CHANGING THE FUEL TYPE

****  CAUTION  ****  

EQUIPMENT DAMAGE - Do not make any fuel adjustments 
or governor adjustments until all pressure readings are in 
compliance with specifi cation.  See fuel pressure charts (tables 
1, 2, and 3).

These engine/generator sets are very easy to convert between 
LP or NG.  As the engine timing is controlled by the ECU on the 
engine you only need to tell it what fuel you want to operate on.  
A small rocker switch has been provide on the underside of  the 
engine control cabinet (see ref  L on Page 13) for this purpose.  

Opening the rocker switch will tell the ECU mounted on the 
engine that you are operating on NG Fuel.  Closing the rocker 
switch will tell the ECU that the fuel being supplied is LP.  The 
Advance Power Controller has an idicator light for LP.  When this 
light is lite the engine is set-up for LP, when the LP light is out the 
engine is set up for NG. The ECU will then reprogram the engine 
to operate on the proper fuel.

GENERATOR SPECIFICATIONS

GR150P4-A
 

Stanford Newage Model#  UCI274G1J

 

06 Winding (Single phase 4 lead generator)

 

Winco Part Number  

350004-120

 Voltage 

Regulator 

 AS440

 Rotor 

Resistance 

 1.69 

ohm

 Stator 

Resistance 

 0.004 

ohm 

 

Excitor Stator Resistance  20.0 ohm

 

Excitor Rotor Resistance  0.182 ohm

GR150P4-D/J/L

 

Stanford Newage Model#  UCI274G1L

 

311 Winding (Three phase 12 lead reconnectable)

 

Winco Part Number  

350004-107

 Voltage 

Regulator 

 AS440

 Rotor 

Resistance 

 1.69 

ohm

 Stator 

Resistance 

 0.01 

ohm 

 

Excitor Stator Resistance  20.0 ohm

 

Excitor Rotor Resistance  0.182 ohm

GENERATOR  REPLACEMENT PARTS

The following list of replacemnt parts apply to all four generator 
models listed for these generators:

Description 

  Stanford 

Part 

#

Automaic Voltage Regulator 

E000-24403

 

  Winco Part # 

 

350818-2

Bearing  UCI227   

 

051-01049

Rectifi er Service Kit 

 

RSK-2001

     Comprises of
 

6 Diodes with Surge Suppressor

 

 

Содержание GR150P4 Series

Страница 1: ...GR150P4 DSE7310 INSTALLATION AND OPERATORS MANUAL LP NG GENERATOR SYSTEM...

Страница 2: ...________ SERIAL NUMBER____________________________ PURCHASE DATE____________________________ DEALER____________________________________ TABLE OF CONTENTS INTRODUCTION 2 GUIDE TO PRODUCT SAFETY 3 BASIC...

Страница 3: ...the earth 2 FIRE HAZARD Natural gas and L P present a hazard of possible explosion and or fire a Do not smoke or use open flame near the generator set b Keep a fire extinguisher nearby and know its p...

Страница 4: ...for a quote 2 ENGINE GENERATOR GR150P4 The engine generator set consists of a PSI8 8 Liter Turbocharged Aftercooled V 8 industrial liquid cooled engine equipped to run on L P N G fuel The engine oper...

Страница 5: ...oil level frequently as specified in the engine manual The engine manufacturer has established an excellent worldwide engine service organization engine service is available from a nearby authorized d...

Страница 6: ...the installation cost of fuel runs The information in this manual is offered to assist you in providing the proper fuel for your engine However this information is only provided to inform you of the...

Страница 7: ...e most common cause for inoperative systems is an inadequate or incorrect fuel pressure Power and performance of the engine is in direct relation to the correctness of the fuel system Shown below is a...

Страница 8: ...the correct oil and keeping the crankcase full cannot be over emphasized Failure to use the proper oil and keep the crankcase properly filled will cause excessive engine wear and shorten its useful l...

Страница 9: ...HEATER A three stage battery charger is provided standard for all 12 volt standby systems The standard charger is an Automatic Battery Charger Maintainer This Charger has three rates of charging Durin...

Страница 10: ...feeds have already been wired into the upper lugs Please refer to the circuit breaker installed on your unit for breaker lug capacities and proper torque specifications To select the proper conductor...

Страница 11: ...in terminal labeled 1 is Battery Negative and the wire in the terminal labeled 23 is your Remote Start lead Closing these two leads together will signal the DSE 7310 to go into an auto start mode and...

Страница 12: ...NTROL PANEL LAYOUT A USB PROGRAMMING PORT USB port for computer interface Used for programming the DSE7310 controller B DSE7310 CONTROLLER See controller explanation C Emergency Stop Switch When depre...

Страница 13: ...e remote start signal has been lost You must use the STOP RESET or AUTO button to stop the unit once you have started it in manual mode CAUTION IF THE POWER FAILS WHILE RUNNING IN THE MANUAL MODE THE...

Страница 14: ...send information signals to the DSE7310 via the CAN connections to indicate oil pressure water temperature etc for the display on the engine control All shutdown functions are also controlled by the...

Страница 15: ...p engine genset ENGINE CRANKS BUT WILL NOT START 1 Improper fuel pressure being delivered to unit 2 Fuel supply shut off 3 Fuel tank empty 4 Defective spark plug 5 Defective engine ignition module 6 D...

Страница 16: ...ngine is set up for LP when the LP light is out the engine is set up for NG The ECU will then reprogram the engine to operate on the proper fuel GENERATOR SPECIFICATIONS GR150P4 A Stanford Newage Mode...

Страница 17: ...closing X X Leak check fuel lines X X Check air inductionfor leaks X X X X X Check manifold for vacuum leaks X X X X X DrainVaporizer oil build up Engine Exhaust System Inspect exhaust manifold for le...

Страница 18: ...21 psi idle 6 psi 1000 rpm 6 psi 1000 rpm 6 psi 1000 rpm 5 psi 1000 rpm 5 psi 1000 rpm 18 psi 2000 rpm 18 psi 2000 rpm 18 psi 2000 rpm 15 psi 2000 rpm 15 psi 2000 rpm Coolant Capacity Engine 3 5 qts 4...

Страница 19: ...to 1 1 2 inches below the filler neck seat when the coolant is cold WARNING EQUIPMENT DAMAGE Never remove the radiator cap when the engine is hot and never add coolant to any engine that has become ov...

Страница 20: ...20 4300 00 60706 244 THREE PHASE AC WIRING HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS...

Страница 21: ...21 4300 00 60706 244 THREE PHASE AC WIRING DELTA SINGLE PHASE AC WIRING SINGLE PHASE 120 240 VOLTS THREE PHASE DELTA 120 240 VOLTS...

Страница 22: ...22 4300 00 60706 244 ENGINE CONTROL SCHEMATIC...

Страница 23: ...Type THHW THW 2 RHW RHW 2 THHN RHW THWN 2 RHH THHW THW THHW THW 2 THHW THW RHW 2 USE 2 THWN XHHW XHH XHHW SIZE AWG THWN XHHW XHH XHHW USE ZW XHHW 2 ZW 2 OR kcmil USE XHHW 2 ZW 2 44 50 8 35 41 57 68 6...

Страница 24: ...months or 1000 hours which ever occurs first from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of impl...

Отзывы: