PAGE 11
D.C. ELECTRICAL INTERCONNECTION
*******CAUTION******
Never run the AC and DC wiring in the same
conduit.
PSS8000
Three control wires are required to be installed between
the A.T.S. panel and the generator control terminal
box. Depending on the distance 14 to 16 gauge
stranded wire should be used. These wires will be
labeled “Bat +”, “Bat -”, and “Start”.
The control wires will be connected as follows in the
generator control terminal box:
ATS Panel
Generator Control Panel
BAT +
to
Wire #4
Bat -
to
Wire # 1 & Fuel Solenoid Wire #1
Start
to
Wire #23
Wire #21 & Fuel Solenoid Wire #21
are just left capped together.
PSS12000 and PSS20000
Three control wires are required to be installed between
the A.T.S. panel and the generator control terminal
box. Depending on the distance 14 to 16 gauge
stranded wire should be used. These wires will be
labeled “Bat +”, “Bat -”, and “Start”.
The control wires will be connected in the generator
control terminal box and in the A.T.S. to small terminal
blocks. Both are labeled “Bat +”, “Bat -” and “Start”.
The wire are run between identical terminals, i.e.
“start” to “start”.
SETTING THE EXERCISER CLOCK
Setting the current time and date.
1. Position the top right hand (RUN) slide switch to the
left position.
2. Push the clock’s “Day Select Button” until the clock
displays a triangle under the number corresponding to
the current day of the week. (Monday is day 1, Sunday
is day 7)
3. Push the “Hour Select Button” until the display
indicates the correct time in hours. Note: In the
afternoon you should push the button until a “P” is
displayed beside the correct hour.
4. Push the “Minute Select Button” until the display
indicates the correct time in minutes.
5. Position the top right hand (RUN) slide switch to the
center position. The correct time and date should now
be displayed.
Setting the Exerciser Program:
1. Position the top right hand (RUN) slide switch to the
right hand position.
2. Position the top left hand (AUTO) slide switch to the
center position.
3. Press the “Program Select Button” until No 1 is
displayed on the clock to the right of the time.
4. Push the “Day Select Button” to select the day you
want the engine generator set to start up and run.
Note: You can get more than one triangle displayed
on the clock. If this happens just keep pressing the
button and it will work back through the cycle and
display only one triangle under whichever day you
desire.
5. With the “Hour” and “Minute” buttons select the time of
day you want the engine to start up.
6. Press the “Program Select Button” until No. 2 is
displayed on the clock.
7. Push the “Day Select Button” to select the day you
want the engine to stop. This must be the same day
you selected in step 4 above.
8. With the “Hour” and “Minute” buttons, select the time
you want the engine to stop. It is recommended you
let the engine run at least 15 minutes during any
exercise period.
9. Position the top right hand (RUN) slide switch to the
center (RUN) position.
CLOCK NOTES:
This seven day exerciser clock has seven additional
program cycles available. Always keep in mind the
odd number turns the unit on and the even number
shuts the unit off. (i.e. (3 on, 4 off) (5 on, 6 off) etc.)
The relay in the clock will not work unless the transfer
switch is installed and powered up. The relay needs
120 volts AC to operate.
If, when you finish programming the clock, you get an
“EEEE” on the display, it stands for error. The most
common error is that the day of operation has not been
properly set at each step or a program has been
turned on and not turned off. (i.e. programs not
properly grouped 1& 2, 3 & 4, 5 & 6, etc.)
On the face of clock is a small button marked “R”, this is a
reset switch. Depressing this switch will remove all
programming in the clock including the time, Use a
small screwdriver or the tip of a pencil to depress this
button. This should be used only as a last resort.
Содержание PSS12000
Страница 18: ...PAGE 16 SINGLE PHASE ATS SCHEMATIC THREE PHASE ATS SCHEMATIC ...
Страница 19: ...PAGE 17 PSS8000 AC AND DC SCHEMATIC ...
Страница 20: ...PAGE 18 PSS120000 AC CONNECTIONS PSS12000 AUTOMATIC VOLTAGE REGULATOR ...
Страница 21: ...PAGE 19 ...
Страница 22: ...PAGE 20 PSS20000 AC SCHEMATIC 120 240 VOLT SINGLE PHASE 120 208 VOLT THREE PHASE 120 240 VOLT THREE PHASE ...
Страница 23: ...PAGE 21 PSS20000 DC SCHEMATIC ...
Страница 25: ...PAGE 23 PSS12000 LAYOUT PSS20000 LAYOUT ...
Страница 26: ...PAGE 24 MAINTENANCE LOG DATE ITEM WORK PERFORMED ...
Страница 28: ......
Страница 29: ...225 SOUTH CORDOVA AVE LE CENTER MN 56057 Phone 507 357 6831 P N 60706 126 615801 ...