background image

3225-00

60706-241

3.   Make sure the drive shaft (tumbling bar) is assembled 

with its universal joint knuckles “synchronized,” as il-

lustrated in Figure 7. If knuckles are not synchronized, 

the bar will chatter when rotating, which will cause the 

generator output voltage to flicker. Drive shafts shipped 

new from Winco are always synchronized and tethered 

so they can not be taken apart. 

DANGER: Personal Injury

POWER TAKE-OFF MUST BE DISENGAGED AT THIS TIME.

4.   Couple the tractor to the generator with the drive shaft 

(tumbling bar). Couple the tumbling bar to the genera-

tor input shaft first, then to the power take-off shaft. 

Check alignment, tractor, power take-off shaft (tumbling 

bar), and generator input shaft should form a straight 

(or nearly straight) line, with less than 5° misalignment 

between the shafts. Misalignment will cause generator 

output voltage to flicker.

WARNING - Personal Injury

Make sure that all tumbling bar lock pins are engaged and 

that all safety shields are in place before operating the PTO 

generator

.

5.   Make sure no binding exists in generator or gear box. If 

binding is found, locate the cause and correct it before 

proceeding.

6.  Make sure that the electrical loads to be driven by the 

generator will not draw more current than the ratings of 

the generator receptacle or cord set which will supply 

the current.

7.   Check all electrical connections in the system to be 

energized by the generator. Make sure the connections 

are correct and are tight.

8.   Make sure all loads are turned off. Do not start the gen-

erator under load.

GENERATOR STARTING 

PROCEDURE

1.  Set the manual transfer to mid or normal (up)  

 

position.

2.    With the power take-off drive disengaged, start the en-

gine which will drive the generator. Run the engine long 

enough to warm it up before proceeding, so that it will 

run smoothly and achieve full power under generator 

load.

3.   With engine idling, engage the power take-off drive.

4.   Watch the voltmeter on the generator and slowly 

increase engine speed until the output reaches approxi-

mately 240 to 245 volts, in green portion of voltmeter 

scale. 

CAUTION:  Equipment Damage

Most  electrical equipment in North America operates sat

-

isfactorily at frequencies between 59 and 61 Hz (cycles per 

second).  Operating the generator at frequencies outside 

that range may cause damage to the generator and/or to 

electrical equipment driven by the generator.

5.  Plug 4 wire load cord set into receptacle.  Place  

transfer switch in the emergency position.

6.  Place the load circuit breaker in the “on” position.  If 

the breaker trips, move manual transfer switch to “off” 

or normal position.  Check for short circuit or grounded 

connection in the load cable to the double throw switch 

and repair.  A breaker that trips from overload or short 

circuit must be reset by moving to “off” before reclosing.

7.   With engine and generator running smoothly, switch on 

the electrical load while watching the voltmeter. Read-

just engine throttle to keep generator output under load 

at 240V (in green portion of voltmeter scale). If engine 

is equipped with speed governor, it may automatically 

readjust the throttle as the load changes and keep the 

generator output at the proper level. However, some 

governors are not sensitive enough to maintain proper 

output under changing load, and in such cases the 

throttle will have to be manually readjusted.

NOTE: Equipment Damage

If the load includes motors turn them on one at a time, high

-

est starting current motor first, next highest second, etc

8.  The return of normal power will be indicated by the  

lamp on the front of transfer switch; (applicable only 

when the transfer switch is equipped with indicating 

lamps or your electrician has installed them).  After suffi

-

cient time to assure that power restoration isn’t tempo-

rary, return the transfer switch to normal power (10 - 20 

minutes).

9.  Place the alternator circuit breaker in “off” position.  Do 

not remove plug before opening the breaker.

Page 6

60706-180

0310-00

3. Make sure the drive shaft (tumbling bar) is assembled with

its universal joint knuckles “synchronized,” as illustrated in

Figure 7. If knuckles are not synchronized, the bar will chat-

ter when rotating, which will cause the generator output volt-

age to flicker. Drive shafts shipped new from Winco are al-

ways synchronized and tethered so they can not be taken

apart.

DANGER: Personal Injury

POWER TAKE-OFF MUST BE DISENGAGED AT THIS TIME.

4. Couple the tractor to the generator with the drive shaft (tum-

bling bar). Couple the tumbling bar to the generator input

shaft first, then to the power take-off shaft. Check align-

ment, tractor, power take-off shaft (tumbling bar), and gen-

erator input shaft should form a straight (or nearly straight)

line, with less than 10° misalignment between the shafts.

Misalignment will cause generator output voltage to flicker.

CAUTION:

Make sure that all tumbling bar lock pins are engaged and that

all safety shields are in place before operating the PTO

generator.

5. Make sure no binding exists in generator or gear box. If

binding is found, locate the cause and correct it before pro-

ceeding.

6. Make sure that the electrical loads to be driven by the gen-

erator will not draw more current than the ratings of the gen-

erator receptacle or cord set which will supply the current.

7. Check all electrical connections in the system to be ener-

gized by the generator. Make sure the connections are cor-

rect and are tight.

8. Make sure all loads are turned off. Do not start the genera-

tor under load.

GENERATOR STARTING

PROCEDURE

1. Set the manual transfer to mid or normal (up)

position.

2. With the power take-off drive disengaged, start the engine

which will drive the generator. Run the engine long enough

to warm it up before proceeding, so that it will run smoothly

and achieve full power under generator load.

3. With engine idling, engage the power take-off drive.

4. Watch the voltmeter on the generator and slowly increase

engine speed until the output reaches approximately 240 to

245 volts, in green portion of voltmeter scale.

5. Plug 4 wire load cord set into receptacle.  Place transfer

switch in the emergency position.

6. Place the load circuit breaker in the “on” position.  If the

breaker trips, move manual transfer switch to “off” or

normal position.  Check for short circuit or grounded

connection in the load cable to the double throw switch and

repair.  A breaker that trips from overload or short circuit

must be reset by moving to “off” before reclosing.

7.  With engine and generator running smoothly, switch on the

electrical load while watching the voltmeter. Readjust en-

gine throttle to keep generator output under load at 240V

(in green portion of voltmeter scale). If engine is equipped

with speed governor, it may automatically readjust the

throttle as the load changes and keep the generator output

at the proper level. However, some governors are not sen-

sitive enough to maintain proper output under changing

load, and in such cases the throttle will have to be manually

readjusted .

NOTE: Equipment Damage

If the load includes motors turn them on one at a time,

highest starting current motor first, next highest second,

etc.

8. The return of normal power will be indicated by the

lamp on the front of transfer switch; (applicable only when

the transfer switch is equipped with indicating lamps or

your electrician has installed them).  After sufficient time to

assure that power restoration isn’t temporary, return the

transfer switch to normal power (10 - 20 minutes).

9. Place the alternator circuit breaker in “off” position.  Do not

remove plug before opening the breaker.

10. Slowly reduce power take-off speed to a minimum and

disengage the power take-off. Some tractors have a brake

on the power take-off that stops the shaft instantly. Stop-

ping the alternator rotor instantly from rated speed may

result in a broken shaft or other drive line failures.

WARNING: Personal Injury

Never try to manually stop the generator.  Always let it

coast until it stops.

11. Shut off the engine.

12. Disconnect drive shaft (tumbling bar)

power take-off end first, then generator end.

13. Exercise PTO alternator for one hour under load at least

twice a year.

Содержание W10PTOS/A

Страница 1: ...COMPACT SERIES TRACTOR DRIVE GENERATOR W10PTOS A...

Страница 2: ...ser vice when commercial power is interrupted inaccessible or impractical This PTO unit has a cast iron gear case with a 1 3 8 6 spline 540 rpm rated input shaft unit operating speed is 515 RPM and b...

Страница 3: ...r nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxide an invisible odorless and deadly gas th...

Страница 4: ...and adjustment UNPACKING CAUTION Equipment Damage DO NOT invert generator during unpacking The Gearcase con tains oil which will leak out if inverted during unpacking Unpack the generator as follows...

Страница 5: ...ling bar C For safety the generator must be bolted to the three point hitch deck using all four mounting bolts B The foundation must be solid enough to absorb generator starting and reflected load tor...

Страница 6: ...INES FROM THE LOAD AND THE GENERATOR WHEN THE GEN ERATOR IS SUPPLYING POWER SEE FIGURE 6 Page 4 60706 180 0310 00 ELECTRICAL CONNECTIONS CAUTION Only qualified electricians should install electrical w...

Страница 7: ...OR TOO MUCH OIL CAN HARM THE EQUIPMENT See Lubrication portion of Main tenance for oil specifications Page 5 60706 180 0310 00 A properly rated and installed double throw manual power isolation transf...

Страница 8: ...e sure the drive shaft tumbling bar is assembled with its universal joint knuckles synchronized as illustrated in Figure 7 If knuckles are not synchronized the bar will chat ter when rotating which wi...

Страница 9: ...ING Equipment Damage DO NOT CLEAN THE GENERATOR WHILE IT IS RUNNING STORAGE MAINTENANCE If the generator is mounted on an off highway trailer such as the Winco trailer it should be stored in a garage...

Страница 10: ...t and replace if defective Low Speed High line loss Indicated by lower voltage at load than at generator terminals 1 Undersized overloaded 2 Defective governor 3 Low power worn engine LOW OUTPUT VOLTA...

Страница 11: ...11 3225 00 60706 241 ILLUSTRATED PARTS LIST COMPLETE ASSEMBLY...

Страница 12: ...w 7 300080 3 1 Top Cover 8 Z2568 1 Decal Danger PTO 9 300086 2 1 Drive Shaft Guard 10 98479 000 1 Decal Winco 1 11 53113 002 2 Decal Winco 12 63966 009 1 Nameplete 13 99841 003 1 Gear Case Support 14...

Страница 13: ...QTY DESCRIPTION 99839 002 1 Complete Generator End with Gear Case 19 54665 000 1 6205 2RS Bearing 26 300323 208 2 Varistor 27 300323 207 2 Diode 65 99839 112 1 45 mf Capacitor GENERATOR SPECIFICATIONS...

Страница 14: ...REF PART NUMBER QTY DESCRIPTION 1 300080 3 1 Top Cover 2 91286 001 1 20 Amp 1 Pole Circuit Breaker 3 63708 000 1 Ground Lug 4 57030 007 1 45 Amp 240 VAC Circuit Breaker 5 91370 000 1 Voltmeter 6 3000...

Страница 15: ...O WHEEL TRANSPORT DESCRIPTION PART NO 1 SUPPORT TONGUE QTY 2 300081 2 HITCH TONGUE QTY 2 300082 3 TONGUE 300083 4 AXLE QTY 2 300085 5 SUPPORT AXLE 300164 6 SUPPORT PTO SHAFT 300161 1 7 SUPPORT PTO SHA...

Страница 16: ...of incidental or consequential damages so that above limitation or exclusion may not apply to you This warranty gives you specific legal rights you may have other rights which vary from state to state...

Отзывы: