Smoke control unit 

– Type: WSC 308 01  

 

Safety information WSC 308 01 

 
 
 

Attention! 
Adherence to the following information is mandatory:

 

 

Only allow correspondingly trained, qualified  
and skilled personnel to carry out installation work.  
 
Reliable operation and the avoidance of  
damage and hazards is only guaranteed if  
installation and settings are carried out carefully 
in accordance with these instructions.  
 
Check the technical data on the system plate.  
 
Hazards to persons ensuing from flaps and  
wings operated by electric motors.  
 
The forces occurring in the automatic mode can  
be such that parts of the body could get crushed.  
When opened, actuators could protrude into the  
room.  
For this reason, measures have to be taken  
prior to starting up the actuators which exclude  
the danger of injury.  
 
With wings tilting inwards or outwards, the wing  
must be protected from hinging down once the  
actuator is unhooked (e.g. for window cleaning).  
For safety reasons we recommend the use of  
catching shears.  
 
In the event that wings or flaps are subjected to  
high wind loads, we recommend to connect the  
central control unit to a wind detector which will  
automatically close the flaps.  
 
The fastening methods are exclusively intended  
for the intended use for which they are designed  
The manufacturer does not assume any liability  
for possible damage resulting from inappropriate  
use.  
 

230V AC  dangerous voltage  

Can cause death, severe injury or considerable  
damage to assets.  
The connection of the control system is reserved  
for qualified personnel.  
Disconnect all poles of the unit from the supply  
voltage prior to opening, installation or  
assembling. Adhere to the VDE regulations. 
 

Field of application  

The central control system is exclusively designed  
for the automatic closing of smoke extraction  
systems, windows, flaps or doors.  
Always check that your system meets the valid  
regulations.  
Pay particular attention to the opening cross section,  
the opening time and opening speed. The cable cross 
 sections depend on the cable length and current  
consumption (amperage).  
 

Maintenance work  

Where devices are used in smoke and heat  
extraction systems, ensure that they are checked,  
maintained and, if necessary, repaired at least once  
per year. 
Remove all soiling from the devices,  
check the fastening and clamping screws for firm  
seating. Trial run the entire system.  
Defective devices may only be repaired in our factory.  
Only use original spare parts.  
The supplied accumulators are subject to regular  
checks and must be replaced every 4 years.  
 

Cable routing and electrical connection  

Fuse the 230V AC power supply cable separately on  
site. 

Leave the insulation of the power supply  

cable in place up to the mains terminal.  

Adhere to the DIN and VDE regulations (Germany)  
or equivalent in your country.  
Establish the cable types, if necessary, with the local  
approval bodies or the fire protection authority.  
Do not conceal flexible cables. Junction box  
must be accessible for maintenance purposes.  
Disconnect all poles of the mains voltage and the  
accumulators prior to starting maintenance work or  
making changes to the system.  
Secure the system to prevent unintentional switching  
on again.  
Design cable types, lengths and cross sections in  
accordance with the technical information.  
Route all low voltage cables (24V DC) separate from  
the power current cables.  
 

Manufacturer's declaration  

The devices have been inspected and manufactured  
in accordance with the European directives.  
A corresponding manufacturer's declaration is  
available.  
You are only authorised to use the devices if a  
conformity declaration is issued for the entire system.  
 

 

Содержание WSC 308 01

Страница 1: ...mation Operating elements diagnosis LED s fuse review Technical function description Technical data Installation and assembly Cable lengths table Cable plan Wiring diagram Start up and test run CH Win...

Страница 2: ...system is exclusively designed for the automatic closing of smoke extraction systems windows flaps or doors Always check that your system meets the valid regulations Pay particular attention to the op...

Страница 3: ...tches Dead man s control Diagnosis LEDs Trip following a malfunction N e t z L E D Motor Battery R e s e t S H E C L O S E D Vent OPEN display 120mA Wind rain Manual detector Autom detector External v...

Страница 4: ...oke control unit and the red LED in the break glass unit are lit The yellow malfunction LED in the break glass unit flashes The green operating LED s extinguish Resetting a trip caused by high tempera...

Страница 5: ...the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped potential free contact in the sensor switches The ventilation functions ar...

Страница 6: ...ction by using special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break glass unit All ventilation functions...

Страница 7: ...ns screw terminal plug screw terminals 0 5 2 5sqmm Motor screw terminal 0 5 10sqmm Cable monitoring automatic detectors detector circuit with active end module break glass unit detector circuit with e...

Страница 8: ...s Also the green operating LED is still lit to indicate the absence of a fault A malfunction message has priority SW 1 2 ON The transmission of the alarm message alarm malfunction module 1 is interrup...

Страница 9: ...terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded smoke control units to the break glass unit c...

Страница 10: ...the smoke control unit and affix by means of the 4 holes in the building structure Ensure that suitable fastening material is available Note Place sealing washers plastic or similar between the housi...

Страница 11: ...ke ventilation system actuator is part of the system component electric motor actuation and does not belong to the electrical installation We recommend in all cases to discuss the type of cable routin...

Страница 12: ...Smoke control unit Type WSC 308 01 12 Cable plan...

Страница 13: ...Smoke control unit Type WSC 308 01 13 WSA 435 Standard wiring diagram...

Страница 14: ...Smoke control unit Type WSC 308 01 14 WSA 435 Various wiring diagrams...

Страница 15: ...Smoke control unit Type WSC 308 01 15 WSA 435 Various wiring diagrams...

Страница 16: ...ally with an approx 3 mm spacing from the housing edge and firmly press down to the housing bottom b Plug the red connection cable to the and the blue connection to the flat plug of the smoke control...

Страница 17: ...will automatically close after 2 minutes e Test the smoke trip and reset close as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow battery LED is OFF T...

Отзывы: