S1
X11
For connection of master / slave connection via WSK-
Link™.
Data:
11.1 24V IN
11.2 Communication IN
11.3 0V IN
A master-slave connection via WSK-Lin
k™ enables signals to be distributed between several MotorControllers
or/and the MotorController may be used as slave in a 120V UPS smoke ventilation system.
On the master MotorController, either use input X5 or X6 for the master-slave connection. On the slave
MotorController, the connection is done via X11.
It is possible to connect several MotorControllers in a master slave connection. However, the max total number
of MotorControllers on the WSK-
Link™ must not exceed 10 units. The max cable length between two units must
not exceed 200m, see examples below, for how to connect the MotorControllers.
Sharing of signals from weather station
Example 1
Example 2
MotorController #2 and #3 are both master and salve MotorControllers.
See under X10 for connection of weather station
WCC 3xx as slave in a 120V UPS supplied smoke ventilation system
Example 1
Example 2
See WSC 3xx instruction for further information about connection to smoke ventilation system.