cable (ground) from the engine generator assembly. All
connections must be clean and tight. Check the electrolyte
(fluid) in the battery periodically to be sure it is above the
plates. Never allow the battery to remain in a discharge
condition.
CAUTION: EQUIPMENT DAMAGE
NEVER JUMP START these units. Doing so will destroy
the engine control module, rendering the unit non-
operational. Remove and fully recharge the battery before
attempting to start.
CONNECTING BATTERY CHARGER
A two-stage battery tender is provided on all PSS series
generators. This battery tender charges at a rate of 750 mA
until the battery is fully charged and then automatically
switches to a 13.2 VDC float charger. The charger has an
indicator light on it. Red indicates it is charging, and green
indicates it is in storage mode (float charge). This charger is
mounted on the generator set which is located behind an
access cover in the rear of the unit.
The battery tender receptacle is to be powered by a GFCI
circuit and installed in accordance with the United States
National Electric Code. These AC wires can be run in the
same conduit as the other AC leads from the generator. It
is suggested that this circuit be fused for 15 Amps. Terminal
block connections have been provided in the customer
connection area of the engine-generator set. See following
diagram.
CUSTOMER CONNECTION AREA
TORQUE SCREWS TO
9.6 IN LBS. 14 TO 16
AWG COPPER WITH LUGS
CUSTOMER TO CONNECT TO
120 VOLT UTILITY LINE TO
POWER BATTERY TENDER
AND OPTIONAL ENGINE
HEATER
CUSTOMER GENERATOR
OUTPUT CONNECTIONS TO
EMERGENCY TRANSFER
SWITCH
TORQUE TO 16 IN LBS
RATED FOR 4 TO 10 AWG
COPPER - 85 AMPS
EMERGENCY STOP CONTACTS PROVIDED
FOR REMOTE EMERGENCY STOP SWITCH
UNIT WILL NOT RUN IF JUMPER IS REMOVED
2-WIRE CONNECTOR
THIS IS PLUGGED INTO
MATCHING CONNECTOR
BELOW THE CONTROL MODULE
CUSTOMER DC CONNECTIONS
TO 2-WIRE AUTOMATIC
TRANSFER SWITCH 1 & 22/23
CUSTOMER EARTH
GROUND CONNECTED HERE
AS REQUIRED
ENGINE CONTROL
MODULE ASSEMBLY
BATTERY
TENDER
START & FUEL
RELAYS
NOTICE:
The battery tender is not intended to recharge a battery
which has become completely discharged. It is designed to
produce enough current to recharge a slightly low battery
and maintain a fully charged battery.
Содержание PSS20B2W/C
Страница 19: ...19 60706 229 F ...
Страница 24: ...24 60706 229 F OUTLINE DRAWING ...
Страница 25: ...25 60706 229 F PAD LAYOUT 60706 229 23 12270 01 60706 229 ET A ENGINE GENERATOR SET PAD LAYOUT ...
Страница 26: ...26 60706 229 F AC AND DC GENERATOR SCHEMATIC ...
Страница 27: ...27 60706 229 F AC WIRING SCHEMATIC PSS20 3 A PSS20 17 A PSS20 18 A PSS20 4 A ...