Install the panel board in the direction shown in the 

below figure, you can follow below steps.

NOTE! 

The  incorrect  direction  will  result  in  water 

leakage,  meanwhile  swing  and  signal  receiving  are  dis-

played that cannot be connected. Please refer to section 5.7 

before connect the cables.

• 

Fasten  the  screws  to  make  the 

height  difference  between  the 

two sides of indoor unit less than 

5mm.

• 

Fasten  the  two  temporally  fixing 

screws and other two. 

• 

Connect  the  cable  of  Swing-

motor. 

• 

Connect the cable of Signal cable. 

• 

Adjust the panel to make sure the 

air outlet is well matched with the 

unit condensate drain pan. 

• 

Tighten  the  four  screws  to  make 

sure the panel is tightly matched 

with indoor unit.

NOTE!

 If screws are not tightening, problems in be-

low Fig. might occur. Tighten screws properly. If there is still 

space after tightening of screws, please readjust the height 

of indoor

unit.

4.11. Pipe connection

DANGER  OF  SCALDING  BY  ESCAPING 

HEATING MEDIUM!

Before  the  on-site  piping  and  the  fan  coil  hydraulic 

connection  is  set  up,  the  heating/cooling  water  should  be 

isolated and secured against being opened unintentionally.

Установите панель в направлении, указанном на рисунке 

ниже и следуйте следующим шагам.

ПРИМЕЧАНИЕ! 

Неправильное  напрвление  установки 

панели  приведет  к  протечкам  воды.  При  этом  провода 

подключения  двигателей  жалюзи  и  сигнальных  лампочек  не 

сможете  подключить.

 

См  раздел  5.7.  перед  подключением 

кабелей. 

• 

Закрепите  времмено  винты,  чтобы  

подогнать  между  панелью  и  потолком 

до 5 мм.

• 

Закрепите  вначале  два  винта  по 

диагонеле, а потом остальные два.

• 

Подключите кабель приводов жалюзи. 

• 

Подключите кабель сигнальной панели.

• 

Отрегулируйте 

панель, 

чтобы 

убедиться,  что  выход  воздуха  хорошо 

подогнан с лотком дренажа конденсата

• 

Затяните  4  винта,  чтобы  убедиться, 

что панель плотно подогнана к корпусу 

агрегата.

ПРИМЕЧАНИЕ

!  Если  винты  не  будут  полностью 

завинчены, то будет щель между корпусом аппарата и панелью, 

через  которую  будет  выходить  воздух  и  образовываться 

конденсат.  Если  после  затягивания  винтов  останется  зазор 

между  панелью  и  аппаратом,  уменьшите  высоту  монтажа 

внутренного блока.

4.11. Подключения труб.

Опасность ожога горячей водой!

Перед  тем,  как  трубопроводные  и  гидравлические 

соединения фанкойла подключить, вода для нагрева/охлаждения 

должна  быть  перекрыта  и  застрахована  от  непреднамеренного 
открывания.

!

!

Сassette fan coil CUBE Line

14

4. Installation

Содержание CUBE LINE 04-2T

Страница 1: ...oil CUBE LINE CUBE LINE WITO Climate control of your business EN RU Model 2 pipe 2 04 2T 05 2T 08 2T 10 2T 14 2T Model 4 pipe 4 04 4T 05 4T 08 4T 10 4T 14 4T Please read this manual before using the f...

Страница 2: ......

Страница 3: ...5 Installation location 4 6 Installation requirement 4 7 Recommended service opening 4 8 Precautions 4 9 Unit mounting 4 10 Panel installation 4 11 Pipe connection 4 12 Valve connection 4 13 Condensa...

Страница 4: ...site power supply is secured against being switched back on DANGER OF SCALDING Before performing work on the valves or the inlet or outlet pipes seal off the heating or cooling water inlet to prevent...

Страница 5: ...risk of explosion In wet areas In locations with high dust levels or aggressive air 2 1 Purpose Fan coils CUBE Line are used for heating cooling dehu midification and ventilation Designed for installa...

Страница 6: ...wise it may cause leakage or work abnormally Please adjust indoor temperature properly especially when there are old people children and patient and so on in the house Lightning and electromagnetic ra...

Страница 7: ...t max W 60 76 132 152 220 Running Current A A 0 27 0 34 0 59 0 67 0 98 Power Supply V Hz 220 230 50 Motor Type 3 speed motor 3 Insulation Class class B B Water Flow l h Cooling 640 860 1220 1570 2170...

Страница 8: ...max W 60 76 132 152 220 Running Current A A 0 27 0 34 0 59 0 67 0 98 Power Supply V Hz 220 230 50 Motor Type 3 speed motor 3 Insulation Class class B B Water Flow l h Cooling 413 533 826 1032 1445 He...

Страница 9: ...OFF Button Press the TIMER OFF button once the previous timer setting will display on the LCD Press the TIMER OFF button continuously the timer will be changed in one minute intervals You can hold on...

Страница 10: ...4 3 4 25 B 48 103 149 90 45 3 4 3 4 25 614 424 D E Model D E CUBE Line 05 2 CUBE Line 08 2 710 mm 125 mm 800 mm 338 mm 737 mm CUBE Line 10 2 CUBE Line 14 2 832 mm 160 mm 950 mm 416 mm 864 mm Dimensio...

Страница 11: ...e 10 4 CUBE Line 14 4 832 mm 100 mm 950 mm 416 mm 864 mm 152 mm 77 mm 43 mm 144 mm 77 mm 90 mm 165 mm 12 4 25 0 5 8 0 6 5 0 5 8 0 6 5 0 C C 112 29 0 A A 105 32 72 142 60 45 60 130 25 I H L M G F B K 3...

Страница 12: ...lled fancoil connection manager fancoil WARNING When you install fancoil without valve it is necessary to remove the jumper S6 Mode is temperature control through the fan S6 wall pad optional step mot...

Страница 13: ...s are found please notify the carrier and request the carrier and the receiver to conduct a joint inspection f Do not repair it yourself before inspection and con firmation by the carrier representati...

Страница 14: ...ere may not be any openings to the outside in the area of the intermediate ceiling The entire intermediate ceiling area must be dry and sufficiently protected against humidity and moist air The intern...

Страница 15: ...ilding ceiling The length dimensions depend on the distance to the in termediate ceiling Push the unit with the terminal box facing front into the intermediate ceiling at an angle until the unit is fu...

Страница 16: ...cable of Signal cable Adjust the panel to make sure the air outlet is well matched with the unit condensate drain pan Tighten the four screws to make sure the panel is tightly matched with indoor uni...

Страница 17: ...en cut off Connect the chilled water pipe to coil pipe by using 3 4 external thread connecter Distinguish the inlet outlet water according to the sign on the unit Heat preservation must be used for th...

Страница 18: ...gulations The connection diagrams do not contain any protective measures During connection the standards and regu lations currently in force must be observed and cleared with the local electricity com...

Страница 19: ...regular mainte nance and inspection by technical experts is necessary NOTE Maintenance may only be performed by trained techni cal personnel in observance of this operation manual and current regulati...

Страница 20: ...connections are securely seat ed in the terminal strips Check the correct earthing of the unit with an appropri ate measuring device Close the electrical switch box again Checking valves Check the fu...

Отзывы: