26
Motor line
Actuators are to be connected on the motor lines. ±24V standard actuators and actuators with MotorLink
®
can be connected to
all motor lines, but a motor line can only be connected to one type of actuators
– either ±24V standard or MotorLink
®
actuators.
12.2.1 Motor line - numbering
All motor lines are numbered and they are all to be configured.
12.2.2 Motor line - configuration
Press ”Motor line” and the overview of the motor lines in the MotorController is shown.
Overview
configuration motor lines
One motor line is marked with a
as the configuration is missing.
All motor lines are configured.
Both actuators outputs on the main control card as well as the four or eight actuators outputs on the motor line card
– if such is
connected
– are to be configured:
- Motor lines with actuators connected
are to be configured in “motor group
-
- Motor lines with no actuator connected
are set to “none“
Since ±24V actuators and actuators with MotorLink
®
are not to be configured exactly the same way, both type of actuators are
listed below with the settings that are to be configured for each actuator type. Be aware that both types of actuators can be
connected to the MotorController at the same time.
For ±24V actuators the full chain length is define as a runtime of 60 seconds. When the MotorController is to be 100% sure that
the windows ae 100% open or closed, the chain length is run twice (120). This can have an influence when configuring the a
sequence control.
Motor lines configuration
±24V actuator configuration
The ±24V actuators can be configured in:
1.
Output mode: informs the type of the actuator selected
2.
Motor configuration
3.
Stroke time
4.
Motor group
The appendix contains all the menus that can be configured - see
appendix for detailed explanation.