14
4J
Is heat pump’s hydraulic connection
correct? Check using the flow schema.
4I
Water level in compensator reservoir
not
visible?
Indicative of leak in the intermediate
circuit/ non-return valve defective
4H
Circulating pump for tank heating defec-
tive / incorrectly connected?
4G
Intermediate circuit pump defective /
incorrectly connected?
4F
Ventilator defective / incorrectly connect-
ed?
yes
Repair / replace.
Replace non-return valve.
Fix leak.
Rectify.
no
no
yes
yes
no
no
Repair / replace.
yes
no
Repair / replace.
yes
Continue to page 15