Operation Manual / Technical information 
 
 

Smoke control unit 

Type: 

WSC 308 01 

 

 

Table of contents: 

 
Safety information 
 
Operating elements / diagnosis LED's / fuse review 
 
Technical function description 
 
Technical data 
 
Installation and assembly 
 
Cable lengths table 
 
Cable plan 
 
Wiring diagram 
 
Start-up and test run 
 

 

CH:      WindowMaster AG

 

 

  +41 (0) 62 289 22 22

 

D:         WindowMaster GmbH

 

 

  +49 (0) 5221 6940 500

 

GB:      WindowMaster Control Systems Limited

 

 

  +44 (0) 1536 510 990

 

Head office:          WindowMaster A/S

 

 

  

 

+45 45 67 03 00

 

Skelstedet 13

 

2950 Vedbæk

 

Denmark

 

 

www.WindowMaster.com

 

Содержание WSC 308 01

Страница 1: ...mation Operating elements diagnosis LED s fuse review Technical function description Technical data Installation and assembly Cable lengths table Cable plan Wiring diagram Start up and test run CH Win...

Страница 2: ...system is exclusively designed for the automatic closing of smoke extraction systems windows flaps or doors Always check that your system meets the valid regulations Pay particular attention to the op...

Страница 3: ...tches Dead man s control Diagnosis LEDs Trip following a malfunction N e t z L E D Motor Battery R e s e t S H E C L O S E D Vent OPEN display 120mA Wind rain Manual detector Autom detector External v...

Страница 4: ...oke control unit and the red LED in the break glass unit are lit The yellow malfunction LED in the break glass unit flashes The green operating LED s extinguish Resetting a trip caused by high tempera...

Страница 5: ...the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped potential free contact in the sensor switches The ventilation functions ar...

Страница 6: ...ction by using special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break glass unit All ventilation functions...

Страница 7: ...ns screw terminal plug screw terminals 0 5 2 5sqmm Motor screw terminal 0 5 10sqmm Cable monitoring automatic detectors detector circuit with active end module break glass unit detector circuit with e...

Страница 8: ...s Also the green operating LED is still lit to indicate the absence of a fault A malfunction message has priority SW 1 2 ON The transmission of the alarm message alarm malfunction module 1 is interrup...

Страница 9: ...terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded smoke control units to the break glass unit c...

Страница 10: ...the smoke control unit and affix by means of the 4 holes in the building structure Ensure that suitable fastening material is available Note Place sealing washers plastic or similar between the housi...

Страница 11: ...ke ventilation system actuator is part of the system component electric motor actuation and does not belong to the electrical installation We recommend in all cases to discuss the type of cable routin...

Страница 12: ...Smoke control unit Type WSC 308 01 12 Cable plan...

Страница 13: ...Smoke control unit Type WSC 308 01 13 WSA 435 Standard wiring diagram...

Страница 14: ...Smoke control unit Type WSC 308 01 14 WSA 435 Various wiring diagrams...

Страница 15: ...Smoke control unit Type WSC 308 01 15 WSA 435 Various wiring diagrams...

Страница 16: ...ally with an approx 3 mm spacing from the housing edge and firmly press down to the housing bottom b Plug the red connection cable to the and the blue connection to the flat plug of the smoke control...

Страница 17: ...will automatically close after 2 minutes e Test the smoke trip and reset close as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow battery LED is OFF T...