives.
The air filters are provided to keep the air inside the
unit as clean as possible. Dirt build-up on the coils
will lead to poor heat transfer with loss of capacity.
In extreme cases, the coil will completely clog. The
supplied filter is washable and should be replaced
when worn.
Maintenance, Reference Diagrams and Warranty
General Maintenance for
KD150
Air Inlet Filters
Wood-Mizer
Refrigerant Loading
for
KD150
KD150 12/22/17
Содержание KD150 Series
Страница 2: ...KD150 12 22 17 ...
Страница 6: ...Service Log Issue Description Date Servicer KD150 12 22 17 ...
Страница 15: ...9 Figure 1 5 Kiln Chamber Wall Details Wood Mizer KD150 12 22 17 ...
Страница 16: ...10 Figure 1 6 Kiln Chamber Front Elevation Wood Mizer KD150 12 22 17 ...
Страница 17: ...11 Figure 1 7 Kiln Chamber Door Framing Wood Mizer KD150 12 22 17 ...
Страница 18: ...12 Figure 1 8 Kiln Chamber Door Section E Wood Mizer KD150 12 22 17 ...
Страница 19: ...13 Figure 1 9 Kiln Chamber Door Section F Wood Mizer KD150 12 22 17 ...
Страница 21: ...15 Figure 1 11 Door Gasket Installation GASKETS AND DOOR KITS AVAILABLE Wood Mizer KD150 12 22 17 ...
Страница 47: ...41 Notes Wood Mizer KD150 12 22 17 ...