LP LIQUID WITHDRAWAL

The following is a block diagram of a typical L/P Liquid

Withdrawal fuel system for the PSS20000.

Tank

Fuel Solenoid

Converter

Engine

   1

        2

      3

    4

Reference number 1 is the fuel tank.  No regulator is

required but the tank must have a liquid withdrawal
drop tube installed in it and a liquid valve on the tank.

Reference number 2 through 4 are installed on the engine

generator set.

Liquid fuel is delivered from the tank directly to the fuel

solenoid on the generator at full tank pressure.  This
system requires no  pressure regulator be installed
any where in the system.  The converter mounted on
the engine generator set will take the liquid fuel at tank
pressure and convert it to vapor at the proper delivery
rate.

LP/NG FUEL ADJUSTMENTS

****  CAUTION  ****
Do not make any fuel adjustments  or governor adjust-

ments until all pressure readings are in compliance
with specification.  See fuel pressure charts (tables 1,
2, and 3).

NATURAL GAS (NG)

Due to variations in NG fuel characteristics and BTU

levels throughout the country, it may be necessary to
readjust the fuel mixture once the engine has been
installed and serviced.

****  CAUTION  ****
Never make a fuel mixture adjustment on a unit when it is

stopped or running no load.  A mixture adjustment is
only effective when the engine is operating under load.

ADJUSTMENT PROCEDURE

1. Insure the unit is operating with an 80 to 100% load or

at the highest anticipated load.

2. Attach a frequency meter to monitor Hz.

Note:  The fuel mixture adjustment on the PSS8000 &

PSS12000 is the brass load block located on top of the
demand regulator.  This load block is a multi-turn
needle valve. On the PSS20000 it is located on the
carburetor just behind the fuel inlet hose.  This mixture
adjustment is a partial turn, lean to rich, load block
.

3. Begin making a mixture adjustment, observing the Hz

meter. If the meter begins to drop you have the mixture
set too lean or to rich . Adjust the valve in the opposite
direction.  Adjustments should be made very slowly.

Adjust back and forth until the highest Hz is achieved.
Do not turn the valve richer after the Hz quits rising,
this would cause the engine to run rich. If the Hz is out
of upper or lower limits, a governor adjustment will be
necessary.

4. On the PSS8000 & PSS12000 see your engine

manual for governor adjustment procedures.  The
PSS20000 is equipped with an electronic governor
which requires no adjustment.

****  CAUTION  ****
Under full load do not adjust the Hz above 60.  If a higher

Hz reading is used, as the load is decreased the Hz
will go out of upper limits (61 to 62 Hz).

PROPANE (LP)

A generator set  factory tested on LP will normally require

no adjustment. If for some unforeseen reason the
machine should  require adjustment, follow the NG
procedure.

FUEL TYPE CONVERSION

If it should be necessary to change the type of fuel used

after a unit is received, the following procedures are
provided.

PSS8000

These units require no changes to the regulator.  After

plumbing in the fuel lines the only thing necessary is to
reset your mixture as detailed in the adjustment
section above.

PSS12000 & PSS20000

NATURAL GAS TO PROPANE

1. Turn off fuel supply.

2. Remove the fuel line from the carburetor at the

demand regulator.

3. Remove the cap on the upright column of the regula-

tor. This will expose the pressure spring adjusting
screw. Back off the spring adjusting screw so there is
just enough room to replace the cover.  Replace the
cover

4. Invert the regulator so it is positioned with the column

pointing down.

5. Reconnect the fuel line at the regulator.

6. Remove the 1/8 NPT plug (the one closest to fuel

solenoid) located on what is now the top of the
regulator. Connect a fuel pressure meter or a manom-
eter where the plug has been removed. Move the
generator control switch to the run position. As the unit
starts to crank the fuel solenoid will open and you
should get a pressure reading of between 4 to 6
ounces (7 to 11 inches of water column).

Содержание PSS12000

Страница 1: ...PACKAGED STANDBY SYSTEM PSS8000 PSS12000 PSS20000 INSTALLATION AND OPERATORS MANUAL Model PSS8000 Automatic Transfer Switch ...

Страница 2: ...STALLATION 8 AC Electrical Connections 9 DC Electrical Connections 11 Exerciser Clock Set Up 11 INITIAL START UP 12 TROUBLESHOOTING INFORMATION 13 WIRING DIAGRAMS ATS PANELS 16 PSS8000 AC DC Schematic 17 PSS12000 AC Schematic 18 PSS12000 DC Schematic 19 PSS20000 AC Schematic 20 PSS20000 DC Schematic 21 ATS Dimensions 22 PSS8000 Layout 22 PSS12000 Layout 23 PSS20000 Layout 23 MAINTENANCE LOG 24 12 ...

Страница 3: ...ach of children c Do not smoke or use open flame near the generator set or fuel tank d Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate e Store fuel only in an approved container and only in a well ventilated area f Follow local codes for closeness to combustible material 3 DEADLY EXHAUST GAS Exhaust fumes from any gasoline engine contain...

Страница 4: ...y the engine governor within 4 cycles variation 62 5 Hz 58 5 Hz from no load to rated load The 8000 watt 8kW generator is a brushless single bearing direct drive rotating field design The generator is connected to the engine s tapered quill crankshaft extension The engine generator is mounted in a NEMA 3R enclosure for outside installa tion Connection boxes are provided for all customer connection...

Страница 5: ...whom you purchased the power plant The rated power of each engine generator is limited by the temperature altitude and all other ambient conditions specified by the engine manufacturer Engine power will decrease 3 1 2 for each 1000 ft above sea level and will decrease an additional 1 for each 10 degrees Fahrenheit above 60 degrees Fahrenheit UNPACKING INSTRUCTIONS NOTICE When unpacking the generat...

Страница 6: ...will reduce the installation cost of fuel runs The information in this manual is offered to assist you in providing the proper fuel for your engine However this information is only provided to inform you of the engine s requirements and assist in making you aware of the decisions you must make In no case should the instructions or information provided be interpreted to conflict with any local stat...

Страница 7: ...nadequate or incorrect fuel pressure Performance of the engine is in direct relation to the correctness of the fuel system Shown below is a block diagram of a typical L P or N G vapor fuel installation Notice the following tables give two 2 different units of measuring fuel pressure The first and most accurate is the use of a simple water manometer A manometer is calibrated in inches of water colu...

Страница 8: ...to drop you have the mixture set too lean or to rich Adjust the valve in the opposite direction Adjustments should be made very slowly Adjust back and forth until the highest Hz is achieved Do not turn the valve richer after the Hz quits rising this would cause the engine to run rich If the Hz is out of upper or lower limits a governor adjustment will be necessary 4 On the PSS8000 PSS12000 see you...

Страница 9: ...INSTALLING THE BATTERY CAUTION In the following battery installation procedure check to be sure the selector switch remains in the stop position This should be your last step before initial start up PSS8000 A customer supplied twelve volt BCI group U1 battery rated 235 CCA minimum is required to complete the installation Install the highest CCA rated battery available for best cold weather startin...

Страница 10: ...installing the A T S you must first ensure that the 100 Amp line side contactor will be sufficient to handle your complete service See Figure 3 i e the main line breaker must not be larger than 100 Amps If you have a 125 150 200 Amp or larger system you will not be able to transfer the complete electrical system In this case it will be necessary to install a secondary emergency distribution panel ...

Страница 11: ...sult your local wire supplier for proper gauge and type for your area A T S Connections The standby generator terminals in the A T S are marked GENERATOR G1 G N G3 The hot leads G1 and G3 are prewired to the generator side contactor terminals G1 and G3 The line terminals in the A T S are marked LINE L1 L N L3 The hot leads L1 and L3 are prewired to the line side contactor terminals L1 and L3 The l...

Страница 12: ...factory set up for A B C phase rotation If you have trouble getting the A T S to pick up the line power on initial installa tion try switching the A and B phase on the monitor Your rotation may be C B A If so be sure to match the generator rotation to your current line rotation or your three phase motors will try to turn backwards WARNING When installing a Three Phase 240 Volt Delta system be sure...

Страница 13: ...ion the top right hand RUN slide switch to the right hand position 2 Position the top left hand AUTO slide switch to the center position 3 Press the Program Select Button until No 1 is displayed on the clock to the right of the time 4 Push the Day Select Button to select the day you want the engine generator set to start up and run Note You can get more than one triangle displayed on the clock If ...

Страница 14: ...to the STOP position and correct the trouble before proceeding After verifying the voltage and frequency are correct turn the selector switch to the STOP position The unit should shut off with no time delay You are now ready to test the automatic start function Move the selector switch on the engine generator set to the AUTOMATIC position Next move the selector switch on the A T S panel to the STA...

Страница 15: ...on oil 2 No AC output from generator to engage stop crank circuit ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS 1 Insufficient fuel volume getting to the unit a Fuel line too small b Low fuel pressure 2 Fuel load block needs to be adjusted 3 AC short circuit 4 Wiring to the A T S panel crossed or shorted ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY GENERATOR 1 No AC generator output from gen...

Страница 16: ... in line side contactor 3 Broken or defective mechanical electrical inter locks NO AC OUTPUT FROM GENERATOR 1 AC short in the output leads 2 Defective voltage regulator 3 Defective armature 4 Defective coils 5 Unit has lost its residual voltage 6 Rotor loose on engine crankshaft PSS20000 UNIT WILL NOT CRANK WHEN THE POWER FAILS 1 Alarm light on from previous run cycle 2 Generator control switch no...

Страница 17: ...MAINTENANCE Reasonable care in preventive maintenance will insure high reliability and a long life for the engine generator set and the Automatic Transfer Switch WARNING When performing any type of maintenance on this equipment make sure the selector switch on the engine generator is in the off position If you are working in the Automatic Transfer Switch confirm with a reliable meter that all powe...

Страница 18: ...PAGE 16 SINGLE PHASE ATS SCHEMATIC THREE PHASE ATS SCHEMATIC ...

Страница 19: ...PAGE 17 PSS8000 AC AND DC SCHEMATIC ...

Страница 20: ...PAGE 18 PSS120000 AC CONNECTIONS PSS12000 AUTOMATIC VOLTAGE REGULATOR ...

Страница 21: ...PAGE 19 ...

Страница 22: ...PAGE 20 PSS20000 AC SCHEMATIC 120 240 VOLT SINGLE PHASE 120 208 VOLT THREE PHASE 120 240 VOLT THREE PHASE ...

Страница 23: ...PAGE 21 PSS20000 DC SCHEMATIC ...

Страница 24: ... 100 ATS 22 88 14 00 10 63 28 25 18 375 225 100 ATS 22 88 14 00 10 63 28 25 18 375 225 225 ATS 22 88 14 00 10 63 28 25 18 375 400 225 ATS 28 00 16 00 12 68 36 00 23 88 400 300 ATS 28 00 16 00 12 68 36 00 23 88 110 60 ATS 17 00 8 00 8 10 20 00 12 375 230 150 ATS 22 90 14 00 10 63 28 00 18 375 400 320 ATS 28 00 16 00 12 68 36 00 23 875 ...

Страница 25: ...PAGE 23 PSS12000 LAYOUT PSS20000 LAYOUT ...

Страница 26: ...PAGE 24 MAINTENANCE LOG DATE ITEM WORK PERFORMED ...

Страница 27: ...ose of merchantability and fitness for a particular purpose are limited to 12 months from date of purchase In no event is WINCO liable for incidental or consequential damages Note Some states do not allow limitation on the duration of implied warranty and some states do not allow the exclusion or limitation of incidental or consequential damages so the above limitations may not apply in every inst...

Страница 28: ......

Страница 29: ...225 SOUTH CORDOVA AVE LE CENTER MN 56057 Phone 507 357 6831 P N 60706 126 615801 ...

Отзывы: