Smoke control unit 

– Type: WSC 308 01  

11 

 

Electrical cables 

 
 

Ensure that the electrical cables are always routed according to the valid national and local regulations of the individual 
country. 

 

Maintaining the cable functions 

The sample cable system directive (MLAR) in its current version is decisive for the type of cables and their corresponding 
way of routing. In most of the German provinces, MLAR has been introduced as Technical Construction Regulation. 
Various revisions of the MLAR as Technical Construction Regulation are valid in the individual provinces. Due to the fact 
that the requirements with regard to the conductors for smoke control systems contained in the individual versions differ 
considerably, different conductor requirements result for the individual provinces. MLAR is based on the state-of-the-art of 
the year 2000 (Revision: 06/2001). In this directive, for the first time a differentiation is made between machine operated 
and natural smoke ventilation systems. For natural smoke extraction systems it is sufficient to maintain the function 
according to classification E30. These cables must be checked and approved in accordance with DIN 4102 Part 12. Route 
the cables in conformity with the instructions of the cable manufacturers using the corresponding fastening materials. 
The maintenance of the function for the smoke ventilation cables is not required if all cable paths are monitored by the 
smoke detector and when the smoke and heat detection system opens as a result of the automatic detector tripping. 
 
Concealed installation is not an approved type of installation to maintain the function in accordance with DIN 4102 Part 12. 
The function is also only securely maintained by cables of class E30, or the room is monitored by smoke detectors. 
 
The cable 

network for smoke ventilation systems („Cable system“) ends at the interface (junction box) for the actuator! 

The flexible, heat resistant connection cable of the smoke ventilation system actuator is part of the system component 
‚electric motor actuation' and does not belong to the electrical installation! 
 

We recommend in all cases to discuss the type of cable routing with the competent fire fighting authorities. 
Independent of the fact whether or not the respective MLAR is introduced in the corresponding province as 
Technical Building Regulation, we recommend to point out the technical possibilities and the state-of-the-art of 
MLAR 2000. 

 

Cable length table 

For determining the maximum permissible cable lengths between the smoke control unit and the actuators, taking into 
account the specified cables cross sections, please refer to the following table: 

Maximum motor current: 8A

  

Note

: Be aware of the overall capacity/rating of the smoke control unit! 

 
Maximum cable length: (always routed from the central control panel to the last connection socket) 
Actuating current: Sum of all motor currents per group module 
 

Note: 

Do not use the green/yellow wire! 

 

Per motor supply line, 3 wires are required (2 wires current carrying /1 wire for monitoring) 

 

Cross section 

3 wire 

5 wire 

3 wire 

5 wire 

3 wire 

3 wire 

 

1,5 mm² 

1,5 mm² 

2,5 mm² 

2,5 mm² 

4 mm² 

6 mm² 

Actuator current in A 

 

(2 parallel wires) 

 

(2 parallel wires) 

 

 

84,00 m 

168,00 m 

140,00 m 

280,00 m 

224,00 m 

336,00 m 

42,00 m 

84,00 m 

70,00 m 

140,00 m 

112,00 m 

168,00 m 

28,00 m 

56,00 m 

46,67 m 

93,33 m 

74,67 m 

112,00 m 

21,00 m 

42,00 m 

35,00 m 

70,00 m 

56,00 m 

84,00 m 

16,80 m 

33,60 m 

28,00 m 

56,00 m 

44,80 m 

67,20 m 

14,00 m 

28,00 m 

23,33 m 

46,67 m 

37,33 m 

56,00 m 

12,00 m 

24,00 m 

20,00 m 

40,00 m 

32,00 m 

48,00 m 

10,50 m 

21,00 m 

17,50 m 

35,00 m 

28,00 m 

42,00 m 

(The information is valid for ambient temperatures of 25°C) 
 

Formula for the calculation of the maximum cable length 

Maximum permissible voltage drop in the cable UL : 

2 Volt 

 
max. cable length = 

permissible voltage drop (UL) x conductivity of copper (56) x cable cross section (A) 

max. actuator current total (I) in amps x 2 
 

Permissible cable length for the break glass unit supply cable when using......4x2x0.8mm:     

up to 200m

 

The motor connection cable length to the junction box (or control module) must not exceed 

10 m.

 

Содержание WSC 308 01

Страница 1: ...mation Operating elements diagnosis LED s fuse review Technical function description Technical data Installation and assembly Cable lengths table Cable plan Wiring diagram Start up and test run CH Win...

Страница 2: ...system is exclusively designed for the automatic closing of smoke extraction systems windows flaps or doors Always check that your system meets the valid regulations Pay particular attention to the op...

Страница 3: ...tches Dead man s control Diagnosis LEDs Trip following a malfunction N e t z L E D Motor Battery R e s e t S H E C L O S E D Vent OPEN display 120mA Wind rain Manual detector Autom detector External v...

Страница 4: ...oke control unit and the red LED in the break glass unit are lit The yellow malfunction LED in the break glass unit flashes The green operating LED s extinguish Resetting a trip caused by high tempera...

Страница 5: ...the setting potentiometer is on the right hand stop Wind rain CLOSE The actuators close when the wind rain sensor has tripped potential free contact in the sensor switches The ventilation functions ar...

Страница 6: ...ction by using special software ASV CLOSE When ASV CLOSE is tripped all actuators automatically CLOSE An acoustic alarm signal sounds continuous sound in the break glass unit All ventilation functions...

Страница 7: ...ns screw terminal plug screw terminals 0 5 2 5sqmm Motor screw terminal 0 5 10sqmm Cable monitoring automatic detectors detector circuit with active end module break glass unit detector circuit with e...

Страница 8: ...s Also the green operating LED is still lit to indicate the absence of a fault A malfunction message has priority SW 1 2 ON The transmission of the alarm message alarm malfunction module 1 is interrup...

Страница 9: ...terminal for potential free transmission to the BMS panel etc 2 pole connection terminal for 2 wire BUS cable for the feedback of malfunctions in cascaded smoke control units to the break glass unit c...

Страница 10: ...the smoke control unit and affix by means of the 4 holes in the building structure Ensure that suitable fastening material is available Note Place sealing washers plastic or similar between the housi...

Страница 11: ...ke ventilation system actuator is part of the system component electric motor actuation and does not belong to the electrical installation We recommend in all cases to discuss the type of cable routin...

Страница 12: ...Smoke control unit Type WSC 308 01 12 Cable plan...

Страница 13: ...Smoke control unit Type WSC 308 01 13 WSA 435 Standard wiring diagram...

Страница 14: ...Smoke control unit Type WSC 308 01 14 WSA 435 Various wiring diagrams...

Страница 15: ...Smoke control unit Type WSC 308 01 15 WSA 435 Various wiring diagrams...

Страница 16: ...ally with an approx 3 mm spacing from the housing edge and firmly press down to the housing bottom b Plug the red connection cable to the and the blue connection to the flat plug of the smoke control...

Страница 17: ...will automatically close after 2 minutes e Test the smoke trip and reset close as described under 5 f Refit the mains fuse g The green mains and operating LED s are ON the yellow battery LED is OFF T...