Installation
Use
Maintenance
Warranty
4. Installation in semi–ducted configuration (1 discharge duct).
9
Unheated location at temperatures above 5°C and isolated from the
heated rooms of the house.
9
"Ducting" setting to be set to "Interior/Exterior"
9
Recommended location = underground or semi-underground, room where
the temperature is higher than 10°C all year round.
The de-pressurising of the location by the outside air discharge generates air inlets through the
woodwork (
doors and windows
). Install an air inlet (Ø 160mm) in relation to the outside one to
avoid sucking air from the heated space.
In winter, the air entering through the air inlet can cool the room.
Leave a space of 500mm in front of the electrical equipment and 300mm in front of the hydraulic
equipment so that the water heater is accessible for its periodic servicing.
670mm
mini
Examples of locations:
•
Garage: recovery of free calories released by the car engine when it is shut
down after operation, or other household appliances in operation.
•
Laundry room: Dehumidification of the room and recovery of lost calories
from washing machines and dryers.