Instructions condensing Air heaters type HR
Page 7/31
6
Installation
6.1 Positioning
•
Check that the support is solid enough.
•
The heater is designed as free hanging. The heater
should be able to blow the warm air free from any
ducting or obstacles. Also the air intake should be
free.
•
Keep sufficient distance between the heater and any
obstruction , in connection with safety and access for
service and maintenance. Pay particular attention to
any flammable materials. Please take into account
the possibility to open the door of the heater for the
necessary service and maintenance work . Make
sure the air flow to and from the heater is unhindered. Any obstacles should be a minimum
of 5 metres away from the front of the heater.
•
The heater can be installed horizontally or on an angle of maximum 45 degrees downwards.
•
The heaters type 10 and 20 are provided with 2 off M10 threaded sockets as fixing points
(see the dimension diagram).
•
The types 30 and 40 have in the middle a M10 socket and also 4 sockets on the top corners
of the heater
•
The types 50 and 60 have on the top and bottom 4 M10 sockets. (see drawings)
•
Use preferably the Winterwarm suspension kits.
•
Make sure that after fitting, there is no mechanical tension on any connecting gas or electric
supplies.
•
If the heater is installed with the air stream vertical downwards the maximum suspension
height is 8 meters. Otherwise the warm air will not reach the floor.
Attention:
See the application-restrictions in this manual (Chapter 4) for further installation restrictions.
m
in
2
50
10 t/m 30 min. 500 mm
40 t/m 60 min 660 mm