PAGE 8
MOUNTING THE AUTOMATIC
TRANSFER SWITCH (A.T.S.)
*************
***** WARNING *****
*************
EQUIPMENT DAMAGE- Protect the switch from con-
struction grit and metal chips to prevent a malfunction
or shortened life of the switch.
The Automatic Transfer Switch connects the load (lights,
furnace, outlets, etc.) to the normal power line during
standby. When normal power fails, the A.T.S. starts
the engine generator set, disconnects the power line
and then connects the load to the standby generator
set. When normal power is restored, the automatic
switch retransfers the electrical load to the normal
service and stops the engine. The A.T.S. panel should
be mounted as close to the distribution panel as
possible.
*************
***** WARNING *****
*************
All wiring must be done by a licensed electrician, and
must conform to the national electrical code and
comply with all state and local codes and regulations.
Check with your electrical inspectors before proceed-
ing!
PSS8000 - The Automatic Transfer Switch shipped with
the PSS8000 system has a 100 Amp line side
contactor installed to handle your normal power needs
and a 50 Amp generator side contactor to handle the
emergency generator output. Before installing the
A.T.S. you must first ensure that the 100 Amp line side
contactor will be sufficient to handle your complete
service. See Figure 3. (i.e. the main line breaker must
not be larger than 100 Amps) If you have a 125, 150 ,
200 Amp or larger system, you will not be able to
transfer the complete electrical system. In this case it
will be necessary to install a secondary emergency
distribution panel. See Figure 4. NOTE: THE MAXI-
MUM OUTPUT OF THE GENERATOR IS 33.3 AMPS
AT 240 VOLTS. You must also take this into consider-
ation when deciding whether to install an emergency
distribution panel.
PSS12000 - The Automatic Transfer Switch shipped with
the PSS12000 system has a 100 Amp line side
contactor installed to handle your normal power needs
and a 100 Amp generator side contactor to handle the
emergency generator output. Before installing the
A.T.S. you must first ensure that the 100 Amp line side
contactor will be sufficient to handle your complete
service. See Figure 3. (i.e. the main line breaker must
not be larger than 100 Amps) If you have a 125, 150 ,
200 Amp or larger system, you will not be able to
transfer the complete electrical system. In this case it
will be necessary to install a secondary emergency
distribution panel. See Figure 4. NOTE: THE MAXI-
MUM OUTPUT OF THE GENERATOR IS 50.0 AMPS
FIGURE 3
FIGURE 4
FIGURE 5
Содержание PSS12000
Страница 18: ...PAGE 16 SINGLE PHASE ATS SCHEMATIC THREE PHASE ATS SCHEMATIC ...
Страница 19: ...PAGE 17 PSS8000 AC AND DC SCHEMATIC ...
Страница 20: ...PAGE 18 PSS120000 AC CONNECTIONS PSS12000 AUTOMATIC VOLTAGE REGULATOR ...
Страница 21: ...PAGE 19 ...
Страница 22: ...PAGE 20 PSS20000 AC SCHEMATIC 120 240 VOLT SINGLE PHASE 120 208 VOLT THREE PHASE 120 240 VOLT THREE PHASE ...
Страница 23: ...PAGE 21 PSS20000 DC SCHEMATIC ...
Страница 25: ...PAGE 23 PSS12000 LAYOUT PSS20000 LAYOUT ...
Страница 26: ...PAGE 24 MAINTENANCE LOG DATE ITEM WORK PERFORMED ...
Страница 28: ......
Страница 29: ...225 SOUTH CORDOVA AVE LE CENTER MN 56057 Phone 507 357 6831 P N 60706 126 615801 ...