background image

11

OMP-132/D

The speed of the engine was carefully adjusted at the 

factory so that the generator produces the proper voltage 

and frequency. For normal usage, the speed setting should 

not be changed. If the generator is being run continuously 

on a very light load, it is often advisable to lower the 

operating speed slightly. 

The engine will govern itself at full speed. Intentionally 

overriding the governor and operating the generator at 

low voltage may damage both the generator and any load 

connected to it. Running the engine at excessively high 

speeds results in high voltage, which may significantly 

shorten the life of light bulbs and appliances being used, as 

well as possibly damaging the engine.

CAUTION: EQUIPMENT DAMAGE

SPEED ADJUSTMENTS SHOULD ONLY BE MADE BY A 

QUALIFIED SERVICE TECH. Whenever making any speed 

adjustments, check the YourGen meter and be sure the 

voltage and speed are correct.

Output voltage should be checked periodically to ensure 

continued proper operation of the generating plant and 

appliances. 

Hz -

This is the measured frequency of the generator set. See 

the table in the RPM section above for an explanation of 

voltage and frequency ranges under load.

V1 - 

Output voltage of Line 1 (L1 on panel) to neutral. See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

V2 - 

Output voltage of Line 2 (L2 on panel) to neutral. See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

V1-V2 -

Output voltage of Line 1 (L1) and Line 2 (L2). See the 

Load vs. Output table for an explanation of voltage and 

frequency ranges under load. 

Hours -

This displays the total running hours of the generator set. 

When the generator is turned off, the hours will remain 

displayed. The display is run on a CR2032, ten-year battery. 

Once the unit is running, the battery connected to the unit 

will then supply the power to the YourGen meter.

Load Bars - 

These bars indicate how much load is being used on Line 1 

(L1) and Line 2 (L2).

   

= 1-25%            = 25-50%         

= 50-75%              = 75-100%

It is good practice to monitor the YourGen Meter when 

applying load.

This will ensure the generator is balanced. 

Balanced                        Unbalanced

120 Volt and 240 Volt receptacles are provided for 

connection to various loads. 

The diagram below represents this 9,600 watt (rated 

output) generator. A & B represent the 120 volt output legs 

of this generator. Up to 4,800 watts at 120 volts (40 Amps) 

can be drawn from the receptacles attached to either A 

or B output legs. This generator is capable of producing 

40 Amps of 240 volt current at C. Check the appliance 

or tool nameplates for the current and voltage to insure 

compatibility. Remember that power taken from C reduces 

the power available equally at both A and B and vice versa.

Change Oil Warning -

After the first 50 hours, the engine oil should be changed. 

The YourGen meter will light up the oil icon (        ) and the 

word ‘change’ will flash. Once the oil has been changed, 

press and hold the cycle button for approximately 5 

seconds until the warning has been removed from the 

display to reset the warning. The meter will then remind 

you of oil changes on the appropriate schedule for your 

generator. It is important to remember that the engine 

manufacturer recommends changing the oil on a calendar 

schedule even if the total number of operational hours have 

not been reached. Certain operating environments may 

also require more frequent oil changes.

Alarms  - 

The display will start blinking and toggle to the first 

parameter that is out of specification. The panel will remain 

flashing until the fault condition returns to within the 

acceptable range, see following table.

Acceptable Range

Frequency

57-63 Hz

Voltage

110VAC-130VAC

VAC1-VAC2

220VAC-260VAC

Battery - 

When the unit is off, the YourGen meter will display the 

hours continuously using a coin cell back-up battery inside 

the meter. Once the unit is running, the meter will get 

power from the main unit battery. 

Voltage  

 

 

3.0V DC

Battery Type 

 

CR2032 

Lifetime 

   10 

Years

The battery has a 10 year lifetime, in the event you need to 

change the battery, follow these instructions: 

The battery is located in the control box near potentially live 

AC terminals. To prevent electrocution while changing the 

battery disable the unit by disconnecting the main battery, 

spark plug and then open the receptacle panel. Locate the 

Содержание W10000VE-03/A

Страница 1: ...to contact us concerning this unit it will help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURC...

Страница 2: ...NG THE GENERATOR GENERATOR MAINTENANCE CLEANING TROUBLESHOOTING 14 RECEPTACLE WIRING DIAGRAM 15 36 MONTH LIMITED WARRANTY 16 CA EMISSION CONTROL WARRANTY 16 SAVE THESE INSTRUCTIONS This manual contain...

Страница 3: ...ype Code 0614 G1 Spark Plug Gap 0 030 in Intake Valve Clearance 0 007 0 0 in Exhaust Valve Clearance 0 004 0 006 in Oil Capacity 2 4 2 5 qts 78 80 oz TESTING POLICY Before any generator is shipped fro...

Страница 4: ...HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or...

Страница 5: ...s can be drawn from the receptacles attached to either A or B output legs This generator is capable of producing 40 Amps of 240 volt current at C Check the appliance or tool nameplates for the current...

Страница 6: ...h can be cumulative GASOLINE When using gasoline always use fresh clean unleaded fuel The engine is certified to operate on unleaded gasoline with a minimum octane rating of 87 or higher Gasoline cont...

Страница 7: ...he negative battery cable to the bat terminal Make sure all connections are clean an tight Reverse the sequence when disconnecting disconnect the negative cable first These engines produce enough dire...

Страница 8: ...urs 100 hours 100 hours CHOKE RUN COMMERCIAL POWER BRIGGS STRATTON TM R NOTE The starter life is improved by using shorter cycles with time to cool off between cranking cycles Do NOT operate the start...

Страница 9: ...at to do contact a competent professional to assist you The NFPA 70 250 34 35 are good technical references STANDARD PORTABLE GENERATOR Your WINCO portable generator ships with a bonded neutral You ca...

Страница 10: ...operation of motors lights and most appliances However electronic equipment and clocks will be affected if correct RPM is not maintained See Load vs Output chart Although individual units and models v...

Страница 11: ...Meter when applying load This will ensure the generator is balanced Balanced Unbalanced 120 Volt and 240 Volt receptacles are provided for connection to various loads The diagram below represents thi...

Страница 12: ...ngines Gasoline for the closest engine repair center or ask the dealer from whom you purchased the power plant 1 Change the oil after the rst 5 hours of operation and yearly or 100 hours thereafter un...

Страница 13: ...r y under Engines Gasoline epair center or ask the dealer sed the power plant r the rst 5 hours of operation s thereafter under normal op ange engine oil every 50 hours ne is operated under heavy t te...

Страница 14: ...it be needed in an emergency GENERATOR MAINTENANCE Any major generator service including the installation or replacement of parts should be performed only by a qualified electrical service technician...

Страница 15: ...15 OMP 132 D RECEPTACLE WIRING DIAGRAM G2 G2 G1 GND GND GND GND GND N N N N N G1 G1 G1 G1 G1 G1 G2 G2 G2 G2 G2...

Страница 16: ...nd Purchaser s sole remedy for a failure under this warranty shall be limited to the repair of the product At WINCO s option material found to be defective in material or workmanship under normal use...

Отзывы: