OPM-134/B

    element, from the inside outward (maximum pressure 

    200 kPa). Do not use detergents; do not use diesel.

  4. Replace the filter if any breakages or tears are found.

  5. Reassemble by repeating the above operations in 

  reverse 

order

  6. Reinstall the element into the air cleaner case.

ADJUSTING THE GOVERNOR

Never attempt to adjust the low or high idle speed limit 

screw. This may impair the safety and performance of the 

machine and shorten its life. If adjustment is ever required, 

contact an authorized service center.

  1. Check that the governor lever (1) makes firm contact 

    with the high idle stop (2) and the low idle speed limit 

    screw (3) when the engine speed control is in the full 

    speed or low idle speed positions.

  2. If the governor lever does not make proper contact 

    with the high idle stop or the low idle speed limit 

    screw, adjust the throttle cable or linkage as necessary.

WARNING: EQUIPMENT DAMAGE

Do not force the throttle cable or linkage to move. 

This may damage the governor lever, the throttle 

cable or linkage and cause irregular operation of the 

engine speed control.

STORAGE

PREPARING THE ENGINE FOR A LONG PERIOD 

OF INACTIVITY

In the case of a planned period of inactivity that lasts 

longer than one month, to prevent the interior parts of the 

engine and some components of the injection system from 

oxidizing, prepare the engine as follows:

One Month

 

  1. While the engine is running, treat upper cylinders by 

    spraying engine fogging agent into the air intake 

    for about two minutes. Open throttle for short bursts of 

    speed, shut off engine and allow it to come to a stop 

    while continuing to spray into air intake. 

  2. If engine is less transmission, spray flywheel and ring 

    gear with mixture of one part recommended engine 

    oil, and one part Stoddard Solvent or equivalent.

 

  3. Check coolant protection. Store indoors in dry area.

Infinite period

In order to prevent oxidation of the internal parts of the 

engine and of certain components in the injection system, 

when the engine is expected to be inoperative for periods 

of more than two months, the following operations must 

be carried out in preparation for this:

  1. Drain the lubricant from the sump, after first warming 

    up the engine.

  2. Fill the engine with protective oil type 30/M (or 

    alternatively oil that complies with MIL 2160B type 2 

    specifications), up to the “minimum” level indicated on 

    the dipstick. Start the engine and keep it running for 

    approximately 5 minutes.

  3. Drain the fuel from the injection circuit, from the filter 

    and from the injection pump pipes.

  4. Connect the fuel circuit to a tank containing CFB (ISO 

    4113) protective fluid, and feed in the fluid by putting 

    the circuit under pressure and running the engine for 

    approximately 2 minutes, after first disabling the 

    injection system. This operation can be performed by 

    polarizing terminal 50 of the starter motor with a 

    positive voltage equivalent to the rated voltage of the 

    system, using a conductor provided for that purpose.

  5. Nebulise approximately -- g of 30/M protective oil (10 g 

    per liter displacement) into the turbocharger suction 

    inlet, during the pressurized filling operation described 

    in the previous point.

  6. Close all the suction, delivery, ventilation and bleeder 

    openings in the engine with suitable plugs, or seal 

    them with adhesive tape.

  7. Drain the residual 30/M protective oil from the sump. 

    This oil can be used again for a further 2 preparation 

  operations.

  8. Attach signs reading “ENGINE WITHOUT OIL” to the 

    engine and to the on-board control panel.

  9. Drain the coolant, if it has not been mixed with suitable 

    antifreeze and corrosion inhibitors, and affix a sign to 

    indicate the fact. In the event of prolonged inactivity, 

    the operations described must be repeated every 6 

    months, following the procedure given below:

    A) drain the 30/M protective oil from the sump;

    B) repeat the operations described from point 2 to 

  

 

point 7.

Should you intend to protect external parts of the engine, 

proceed by spraying OVER 19 AR protective liquid on 

unpainted metal parts, such as the flywheel, pulleys and 

the like, avoiding belts, connector cables and electrical 

equipment.

Содержание DR45F4/1

Страница 1: ...help us to respond to your needs faster MODEL _________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE __________________________________...

Страница 2: ...MANUAL Congratulations on your choice of a WINCO generator You have selected a high quality precision engineered generator designed and tested to give you years of satisfactory service To get the best...

Страница 3: ...ne generator set has been designed and manufactured to allow safe reliable performance Poor maintenance improper or careless use can result in potentially deadly hazards from electrical shock exhaust...

Страница 4: ...1D or 2D EN590 or equivalent Oil Type SEE LUBRICATION SECTION Oil Capacity 8 98 Quarts Cooling System 50 50 mix DR65F4 Generator Wattage 62 000 62 000 62 000 62 000 Volts 120 240 120 208 120 240 277...

Страница 5: ...wage nameplate on your generator before selecting the correct information below Model Stamford UCI274C Winding Group 311 Resistances Rotor 1 34 Ohms 22 C Stator 0 0317 Ohms Per Ph 22 C Exciter Rotor 0...

Страница 6: ...emperature altitude fuel and other conditions specified by the manufacturer of applicable engines This unit comes factory set for either key start or manual start With the DSE 7310 MKII controller use...

Страница 7: ...own brackets hardware d Unit components or accessory items shipped loose for on site installation e Optional accessories 3 Remove main frame hold down bolts 4 Unit can now be lifted from shipping rail...

Страница 8: ...the ATS to protect the contacts ENGINE GENERATOR SET MOUNTING The unit s main frame must be bolted solidly to a solid base The engine generator is mounted on channels which are attached with special...

Страница 9: ...install an additional lift pump to bring the fuel up to the mechanical fuel pump on the engine The information in this manual is offered to assist you in providing the proper fuel for your engine How...

Страница 10: ...ce SERVICING BATTERIES CAUTION EQUIPMENT DAMAGE Voltage spikes can damage the DC control circuits Disconnect the battery charger from the AC power source prior to disconnecting the battery Batteries u...

Страница 11: ...hour meter and the service entrance providing the service entrance ampere rating is within the transfer switch s rated capability If only specific circuits are to be powered under emergency power fail...

Страница 12: ...re sizing based on both wire type and amperage For additional information on wire sizes refer to table 310 16 of the National Electrical Code ANSI NFPA 70 C GROUND LUG These ground lugs are bonded to...

Страница 13: ...t to do contact a competent professional to assist you The NFPA 70 250 34 35 are good technical references PERMANENTLY INSTALLED GENERATORS This WINCO portable generator ships with a bonded neutral an...

Страница 14: ...ng to ensure they function properly SERIAL COMMUNICATION DSE provides a series of remote accessories that can help provide useful information to operators These accessories communicate over the DSE Ne...

Страница 15: ...SCO 300 UL SWITCH When Normal Source Fails Terminals On Transfer Switch Contact Closes TB1 and TB2 Contact Opens TB1 and TB3 Engine start and auxiliary circuit terminal block TB located on 3ATS 3NTS t...

Страница 16: ...d possible serious injury Always inspect unit prior to operation CAUTION For the first 10 seconds of operation all of the oil coolant and electrical shutdowns are disabled This is enough time to cause...

Страница 17: ...unit complete your pre start checklist and ensure the generator mainline circuit breaker is in the proper position prior to starting Starting this unit without it properly connected can cause serious...

Страница 18: ...TOP RESET button will stop the unit immediately Pressing the AUTO mode button will stop the unit but only after the cool down timers have timed out and there is no remote start signal being sent to th...

Страница 19: ...filler port using lubricant oil with the suitable oil table in the LUBRICATION section of this manual 6 Use the dip stick to ensure the level of oil does not exceed the MAX limit 7 Insert the dipstic...

Страница 20: ...t until it has emptied completely When empty repair the circuit making sure that the sleeves are Filter perfectly sealed 2 Refill the engine and the heat exchanger until complete top off 3 With the fi...

Страница 21: ...the injection system when the engine is expected to be inoperative for periods of more than two months the following operations must be carried out in preparation for this 1 Drain the lubricant from...

Страница 22: ...Hours Change Oil Filters 600 Hours Change Fuel Filters 600 Hours Change Fuel Pre Filter 600 Hours Check Exhaust System for Damage 6 Months Clean Fuel Tank 6 Months Change Auxiliary Member Belt 1200 Ho...

Страница 23: ...fective fuel solenoid Defective engine harness Improper battery voltage to fuel pump or fuel solenoid Engine starts then stops and alarm light comes on Engine oil pressure is low Engine has high water...

Страница 24: ...750 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 400 500 600 700 750 800 900 1000 1250 1500 1750 2000 40 50 65 75 90 100 120 135 155 180 205 230 250 270 310 340 375 385 395 425 445 485 520 545 560 45 55 7...

Страница 25: ...5 2 35 6685 6 1 5 22 17 7 03 6 1 5 8 62 12 6 0 67 57 5 7 7 51 725 3 27 5 67 57 62 12 2 22 17 02 8 8 7 7 21 0 1 1 51 66 211 725 27 2 35 6685 1 22 17 7 03 5 785 1 6 1 56 25 6 7 6 5 9 6 216 5 9 51 6 5 3...

Страница 26: ...57 67 57 1 1 77 77 1 5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 1 855 17 66 7...

Страница 27: ...08 165 HIGH AND LOW WYE THREE PHASE LOW WYE 120 208 VOLTS THREE PHASE HIGH WYE 277 480 VOLTS THREE PHASE HIGH WYE 277 480V THREE PHASE LOW WYE 120 208V THREE PHASE DELTA 120 240 VOLTS THREE PHASE AC W...

Страница 28: ...damages WINCO Inc shall not be liable for any claim that requires replacement of engine part or component of the product that is no longer manufactured or available Additionally WINCO Inc will not be...

Отзывы: