10

OPM-141/E

All selected emergency circuits are removed from main 

distribution panels and installed in the emergency 

distribution panel. The ATS is then installed between 

the main panel and the emergency distribution panel. 

Suggested circuits: freezer, refrigerator, furnace, emergency 

lights, sump pump, emergency outlet circuits, etc. Total 

running load must not exceed generator rating.

DC WIRING

All communication and DC wiring should be run in 

separate conduit from AC wiring.

REMOTE START

The DSE7310 is able to start the generator when it receives 

a remote signal from any dry contact. This makes the system 

compatible with a wide range of control mechanisms 

including two-wire start automatic transfer switches. When 

the contact closes the controller will automatically start. 

When the contact is opened the generator will go through 

a cool-down cycle and turn off.  Connect the remote start 

leads to the Remote Start + and Remote Start - terminal 

blocks in the door behind the DSE 7310 controller. 

E STOPS

In some applications additional emergency stops may be 

desired or necessary. The controller has terminals designed 

allowing the addition of multiple remote emergency stops. 

E-stops must be normally closed to work properly in this 

system. The e-stop circuit supplies power to fuel solenoid 

and the starter circuit. Opening any switch in the series 

prevents the engine from cranking or from receiving fuel to 

run. 

To wire additional emergency stop switches first remove 

the orange jumper between the two Emergency Stop 

terminal blocks. Failure to remove the jumper will prevent 

the remote switches from working properly. Add wires 

between the terminal block to the new switch(s). The 

switches must be wired in series for proper function. Test 

each e-stop after wiring to ensure they function properly.

SCR 

(DSENET)

4A 

(DSENET)

4B 

(DSENET)

Battery Charge Fail Emergency Stop Emergency Stop Remote S

tart +

Remote S

tart -

Ground Ground B Battery -

Two-Wire Start Hook-Ups

SCR 

(DSENET)

4A 

(DSENET)

4B 

(DSENET)

Battery Charge Fail Emergency Stop Emergency Stop Remote S

tart +

Remote S

tart -

Ground Ground B Battery -

E-Stops

SERIAL COMMUNICATION

DSE provides a series of remote accessories that can help 

provide useful information to operators. These accessories 

communicate over the DSE Net. Terminal blocks are wired 

to the distribution panel to aid in installation. Follow the 

instructions included with each accessory.

The generator controller can communicate with a variety 

of controls and monitoring systems, including RS232 and 

RS485. The ports are wired onto the back of the DSE7310. 

In order to finalize communication the program will need 

to be adjusted using the free DSE configuration software to 

enable the commutation. Contact Winco service for a list of 

register values.

INSTALLING THE BATTERY

CAUTION

In the following battery installation procedure, check to be 

sure the engine control is in the “stop” position. This should 

be your last step before initial start-up.

A customer supplied 12 Volt battery is required to complete 

the installation. Installation of the highest CCA rated battery, 

within the correct BCI group, will increase cold weather 

starting performance.

BATTERY REQUIREMENTS

Model

Voltage

BCI Group

Min. CCA 

Rating

DE4040F4

12

24

650

WARNING: EQUIPMENT DAMAGE

This unit is12 Volt and is negative ground. Permanent 

damage will occur if they are connected to a 24 Volt 

system or a positive ground system. If you are using the 

truck batteries to start these units, you may have to disable 

the charging system to keep it from interfering with the 

vehicle charging system.

Installation and servicing of batteries must only be 

preformed or supervised by personnel knowledgeable of 

batteries and the required precautions. Keep unauthorized 

personnel away from batteries.

When installing or replacing batteries, use the proper 

group/size starting battery. The battery should be a 

maintenance-free lead acid design. Deep cycle batteries will 

not work for this application.

CAUTION: PERSONAL DANGER

NEVER dispose a battery in a fire. The battery is capable of 

exploding.

DO NOT open or mutilate the battery. Released electrolyte 

is known to be harmful to the skin and eyes and to be very 

toxic.

These engine-generator sets are all NEGATIVE ground. Be 

very careful  not to connect the battery in reverse polarity, 

as this may short circuit the battery charging system on the 

engine.

Содержание DE4040F4

Страница 1: ...ontact us on this unit it will help us to respond to your needs faster MODEL __________________________________________________ SERIAL NUMBER _________________________________________ PURCHASE DATE _________________________________________ DEALER NAME ___________________________________________ DEALER PHONE ________________________________________ www wincogen com ENGINE C O MPRESSO R ...

Страница 2: ...HE OIL FILTER REPLACING FINE SEPARATOR CARTRIDGE REPLACING THE AIR INTAKE FILTER ENGINE MAINTENANCE 19 CHANGING THE OIL CHANGING OIL FILTER REFILLING COOLANT CHANGING AIR FILTER CHECKING WATER IN PRE FILTER CLEANING RADIATOR REPLACING BLOW BY FILTER STORAGE TROUBLE SHOOTING 22 ENGINE GENERATOR SET MAINTENANCE SCHEDULE 22 COMPRESSOR FLOW DIAGRAM ENGINE CODES 24 WIRING SIZE TABLE 30 ENGINE HARNESS 3...

Страница 3: ... HAZARD Gasoline and other fuels present a hazard of possible explosion and or fire A Do not refuel when the engine is running or hot B Keep fuel containers out of reach of children C Do not smoke or use open flame near the generator set or fuel tank D Keep a fire extinguisher nearby and know its proper use Fire extinguishers rated ABC by NFPA are appropriate E Store fuel only in an approved conta...

Страница 4: ...66 139 120 60 48 Hertz 60 60 60 60 60 ENGINE Model FPT F5 C Starting System 12 Volt Fuel Consumption full load 4 16 Gal hr Fuel ASTM D 975 2D Oil Type See Lubrication section in this manual Oil Capacity 10 Quarts Cooling System 50 50 mix See engine manual for additional fuel types and specifications GENERATOR RESISTANCE all value at 22 C Model Stamford UCI224D Winding Group 311 Rotor 0 64 Ω Stator...

Страница 5: ...late information recorded inside the front cover of this manual for future reference and for identification whenever requesting field or factory assistance Primary fields needed for assistance are complete model number and serial number ENGINE This manual covers specific operation of the combined engine generator set The basic engine information provided in this manual is not suitable for all oper...

Страница 6: ...tems shipped loose for on site installation f Optional accessories 3 Remove main frame hold down bolts 4 Unit can now be lifted from shipping rails LIFTING THE GENERATOR SET NOTICE PERSONAL INJURY To prevent injury to persons or equipment observe the following guidelines when lifting the generator CAUTION Do not attempt to lift the generator set by the means of the lifting eyes on the engine or ge...

Страница 7: ...eteriorate and the unit mountings will come loose These units must be mounted to a steel or concrete base VENTILATION REQUIREMENTS WARNING EQUIPMENT DAMAGE It is the installer s responsibility to ensure that there is sufficient cooling air available to prevent the engine and generator from over heating Damage caused by overheating is not covered by warranty Providing proper air movement during you...

Страница 8: ...e fuel inlet pump If your fuel supply is lower than 3 feet you may have to install an additional lift pump to bring the fuel up to the mechanical fuel pump on the engine The information in this manual is offered to assist you in providing the proper fuel for your engine However this information is only provided to inform you of the engine s requirements and assist in making you aware of the decisi...

Страница 9: ... the vehicle frame The generator should only supply equipment that is cord and plug connected through customer installed receptacles mounted on the generator or the vehicle PERMANENTLY INSTALLED GENERATORS This WINCO portable generator ships with a bonded neutral NFPA 70 refers to this as a separately derived system When connecting it to a building a transfer switch specifically designed for GFCI ...

Страница 10: ... Battery Battery E Stops SERIAL COMMUNICATION DSE provides a series of remote accessories that can help provide useful information to operators These accessories communicate over the DSE Net Terminal blocks are wired to the distribution panel to aid in installation Follow the instructions included with each accessory The generator controller can communicate with a variety of controls and monitorin...

Страница 11: ...erflow resulting in corrosion to the engine or nearby parts Immediately wash off any spilled electrolyte following the procedure above NOTE Always make sure that a new battery is fully charged before installing it on a generator set Failure to do so can cause damage to the engine control module in the generator set All connections must be clean and tight Check the electrolyte in the battery period...

Страница 12: ... Fuel WINCO Broad Range 5W 40 Synthetic API CJ 4 ACEA E6 E9 15 ppm Premium 10W 40 Semi Synthetic API CJ 4 ACEA E6 E9 15 ppm Cold Climate 5W 30 Synthetic API CJ 4 ACEA E6 E9 15 ppm Not Authorized Monograde CAUTION PERSONAL INJURY Only check oil when the engine is not running and is at a low temperature in order to avoid the risk of burns 1 Remove the dipstick 1 and ensure the oil level is between t...

Страница 13: ... release the MANUAL MODE button The small LED light next to it should come on Note There is no start delay in this mode of operation 2 Press and release the green START ENGINE button The DSE 7310 will send two signals to the engine The first signal wire 21 will engage the fuel solenoid the second wire 22 will engage the starter on the engine At this point the DSE 7310 will start the cranking cycle...

Страница 14: ...he initial start up or prior to start up it is most likely a false warning light Simply reset the ATS to start over Once you have completed testing of the ATS be sure you ALWAYS leave the system in the standby mode unless servicing the unit For standby operation press the AUTO button on the front of the control The green light should light up next to the AUTO button NOTE For setting the exerciser ...

Страница 15: ...f dust and debris entering the housing and generator components COLD WEATHER OPERATIONS The minimum natural starting temperature with glow plugs is 5 F The minimum starting temperature with glow plugs and block heater is 13 F The degree of fluidity of the diesel oil can may be reduced at low temperatures due to the separation of the paraffin This results in the filters becoming clogged The ASTM D9...

Страница 16: ...ly use genuine parts 3 All maintenance and repair work must only be carried out with the complete unit shut down and the power supply switched off Ensure the machine is secured against accidental switch on WARNING PERSONAL INJURY Before removing plugs filters and other pressurized parts the compressor must be cut off from all pressure sources and a pressure relief of the entire system must be carr...

Страница 17: ...pres sor compact module see chapter 7 8 Mainte nance intervals 7 3 2 Oil drain points The system should be at operating temperature in this case Figure 7 2 Note Dispose of the used oil according to the appli cable regulations Switch off the screw compressor and then secure it against being switched on again by removing the main switch Completely release the pressure in the screw compressor system ...

Страница 18: ... 7 5 2 Replacing fine separator cartridge Figure 7 4 Note Dispose of the old fine separator cartridge ac cording to the applicable regulations Unscrew the fine separator cartridge 1 with a suitable tool e g oil filter strap wrench Oil the gasket on the new fine separator car tridge 1 with oil of the same oil type as in the compressor module Tighten the new fine separator cartridge by hand No tool is req...

Страница 19: ...to avoid the risk of burns 1 Remove the cap 1 on the radiator 2 With the engine cold make sure the level of coolant in ENGINE MAINTENANCE CHANGING THE OIL CAUTION PERSONAL INJURY Only change oil when the engine is not running and is at a low temperature in order to avoid the risk of burns 1 Place a drip pan or suitable container for catching the oil below the drain valve attached to the sump 5 WIN...

Страница 20: ...er cover 4 after having released the two quick closing hooks 3 2 Remove the filter 5 During this operation take care to ensure that no dust enters the sleeve 3 Position the filter 5 in its seat 4 Replace the cover 4 of the air filter and lock it in place using the two quick release hooks 3 CHECKING WATER IN PRE FILTER WARNING EQUIPMENT DAMAGE Clean the exhaust valve prior to checking the pre filte...

Страница 21: ...tective oil in a quantity of approx 130 g 10 g per liter of displacement in the turbocharger intake inlet during the engine turning operation described in the previous paragraph 6 Close all of the engine s intake discharge ventilation and bleeding holes with plugs or seal them with adhesive tape 7 Drain the residual 30 M protective oil from the sump which can be used for an additional 2 preparatio...

Страница 22: ...set Defective control relay in ATS Fuse s blown in the DSE 7310 Defective DSE 7310 Loose or dirty battery terminals Defective starter Defective start solenoid Low dead battery Engine won t crank Low dead battery Blown DC fuses Defective DSE 7310 Defective key switch Loose or dirty battery terminals Defective starter Defective start solenoid Locked up engine genset Defective engine harness Improper...

Страница 23: ... with pre separation 6 Fine separator 7 Minimum pressure valve 8 Oil thermostat 9 Oil filter 10 Oil cooler 11 Air after cooler 12 Non return valve 13 Safety valve optional 2 1 1 2 4 5 3 3 1 13 6 7 11 9 8 10 12 Figure 3 2 3 2 Flow diagram of NK 31 electric control unit 3 3 Operating description for NK 31 Screw Compressor Compact Module electric The flow diagram shows a schematic view of the operating...

Страница 24: ... signal range check is performed on the signal Sensor is inside ECU 6C 3 108 4 Environmental pressure sensor is available and connected via hardware to the ECM Pressure is obtained through Analogic to Digital Converter and transformed to a physical value in EnvP_pSens A signal range check is performed on the signal Sensor is inside ECU 6C 4 110 3 Electrical Signal range check of Coolant temperatur...

Страница 25: ... switch input For the idle shut down a state machine is used The state in which the state machine is at the moment is shown in the message CoEng_stIdlShDwnStM_mp Assuming the conditions to enable the engine shut off then the engine will shut down after a countdown timer The status signal indicates when the countdown timer is below a timer calibrated CoEng_stIdlShDwnStM_mp 1 252 1F 623 6 The Power ...

Страница 26: ... trigger appropriate substitute reaction The behavior pattern describes in a bit mask different detected problem overcurrent command collision RAM error short circuit when the expected combination of errors is detected measured and reference pattern are matching a failure is detected 28E 5 654 6 Hardware errors in the injectors and respective ECM power stages are investigated Diagnostic procedure ...

Страница 27: ...hardware connected sensor The raw voltage signal is acquired in the message Exh_uRawPTrbnUs This signal is checked for the Signal Range Errors and then transformed into physical value Exh_pSensPTrbnUs 4B9 3 1209 4 The turbine upstream pressure is acquired via hardware connected sensor The raw voltage signal is acquired in the message Exh_uRawPTrbnUs This signal is checked for the Signal Range Erro...

Страница 28: ...s the LowLevel Chipdriver for the Powerstage Chips R2S25200kfp The R2S25200 is a chip with 18 powerstages and an additional module for the monitoring of the ECU internal 5V Supply Voltage It is possible to configure max 4 R2S2 B18 C 2840 14 Calibrated parameters for baud rate cannot be read from EEPROM B18 E 2880 2 A range and plausibility check for the value of PTO switch are performed The source...

Страница 29: ...rcuit is monitored separately A plausibility check is made in case a failure Short circuit to Battery SCB or Short circuit to Ground SCG is detected Therefore the switch Low side in case of SCB High side in case of SCG is closed If the Short Circuit failure disappears it is cleared and the Overload failure activated 152B 6 5419 7 The Throttle Valve actuator gives a feedback with a position sensor ...

Страница 30: ... THHW THW 2 XHH XHHW XHHW 2 ZW 2 SIZE AWG OR KCMIL Wire Type RHW THHW THW THWN XHHW USE Wire Type TBS SA SIS THHN THW 2 THWN 2 RHH RHW 2 USE 2 XHH XHHW XHHW 2 ZW 2 50 65 85 100 115 130 150 175 200 230 255 285 310 335 380 420 460 475 490 520 545 590 625 650 655 55 75 95 115 130 145 170 195 225 260 290 320 350 380 430 475 520 535 555 585 615 665 705 735 750 8 6 4 3 2 1 1 0 2 0 3 0 4 0 250 300 350 40...

Страница 31: ...31 OPM 141 E ENGINE HARNESS ...

Страница 32: ...5 7 50 1 2 6 211 725 211 725 66 86 86 86 86 86 36 1 2 8 1387 20021 6 5 1 1 6 5 1 1 1 1 1 36 32 5 6 7 66 0 5 1 6723 6 7 66 8 6 7 21 6 7 9 5 92 7 8670 17 5 267 7 9 5 ƺ 1 855 17 66 7 50 1 2 803 56 6 2 1 29 25 2 7 5 255 6321 1 7 50 1 6 2 22 17 02 8 25 1 7 6 7 5 9 6 216 5 9 51 6 5 37 21 7 33 3 25 1 5 83 7 7 5 3 27 5 6 33 25 1 3 57 5 83 7 5 21 21752 5 8 72 5 1 335 7 7 8 1 1 21752 5 7 7 7 5 1 02 3 57 7 6...

Страница 33: ...33 OPM 141 E THREE PHASE AC WIRE HIGH AND LOW WYE WIRING DIAGRAMS THREE PHASE AC WIRING DELTA SINGLE PHASE 311 WINDING ...

Страница 34: ...or for your failure to ensure the performance of all scheduled maintenance As the off road engine owner you should however be aware that FPT Industrial S p A may deny your warranty coverage if your off road engine or part has failed due to abuse neglect improper maintenance or unapproved modifications Your engine is designed to operate on diesel only Use of any other fuel may result in your engine...

Страница 35: ...iginal equipment Fuel injection system Fuel injection part Fuel injectors Fuel injection lines Air induction system Intake manifold Turbocharger system includes exhaust manifold Charger air cooler Positive Crankcase Ventilation PCV system if applicable PCV valve Oil cap filler Exhaust after treatment devices if applicable Diesel Oxidation Catalyst DOC Diesel Particulate Filter DPF Selective Cataly...

Страница 36: ...at requires replacement of engine part or component of the product that is no longer manufactured or available Additionally WINCO Inc will not be liable for any engine replacement that may require an emissions tier level change THERE ARE NO EXPRESS WARRANTIES OTHER THAN THOSE DESCRIBED HEREIN THERE ARE NO OTHER WARRANTIES EXPRESSED OR IMPLIED OR OTHERWISE CREATED UNDER THE UNIFORM COMMERCIAL CODE ...

Отзывы: