Instructions condensing Air heaters type HR
Page 10/31
6.3.2 Room thermostat
The heater can only be controlled by special modulating Winterwarm room thermostats:
The Multi Therm Comfort
; modulating digital clock thermostat with optimiser. It can control 1 to
8 air heaters HR10 up to HR60 or 1 to 4 air heaters HR80 up to 120.
The Multi Therm Standard
; modulating digital thermostat. It can control 1 to 8 air heaters
HR10 up to HR60 or 1 to 4 air heaters HR80 up to 120.
The Interface printboard
; special designed interface module for connecting the air heaters with
Building Mangagement Systems. (0-10V (modulating input) signal, high/low signal,
external reset and other different in and outputs.
ON/OFF thermostat
The heater can not be controlled with a simple on/off thermostat.
In all cases the communication between heater and thermostat is based on a two wire, low-
voltage connection. In the appliance the wire for the thermostat has to be connected to
connection 4 and 5 (see also electrical wiring diagram) Attention: This also needs a change in
the settings on the print board, see chapter 11
When mounting the thermostat, take attention to the following items:
•
Mount the thermostat in a place where the air can circulate free pass the thermostat. Take
notice that the sun does not shine directly upon the thermostat (in the winter). Do not
place the thermostat on a cold wall. Place the thermostat on an inner wall free from
draught.
Never place the thermostat within the throw of the heater.
6.3.3 Thermostat cable
In all cases the communication between the heater and the thermostat is based on a two wire,
low-voltage connection. In the appliance the wire for the thermostat has to be connected to
connection 4 and 5 (see also electrical wiring diagram).
Cable specification: signal cable, 1x2x0,8 (shielded and twisted)
Maximum length 250m.
If the cable is chosen too thin, the signal will become too poor. If the cable is not shielded and
twisted the signal might become disturbed in an EMC unfriendly environment.
Keep the thermostat cable separated from mains cables. Connect the earth shield of the cable
only to the earth terminal in the heater.
If these guidelines are not followed it may result in malfunction of the installation or worse, it
could damage the thermostat or the electronics in the heater.
Never mount the thermostat near aerials of internal communication networks.
These emit radiation that could lead to disturbance of the thermostat. Always keep
some meters distance.
6.3.4 Fuses
On the heater control HC there are two fuses. See electrical wiring diagram.
F1 and F2 are in the power supply of the heater. Replace the fuse only by a fuse of the same
type, 5AT