C - TWO 120/240 VOLT 50 AMP 4 WIRE TWISTLOCK.
These receptacles are rated for dual voltage, 120 or 240
volt use. It is a four wire receptacle, with a center ground-
ing pin. Four wire drop cords plugged into this receptacle
may be split into 120 volt receptacles at a distribution box.
Each receptacle is protected by a two pole 50 amp circuit
breaker mounted just above it.
THIS RECEPTACLE UTILIZES A HUBBELL PLUG PART
NUMBER “CS 6365”.

D - DOOR SAFETY SWITCH. This safety switch is
connected to the DGC-2020 engine control and will shut
the unit down any time door is opened with the unit
running.  This prevents someone from accidently getting
their hands by the main power connection with the unit
running.  This unit will not start if the door is not closed
and latched.

E - 120 VOLT 20 AMP CIRCUIT BREAKERS.  These
two push button 20 amp circuit breakers protect the two
GFCI receptacles (Ref B) mounted below. If you are not
able to reset these breakers, check the load plugged into
the GFCI receptacle or the receptacle itself for a fault.

F - 250 VOLT 50 AMP CIRCUIT BREAKERS.  These
circuit breakers protect the two 50 amp twistlock recep-
tacles (Ref C) mounted in the panel below.

G - 208/240 VOLT MAINLINE CIRCUIT BREAKER.  This
is the low voltage mainline circuit breaker feeding the full
output terminal block (Ref M) below.  This is the circuit
breaker that is used when the selector switch in the 120/
208 volt or 120/240 volt three phase position as well as
the 120/240 volt single phase position.

H - CIRCUIT BREAKER LOCKING BAR.  Select and
turn on either the high voltage breaker (480 V) or the low
voltage breaker (208 or 240 Volt) depending on which
position you have the selector switch in.

J - 480 VOLT MAINLINE CIRCUIT BREAKER.  This is
the high voltage mainline circuit breaker feeding the full
output terminal block (Ref M) below.  This is the circuit
breaker that is used when the selector switch in the 277/
480 volt three phase position.

K - NEUTRAL TERMINAL BLOCK.  This is the neutral
connection point for the customers full power output
connections.  This terminal block also has the neutral to
ground bond attached to it. If you need to operate an
isolated ground system this jumper must be removed.
Generally this is only required when the generator is
being used as backup or being wired into an existing
wiring system that already has one neutral to ground
bond in it.  Lugs will handle up to 2/0 wire.  Torque
lugs to 150 in. lbs. using #1 & #2 wire and 180 in. lbs.
for 1/0 & 2/0 wire.

L - REMOTE START/E-STOP TERMINAL BLOCK. This
terminal block provides the customer two different con-
nections. Torque Screws to 9.6 in. lb. using 14 to 16
awg copper wire with lugs.

1. Emergency stop connection for installing a remote
emergency stop switch
.  This emergency stop switch
connection point must be closed during normal operation,
this is done at the factory by installing a jumper lead
between the two connection points.  If you have an
application (i.e.. gas station) that requires a remote stop

RECEPTACLES and CIRCUIT  BREAKERS

Содержание REDI POWER RP 55

Страница 1: ...60706 200 INSTALLATION AND OPERATION MANUAL OWNERS MANUAL...

Страница 2: ...ator set designed and tested to give you years of satisfactory portable service To get the best performance from your new engine generator set it is important that you carefully read and follow the op...

Страница 3: ...d rooms i e through windows walls or floors 4 NOISE HAZARD Excessive noise is not only tiring but continual exposure can lead to loss of hearing A Use hearing protection equipment when working around...

Страница 4: ...20 ohms 20 ohms Exciter Rotor 0 156 ohms 0 156 ohms ENGINE SPECIFICATIONS See Iveco Operation and Maintenance Manual for com plete engine specifications TRAILER HOUSING RP55 RP80 Capacity 7000 lb Fue...

Страница 5: ...rsonnel away from batteries When installing or replacing batteries use the proper group size starting battery The battery should be a Maintenance Free lead acid design Deep cycle batteries will not wo...

Страница 6: ...re range liquid crystal display LCD with back lighting can be viewed under a wide range of ambient light and temperature conditions Never fill the battery above the fill line Over filling above the up...

Страница 7: ...s in Off mode I Run Push button and Mode Indicator Pressing this button places the DGC 2020 in Run mode The green Run mode LED lights when Run mode is active J Reset Push button This button is pressed...

Страница 8: ...eed before you can change the selector switch Depressing this will also kill the engine this is to ensure the unit is not running when the selector switch is changed J Panel Light Switch Two panel lig...

Страница 9: ...120 208 volt or 120 240 volt three phase position as well as the 120 240 volt single phase position H CIRCUIT BREAKER LOCKING BAR Select and turn on either the high voltage breaker 480 V or the low vo...

Страница 10: ...r is closed if the start switch is in the run position Do not use the switch on this door to shutdown a unit to connect to the full load terminal block this is a safety switch only OPERATING THE UNIT...

Страница 11: ...Check for loose bolts or hardware 4 Check tire pressure 35 psi 5 Trailer level to within 15 degrees 6 Battery securely fastened connection clean and tight and proper fluid level 7 Fuel tank filled wit...

Страница 12: ...this light tells you it is in automatic mode See control panel layout for additional information 18 If the transfer switch has a test button use it to test the complete system The unit should start u...

Страница 13: ...o major sources of difficulty will decrease the incidence of repair To this end a regular schedule of cleaning and inspection will go far toward assuring trouble free operation Personnel respon sible...

Страница 14: ...e In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warranty and some states do no allow the exclusion or limitati...

Страница 15: ...Page 12 60706 200 7190 00 DC ELECTRICAL SCHEMATIC AC INTERFACE CONNECTOR TO GENERATOR...

Страница 16: ...Page 13 7190 00 60706 200 DC ELECTRICAL SCHEMATIC LEGEND...

Страница 17: ...Page 14 60706 200 7190 00 GENERATOR WIRING DIAGRAM VOLTAGE REGULATOR AC INTERFACE CONNECTOR TO DGC 2020 GENERATOR WIRING...

Страница 18: ...Page 15 7190 00 60706 200 VOLTAGE SELECTOR SWITCH WIRING...

Страница 19: ...Page 16 60706 200 7190 00 CIRCUIT BREAKER FULL POWER TERMINAL BLOCK WIRING...

Страница 20: ...Page 17 7190 00 60706 200 RECEPTACLE WIRING...

Отзывы: