background image

Page  9

7190-00

60706-200

WARNING  - POTENTIAL EQUIPMENT DAMAGE

THIS DELTA CONFIGURATION HAS A WILD LEG
THAT PRODUCES 208 VOLTS LINE TO NEUTRAL ON
G2.  BE SURE WHEN CONNECTING TO YOUR PANEL
OR LOAD THAT YOU MATCH THE WILD PHASE ON
THE GENERATOR TO THE WILD PHASE IN YOUR
PANEL OR LOAD. FAILURE TO DO SO WILL RESULT
IN 12O VOLT DEVICES RECEIVING 208 VOLTS.  YOU
MUST ALSO MATCH YOUR ROTATION.

3.

120/208 Three Phase (Low/Parallel WYE configura-

tion) This configuration will produce the following line-to-
line and line-to-neutral voltage. Use of this selector switch
position allows utilization of the 120 volt receptacle only.
The 240 volt receptacles cannot be used as the voltage at
them will be 208 volts, the line to line voltage.

G1 - G2 - G3 208 Volts three phase
G1 - G2 208 Volts single phase
G2 - G3 208 Volts single phase
G1 - G3 208 Volts single phase
G1 - N 120 Volts
G2 - N 120 Volts
G3 - N 120 Volts

4.

277/480 Three Phase (High/Series WYE configura-

tion) This configuration will produce the following line-to-
line and line-to-neutral outputs.

NOTE - CONVENIENCE RECEPTACLES

THE 120 OR 240 VOLT RECEPTACLES ARE DISCON-
NECTED WITH THE SELECTOR SWITCH IN THIS
POSITION

G1 - G2 - G3 480 Volts three phase
G1 - G2 480 Volts single phase
G2 - G3 480 Volts single phase
G1 - G3 480 Volts single phase
G1 - N 277 Volts
G2 - N 277 Volts
G3 - N 277 Volts

CIRCUIT BREAKER SELECTION

After you have selected the correct voltage for your
application and locked the selector switch, do the same
with the main line circuit breakers.

C. STARTUP CHECKLIST

Before initial start up and each subsequent start complete
the following checklist:

1.

Check oil level, refill with proper grade oil.

2.

Check coolant level, refill with proper mixture of
coolant.  See engine manual.

3.

Check for loose bolts or hardware.

4.

Check tire pressure. (35 psi)

5.

Trailer level to within 15 degrees.

6.

Battery securely fastened, connection clean and
tight, and proper fluid level.

7.

Fuel tank filled with the proper grade of diesel
fuel.

8.

Check the fan belt for tightness and excessive
wear.

9.

Check hoses and clamps for leakage.

10.

Check the air cleaner indicator. Service only
when indicated. Do not over-service.

11.

Clean out dust cup on the air cleaner.

D. ELECTRIC STARTING 

(Normal portable use)

CAUTION: EQUIPMENT DAMAGE
DO NOT ATTEMPT TO JUMP/BOOST START THIS
UNIT. TO DO SO MAY DAMAGE THE ELECTRONIC
MICROPROCESSOR IN THE ENGINE CONTROL.
TURN THE DC BREAKER “OFF” AND RECHARGE THE
BATTERY WITH A BATTERY CHARGER.

1.

Select the desired voltage on the voltage selector

switch.
2.

Turn off both main line circuit breakers.

3.

Depress the run button on the front of the control

panel.
4.

After the engine is running at proper speed, adjust the

voltage to the desired level using the external voltage trim
rheostat.
5.

Turn on the proper main line breaker (either high or

low voltage) and padlock the lock bar to prevent the
incorrect breaker from being turned on.

E. REMOTE STARTING AND CONNECTION

(Standby applications)

1.

Complete the manual starting procedure above to

insure the system is set up properly.

2.

Insure the engine control is in the “off” position during

installation of the remote start connections.

3.

Locate the remote start terminal block.  This terminal

block is located next to the full power connections, behind
the access door on the control panel.

4.

Locate the remote start terminals in your remote

automatic transfer switch (ATS).  The ATS terminal block
and wire numbers will vary with each ATS manufacturer.
The RP55/RP80 require a contact closure for start.

WARNING: EQUIPMENT DAMAGE
THE REMOTE “SIGNAL” MUST BE A “DRY” (NON-
POWERED) CONTACT CLOSURE.  USING A POWER
CONTACT WILL CAUSE PERMANENT DAMAGE TO
THE ENGINE CONTROL MODULE.

Содержание REDI POWER RP 55

Страница 1: ...60706 200 INSTALLATION AND OPERATION MANUAL OWNERS MANUAL...

Страница 2: ...ator set designed and tested to give you years of satisfactory portable service To get the best performance from your new engine generator set it is important that you carefully read and follow the op...

Страница 3: ...d rooms i e through windows walls or floors 4 NOISE HAZARD Excessive noise is not only tiring but continual exposure can lead to loss of hearing A Use hearing protection equipment when working around...

Страница 4: ...20 ohms 20 ohms Exciter Rotor 0 156 ohms 0 156 ohms ENGINE SPECIFICATIONS See Iveco Operation and Maintenance Manual for com plete engine specifications TRAILER HOUSING RP55 RP80 Capacity 7000 lb Fue...

Страница 5: ...rsonnel away from batteries When installing or replacing batteries use the proper group size starting battery The battery should be a Maintenance Free lead acid design Deep cycle batteries will not wo...

Страница 6: ...re range liquid crystal display LCD with back lighting can be viewed under a wide range of ambient light and temperature conditions Never fill the battery above the fill line Over filling above the up...

Страница 7: ...s in Off mode I Run Push button and Mode Indicator Pressing this button places the DGC 2020 in Run mode The green Run mode LED lights when Run mode is active J Reset Push button This button is pressed...

Страница 8: ...eed before you can change the selector switch Depressing this will also kill the engine this is to ensure the unit is not running when the selector switch is changed J Panel Light Switch Two panel lig...

Страница 9: ...120 208 volt or 120 240 volt three phase position as well as the 120 240 volt single phase position H CIRCUIT BREAKER LOCKING BAR Select and turn on either the high voltage breaker 480 V or the low vo...

Страница 10: ...r is closed if the start switch is in the run position Do not use the switch on this door to shutdown a unit to connect to the full load terminal block this is a safety switch only OPERATING THE UNIT...

Страница 11: ...Check for loose bolts or hardware 4 Check tire pressure 35 psi 5 Trailer level to within 15 degrees 6 Battery securely fastened connection clean and tight and proper fluid level 7 Fuel tank filled wit...

Страница 12: ...this light tells you it is in automatic mode See control panel layout for additional information 18 If the transfer switch has a test button use it to test the complete system The unit should start u...

Страница 13: ...o major sources of difficulty will decrease the incidence of repair To this end a regular schedule of cleaning and inspection will go far toward assuring trouble free operation Personnel respon sible...

Страница 14: ...e In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warranty and some states do no allow the exclusion or limitati...

Страница 15: ...Page 12 60706 200 7190 00 DC ELECTRICAL SCHEMATIC AC INTERFACE CONNECTOR TO GENERATOR...

Страница 16: ...Page 13 7190 00 60706 200 DC ELECTRICAL SCHEMATIC LEGEND...

Страница 17: ...Page 14 60706 200 7190 00 GENERATOR WIRING DIAGRAM VOLTAGE REGULATOR AC INTERFACE CONNECTOR TO DGC 2020 GENERATOR WIRING...

Страница 18: ...Page 15 7190 00 60706 200 VOLTAGE SELECTOR SWITCH WIRING...

Страница 19: ...Page 16 60706 200 7190 00 CIRCUIT BREAKER FULL POWER TERMINAL BLOCK WIRING...

Страница 20: ...Page 17 7190 00 60706 200 RECEPTACLE WIRING...

Отзывы: