IMPORTANT NOTE: A ground fault circuit
interrupter (GFCI) is not recommended and
may cause interruption of operation.
You must follow all National Electrical Code
regulations. In addition, be aware of local
codes and ordinances when installing your
service.
8
W O L F
D OW N D R A F T
V E N T I L A T I O N S Y S T E M S
E L E C T R I C A L
R E Q U I R E M E N T S
Wolf downdraft ventilation systems require a
separate, grounded 120 V, 60 Hz power supply.
The service should have its own 15 amp circuit
breaker, and a grounded 3-prong receptacle
should be located within the reach of the 2
1
/
2
'
(.8 m) power cord. The specific location of the
outlet is not critical, as long as it is within
reach of the power cord that is located mid-
way, top and bottom, on the right side of the
downdraft.
IMPORTANT NOTE: If Model DD30 is to be
installed in a 30" (762) wide cabinet, Model
DD36 in a 36" (914) wide cabinet or Model
DD45 in a 45
1
/
2
" (1156) wide cabinet, the
electrical outlet cannot be located on the back
wall of the cabinet. The outlet can be placed in
an adjacent cabinet within reach of the power
cord. An access hole for the power cord must
be drilled in the cabinet wall.
Choose the electrical location shown in
the illustration below that best suits your
installation.
Do not use an extension cord or two-
prong adapter. Electrical ground is
required on this appliance. Do not remove
the power supply cord ground prong.
The electrical outlet must be checked by
a qualified electrician to be sure that it is
wired with the correct polarity. Verify
that the outlet provides 120 V AC and is
properly grounded.
I M P O R T A N T
N O T E
You must follow
all National
Electrical Code
regulations. In
addition, be aware
of local codes and
ordinances when
installing your
service.
Location of electrical
36"
min (914)
FOR MODEL DD36
4 5
1
/
2
"
min (1156)
FOR MODEL DD45
30"
min (762)
FOR MODEL DD30
OPTIONAL
ELECTRICAL
LOCATION IN
ADJACENT RIGHT
SIDE CABINET
E
E
3
1
/
2
"
(89)
4"
min (102)
10"
(254)
24 "
min (610)
CABINET DEPTH