29
12.4.3 Usage of wind/rain sensors - WLA 33x
Usage of wind/rain sensors WLA 33x with motor groups (MG):
The used input e.g. S1
X10.5 is configured to “Control motor groups”,
the groups are chosen.
Then, in the menu “Active function in controlled motor groups” the
function “Safety” is selected.
Then, a function for the motor group when inactive can be selected
“Inactive function in the controlled motor groups”.
By each motor group it is possible to define the max opening for
“Safety”, meaning it is possible to allow windows and louvers inside
the building to open d
espite “Safety” (wind/rain).
Facade windows, which are allowed to open e.g. 10%, to open
despite it rains.
Input shall be configured in:
Configuration of local input
1.
In the motor groups configure the input with the function “Safety“.
2. Configure the motor groups when anything else than close (0%) is
desired.
Note: motor groups also receive “Safety” signals from the smoke
zones they are associated with, see below for further information.
Local output
On the WCA 3CP card the MotorController always has one output (X9.1 / X9.2) for fault signal (not configurable output).
12.5.1 Numbering of local output
All local outputs on the WCA 3CP card are numbered.
The number of the output depends on its location on the card - see overview below.
As the output (fault signal) on the WCA 3CP card cannot be configured it is not numbered.
MotorController with motor line and input cards