A solar heating station can be connected to the water heater
(unit with heat exchangers in "solar" mode). In this configuration,
the water heater only operates when it receives a signal from the
solar station. After receiving the signal, the heat pump will start if
heating is required and if the operating and air ranges allow it. If
the heat pump can not start, the electrical backup will take over
if it is in an operating range (permanent or programming).
Note: A solar thermal station signal and a PV signal can not be
connected simultaneously.
The solar station is wired to the
B1
and
B2
terminals of the
customer terminal block.
9.3. Connection to a solar station.
Power supply
Solar connection
contact 230V ~
A1
A2
B1
B2
C1
C2
9.4. Installing the solar control sensor
Remove the plug and
foam from the housing
next to the connections
of
the
internal
heat
exchanger.
Push
the
temperature
sensor through the plug
(the plug has been drilled
for this purpose).
Insert the sensor into the
chute ensuring that it is
well positioned at the
bottom of the housing.
Put the foam back and
insert the plug back into
the product
❶
❷
❸
❹