background image

7

3225-00

60706-241

A properly rated and installed double throw manual power isola-

tion transfer switch must be used with a standby generator.  The 

transfer switch isolates the load from the power line and allows 

you to safely operate your loads without endangering the power 

line repair crew.  See page 6.

 The load, connected to the normal terminals of the transfer 

switch, is energized by the normal power line when the switch is 

in the normal position.  The generator, connected to the emer-

gency terminals of the switch, furnishes power when the switch 

is in the emergency mode position.

There are two ways to install a manual transfer switch.  The first 

shown on the left side of page 6 is to install the switch between 

the watt-hour meter and the normal distribution panel. As with 

any system you must install an entrance rated breaker before the 

manual transfer switch.  The manual transfer switch must in all 

cases be equal to or greater than the rating of the entrance rated 

breaker.

The second way to install the system is to purchase and install 

an emergency distribution panel and move the circuits you wish  

to back up to the new distribution panel.  In this case the manual 

transfer switch only has to be sized to the amperage of the circuit 

breaker in the main distribution panel that is feeding it.  See the 

right hand drawing on page 6.

Before deciding which system to install, first determine which 

loads you can safely run on your PTO generator and the cost 

of  buying a large manual transfer switch versus the cost of a 

smaller switch and the additional distribution panel.

The final item that you are going to have to assemble/wire is the 

plug that will be used to connect the generator to the manual 

transfer switch.  You should have found this load plug in a small 

box when you unpacked the PTO generator.  If you need addi-

tional plugs for multiple sites you can order additional plugs from 

your Winco dealer, the part number is “300137”.

WARNING:  Personal Injury

DISCONNECT POWER BEFORE WIRING

IMPORTANT: 

 

Use copper wire only.  Do not use tinned con

-

ductors.  Sizing cable - see NEC 400-5.

CORD SIZE:  #4/4 conductor cord SO, 1.25 inch dia. max.

To assemble and wire the load disconnect plug, proceed as fol-

lows:

1.  Strip outer jacket 2-3/4”.

2.  Cut and strip leads to lengths specified for the  

 

particular plug.

3.  Disassemble cable clamp and top cover.

4.  Remove one blade at a time, insert the stripped end    

of the appropriate colored wire designated above,  

 

and tighten the set screw.

5.  Fit blades through slots in bottom cover and push  

 

down until home.  Please note:  Make sure blades  

 

are in correct slots and oriented in accordance with    

the diagram above or you will not be able to close  

 

the top cover fully.  

6.  Place top plastic cover over assembly and partially    

tighten the bakelite assembly screw.  Realign  

 

blades straight (so they fit into the top bakelite  

 

housing properly) and tighten the assembly screw.

7.  Assemble cable clamp over the outer jacket of the  

 

wire and tighten the two clamp screws. 

Special Note: 

 

For small size round (less than 3/4”) and flat cables, the 

wire clamp may be inverted.

WARNING - Personal Injury:

  

Failure to wire as instructed may cause personal injury or 

damage to device or equipment.  To be installed or checked 

by an electrician or qualified person only

.

PRE-START CHECKS

WARNING:  Personal Injury

When working on or around these generators, do not wear 

loose fitting clothing or any articles that may get caught in 

moving parts.

1.  Visually inspect the generator. Check for:

 

a   Correct mounting

 

b.   Physical damage

 

c.   Debris in cooling vents and screens (could  

 

   

cause generator to overheat).

IMPORTANT

The manufacturer recommends that, if the generator has 

been stored for any length of time, before using it, the op

-

erator remove the control box cover and cooling fan screen, 

then inspect the generator for rodent nests or other objects 

that could cause generator binding and/or overheating. See 

“Cleaning” portion of Maintenance section.

2.   Check gear case oil 

level. (See Figure 4.) 

Case should be filled with 

oil to plug marked “OIL 

LEVEL.” Fill or remove oil 

as required.  

NOTE: EITHER TOO LITTLE 

OR TOO MUCH OIL CAN HARM 

THE EQUIPMENT

See “Lubrication” portion of Main-

tenance for oil specifications.

Page 5

60706-180

0310-00

A properly rated and installed double throw manual power

isolation transfer switch must be used with a standby genera-

tor.  The transfer switch isolates the load from the power line

and allows you to safely operate your loads without endanger-

ing the power line repair crew.  See page 4.

  The load, connected to the normal terminals of the transfer

switch, is energized by the normal power line when the switch

is in the normal position.  The generator, connected to the

emergency terminals of the switch, furnishes power when the

switch is in the emergency mode position.

There are two ways to install a manual transfer switch.  The

first shown on the left side of page 4 is to install the switch

between the watt-hour meter and the normal distribution panel.

As with any system you must install an entrance rated breaker

before the manual transfer switch.  The manual transfer switch

must in all cases be equal to or greater than the rating of the

entrance rated breaker.

The second way to install the system is to purchase and install

an emergency distribution panel and move the circuits you

wish  to back up to the new distribution panel.  In this case the

manual transfer switch only has to be sized to the amperage of

the circuit breaker in the main distribution panel that is feeding

it.  See the right hand drawing on page 4

Before deciding which system to install, first determine which

loads you can safely run on your PTO generator and the cost

of  buying a large manual transfer switch versus the cost of a

smaller  switch and the additional distribution panel.

The final item that you are going to have to assembly/wire is

the plug that will be used to connect the generator to the

manual transfer switch.  You should have found this load plug

in a small box when you unpacked the PTO generator.  If you

need additional plugs for multiple sites you can order additional

plugs from your Winco dealer, the part number is “300137”.

WARNING:  Personal Injury

DISCONNECT POWER BEFORE WIRING

IMPORTANT:

Use copper wire only.  Do not use tinned

conductors.  Sizing cable - see NEC 400-5.

CORD SIZE:

#4/4 conductor cord SO, 1.25 inch dia. max.

Figure 2

To assemble and wire the load disconnect plug, proceed as

follows:

1. Strip outer jacket 2-3/4”.

2. Cut and strip leads to lengths specified for the

particular plug.

3. Disassemble cable clamp and top cover.

4. Remove one blade at a time, insert the stripped end

of the appropriate colored wire designated above,

and tighten the set screw.

5. Fit blades through slots in bottom cover and push

down until home.  Please note:  Make sure blades

are in correct slots and oriented in accordance with

the diagram above or you will not be able to close

the top cover fully.

6. Place top plastic cover over assembly and partially

tighten the bakelite assembly screw.  Realign

blades straight (so they fit into the top bakelite

housing properly) and tighten the assembly screw.

7. Assemble cable clamp over the outer jacket of the

wire and tighten the two clamp screws.

Special Note:  For small size round (less than 3/4”) and flat

cables, the wire clamp may be inverted.

WARNING:

Failure to wire as instructed may cause

personal injury or damage to device or equipment.  To be

installed or checked by an electrician or qualified person

only.

PRE-START CHECKS

WARNING:  Personal Injury

When working on or around these generators, do not wear

loose fitting clothing or any articles that may get caught in

moving parts.

1. Visually inspect the generator. Check for:

a Correct mounting

b. Physical damage

c. Debris in cooling vents and screens (could

cause generator to overheat).

IMPORTANT

: The manufacturer recommends that, if the gen-

erator has been stored for any length of time, before using it,

the operator remove the control box cover and cooling fan

screen, then inspect the generator for rodent nests or other ob-

jects that could cause generator binding and/or overheating.

See “Cleaning” portion of Maintenance section.

2. Check gear case oil level. (See

Figure 4.) Case should be filled

with oil to plug marked “OIL

LEVEL.” Fill or remove oil as

required.

NOTE

: EITHER TOO LITTLE OR

TOO MUCH OIL CAN HARM THE

EQUIPMENT.

See “Lubrication” portion of

Maintenance for oil specifications.

Содержание W10PTOS/A

Страница 1: ...COMPACT SERIES TRACTOR DRIVE GENERATOR W10PTOS A...

Страница 2: ...ser vice when commercial power is interrupted inaccessible or impractical This PTO unit has a cast iron gear case with a 1 3 8 6 spline 540 rpm rated input shaft unit operating speed is 515 RPM and b...

Страница 3: ...r nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate 3 DEADLY EXHAUST GAS Exhaust fumes from any engine contain carbon monoxide an invisible odorless and deadly gas th...

Страница 4: ...and adjustment UNPACKING CAUTION Equipment Damage DO NOT invert generator during unpacking The Gearcase con tains oil which will leak out if inverted during unpacking Unpack the generator as follows...

Страница 5: ...ling bar C For safety the generator must be bolted to the three point hitch deck using all four mounting bolts B The foundation must be solid enough to absorb generator starting and reflected load tor...

Страница 6: ...INES FROM THE LOAD AND THE GENERATOR WHEN THE GEN ERATOR IS SUPPLYING POWER SEE FIGURE 6 Page 4 60706 180 0310 00 ELECTRICAL CONNECTIONS CAUTION Only qualified electricians should install electrical w...

Страница 7: ...OR TOO MUCH OIL CAN HARM THE EQUIPMENT See Lubrication portion of Main tenance for oil specifications Page 5 60706 180 0310 00 A properly rated and installed double throw manual power isolation transf...

Страница 8: ...e sure the drive shaft tumbling bar is assembled with its universal joint knuckles synchronized as illustrated in Figure 7 If knuckles are not synchronized the bar will chat ter when rotating which wi...

Страница 9: ...ING Equipment Damage DO NOT CLEAN THE GENERATOR WHILE IT IS RUNNING STORAGE MAINTENANCE If the generator is mounted on an off highway trailer such as the Winco trailer it should be stored in a garage...

Страница 10: ...t and replace if defective Low Speed High line loss Indicated by lower voltage at load than at generator terminals 1 Undersized overloaded 2 Defective governor 3 Low power worn engine LOW OUTPUT VOLTA...

Страница 11: ...11 3225 00 60706 241 ILLUSTRATED PARTS LIST COMPLETE ASSEMBLY...

Страница 12: ...w 7 300080 3 1 Top Cover 8 Z2568 1 Decal Danger PTO 9 300086 2 1 Drive Shaft Guard 10 98479 000 1 Decal Winco 1 11 53113 002 2 Decal Winco 12 63966 009 1 Nameplete 13 99841 003 1 Gear Case Support 14...

Страница 13: ...QTY DESCRIPTION 99839 002 1 Complete Generator End with Gear Case 19 54665 000 1 6205 2RS Bearing 26 300323 208 2 Varistor 27 300323 207 2 Diode 65 99839 112 1 45 mf Capacitor GENERATOR SPECIFICATIONS...

Страница 14: ...REF PART NUMBER QTY DESCRIPTION 1 300080 3 1 Top Cover 2 91286 001 1 20 Amp 1 Pole Circuit Breaker 3 63708 000 1 Ground Lug 4 57030 007 1 45 Amp 240 VAC Circuit Breaker 5 91370 000 1 Voltmeter 6 3000...

Страница 15: ...O WHEEL TRANSPORT DESCRIPTION PART NO 1 SUPPORT TONGUE QTY 2 300081 2 HITCH TONGUE QTY 2 300082 3 TONGUE 300083 4 AXLE QTY 2 300085 5 SUPPORT AXLE 300164 6 SUPPORT PTO SHAFT 300161 1 7 SUPPORT PTO SHA...

Страница 16: ...of incidental or consequential damages so that above limitation or exclusion may not apply to you This warranty gives you specific legal rights you may have other rights which vary from state to state...

Отзывы: