38
Advanced Settings--
Special access
required. Contact
Wine Guardian
Service Department
for access code
Setting 8
P
ress “Mode” button to advance to Setting 8.
Press the
“
up
”
or
“
down
”
arrow buttons to
adjust number to the access code. Press
“Mode” button to continue onto
Setting 9
through 19.
Compressor anti-
short cycling time
Setting 9
Press “Mode” button to
advance to Setting 9.
Press the “Up” or “Down” arrow buttons to
adjust to the desired time in one-minute
increments. Maximum is 10 minutes,
minimum is 0 minutes.
Compressor anti-short cycling time is the
amount of allowable time between compressor
stop and restart. Rapid start/stop of compressors
can cause premature failure. Factory default is 5
minutes.
WINE GUARDIAN DOES NOT
RECOMMEND SETTINGS LOWER THAN
FACTORY DEFAULT.
Set up remote sensor
or thermostat
Setting 10
Press “Mode” button to advance
to Setting 10.
Press the “Up” or “Down” arrow buttons to
adjust to the desired setting.
rS = Remote sensor
rI = Remote interface
LI= Local interface
–
Through-the-wall unit
only
A = Averaging
–
Jumper position within
sensors must be adjusted. See page 35.
Room sensor
calibration
Setting 15
Press “Mode” button to advance to Setting 15.
Press the “Up” or “Down” buttons to adjust to
the desired set point. Maximum setting is +5,
minimum setting is -5. Factory default is zero
(0). Sensor calibration setpoint changes the
actual display reading (temperature only) by
the value of this setting.
Example: Sensor reading = 55 Deg F
Setting 15 set to +4
Display reading = 59 Deg F
Содержание D0200
Страница 12: ...12 Overview Illustration of the Wine Guardian Unit Fig 1 Fig 2...
Страница 13: ...13 Overview Illustration of water cooled system Fig 3 Fig 4...
Страница 14: ...14 Wiring diagrams D025 and D050 Fig 5...
Страница 15: ...15 Wiring diagram D088 and D200 Fig 6...
Страница 16: ...16 Wiring diagram water cooled D025 and D050 Fig 7...
Страница 17: ...17 Wiring diagram water cooled D088 and D200 Fig 8...