Compressor thermal protector tripped
INFO
Thermal
protector
resets
automatically after cool-
ing down (at least 30 minutes).
Then start the heat pump.
Measure the operating currents: Set value: 4.8 – 8.2 A in
L3 phase if Q1 contactor is engaged.
1B
Fault in the circuit
Remedy:
Find and eliminate the fault using the circuit
diagram
1C
Compressor defective
Test:
Rated current 4.8 – 8.2 A in L3 phase if Q1 contactor is
engaged.
Remedy:
Have repair carried out by experienced refrig-
eration technician.
1
Heat pump will not start up although tank temperature is
below rated temperature and dry running protection level
is adhered to (
3)