OPM-132/D

TROUBLESHOOTING

Problem

Possible Causes

Won’t start

Low oil level
Fouled spark plug
Out of fuel
Start switch in OFF position
Fuel Valve turned off
Plugged fuel filter
Blown fuse in key switch

Voltage too low

AVR adjustment
Defective stator
Defective rotor (field)
Defective AVR

Circuit breaker trips

Defective load
Defective receptacle
Excessive load

Voltage too high

Engine speed is too high
AVR Adjustment

Generator overheating

Overloaded
Insufficient ventilation

No output voltage

Short in load (disconnect)
Tripped or defective circuit breaker
Broken or loose wire
Defective receptacle
No residual magnetism (in 
generator)
Defective stator
Defective rotor (field)
Defective AVR
Shorted diodes on rotor
GFCI receptacle tripped

GENERATOR CARE

Proper care and maintenance of the generator is necessary 

to ensure a long trouble free life.

EXERCISING THE GENERATOR

The generator should be operated every three to four 

weeks. It should be operated for a period of time sufficient 

to warm the unit up and to dry out any moisture that has 

accumulated in the windings. If left, this moisture can cause 

corrosion in the winding. Frequent operation of the engine-

generator set will also ensure that the set is operating 

properly should it be needed in an emergency.

GENERATOR MAINTENANCE

Any major generator service, including the installation 

or replacement of parts, should be performed only by a 

qualified electrical service technician. 

USE ONLY FACTORY 

APPROVED REPAIR PARTS.

  A. Bearing - The bearing used in these generators is a 

    heavy duty, double sealed ball bearing. They require 

    no maintenance or lubrication.

  B. Receptacles - Quality receptacles have been utilized. If a 

    receptacle should become cracked or otherwise 

    damaged, replace it. Using damaged or cracked 

    receptacles can be both dangerous to the operator 

    and destructive to the equipment.

CLEANING

Remove dirt and debris with a cloth or brush. DO NOT 

use high pressure spray to clean either the engine or the 

generator. The high pressure spray could contaminate the 

fuel system and the generator components.

1. Keep the air inlet screen on both the engine and 

  generator free of any dirt or debris to ensure proper 

  cooling. At least yearly, remove the blower housing on 

  the engine and clean the chaff and dirt out of the engine 

  cooling fins and fly wheel. Clean more often if necessary. 

  Failure to keep these areas clean may cause overheating 

  and permanent damage to the unit.

2. Periodically clean muffler area to remove all grass, dirt, 

  and combustible debris to prevent a fire.

3. On engine mufflers equipped with spark arresters, the 

  spark arrester must be removed every 50 hours for 

  cleaning and inspection. Replace if damaged.

Содержание W10000VE-03/A

Страница 1: ...to contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURC...

Страница 2: ...NG THE GENERATOR GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING 14 RECEPTACLE WIRING DIAGRAM 15 36 MONTH LIMITED WARRANTY 16 CA EMISSION CONTROL WARRANTY 16 SAVE THESE INSTRUCTIONS This manual contain...

Страница 3: ...ype Code 0614 G1 Spark Plug Gap 0 030 in Intake Valve Clearance 0 007 0 0 in Exhaust Valve Clearance 0 004 0 006 in Oil Capacity 2 4 2 5 qts 78 80 oz TESTING POLICY Before any generator is shipped fro...

Страница 4: ...HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or...

Страница 5: ...s can be drawn from the receptacles attached to either A or B output legs This generator is capable of producing 40 Amps of 240 volt current at C Check the appliance or tool nameplates for the current...

Страница 6: ...h can be cumulative GASOLINE When using gasoline always use fresh clean unleaded fuel The engine is certified to operate on unleaded gasoline with a minimum octane rating of 87 or higher Gasoline cont...

Страница 7: ...he negative battery cable to the bat terminal Make sure all connections are clean an tight Reverse the sequence when disconnecting disconnect the negative cable first These engines produce enough dire...

Страница 8: ...urs 100 hours 100 hours CHOKE RUN COMMERCIAL POWER BRIGGS STRATTON TM R NOTE The starter life is improved by using shorter cycles with time to cool off between cranking cycles Do NOT operate the start...

Страница 9: ...at to do contact a competent professional to assist you The NFPA 70 250 34 35 are good technical references STANDARD PORTABLE GENERATOR Your WINCO portable generator ships with a bonded neutral You ca...

Страница 10: ...operation of motors lights and most appliances However electronic equipment and clocks will be affected if correct RPM is not maintained See Load vs Output chart Although individual units and models v...

Страница 11: ...Meter when applying load This will ensure the generator is balanced Balanced Unbalanced 120 Volt and 240 Volt receptacles are provided for connection to various loads The diagram below represents thi...

Страница 12: ...ngines Gasoline for the closest engine repair center or ask the dealer from whom you purchased the power plant 1 Change the oil after the rst 5 hours of operation and yearly or 100 hours thereafter un...

Страница 13: ...r y under Engines Gasoline epair center or ask the dealer sed the power plant r the rst 5 hours of operation s thereafter under normal op ange engine oil every 50 hours ne is operated under heavy t te...

Страница 14: ...it be needed in an emergency GENERATOR MAINTENANCE Any major generator service including the installation or replacement of parts should be performed only by a qualified electrical service technician...

Страница 15: ...15 OMP 132 D RECEPTACLE WIRING DIAGRAM G2 G2 G1 GND GND GND GND GND N N N N N G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2...

Страница 16: ...nd Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use...

Отзывы: