Connect

20

DN 65

DN 80

DN 100

Screw diameter

M16

Strength class

≥ 4.6

Tightening torque

95 Nm

Screw length

≥ 65 mm

≥ 70 mm

Never interconnect 2 combination flanges.

5.6 

Insulate

Only utilise thermal insulation shell in heating applica-

tions with fluid temperature > 20 °C.

During cold and air-conditioning applications use stand-

ard, diffusion-proof insulation materials. Empty conden-

sation drain 

➜ 

Fig. 

11

.

5.7 

Following installation

 

Check impermeability of the pipe/flange connection.

Connect

6.1 

Personnel requisition

The electrical connection may only be performed by a 

qualified electrician.

6.2 

Requirements

ATTENTION

 

Wrong connection of the pump leads to damage to the 

electronics.

 

Observe voltage rating on the rating plate.

 

Maximum back-up fuse: 10 A, inactive or circuit breaker 

with C characteristic

 

Never connect to an uninterruptible power supply or 

IT-networks.

 

During external connection of the pump deactivate a 

pulse of the voltage (for example phase angle control).

 

Switching the pump via triacs/solid-state relays must be 

examined on a case-by-case basis.

 

During deactivation with on-site power relay:  

Rated current ≥ 10 A, rated voltage 250 V AC

 

Note switching frequency:

 

Switching on/off mains voltage ≤ 100/24 h

 

≤ 20/h at a switching frequency of 1 min between 

switching on/off via mains voltage

 

Secure pump with a residual-current device (type A or B). 

 

Leakage current I

eff

 ≤ 3.5 mA

 

The electrical connection must be made via a fixed 

connecting cable equipped with a connector device or an 

all-pole switch with a contact opening width of at least 

3 mm (VDE 0700/Part 1).

 

To protect against leakage and for strain relief to the 

threaded cable connection use a connection pipe with 

sufficient outer diameter 

➜ 

Fig. 

15

.

 

Use a heat-resistant connecting cable where fluid tem

-

peratures exceed 90 °C.

 

Lay the connection pipe in such a way that it touches 

neither the pipes nor the pump.

Содержание Yonos MAXO Series

Страница 1: ...erings og driftsveiledning 85 FI Asennus ja k ytt ohje 92 DA Installations og driftsvejledning 99 Wilo Yonos MAXO D 2 172 446 Ed 01 2016 08 Wilo de Einbau und Betriebsanleitung en Installation and ope...

Страница 2: ...17 18 19 6 6 7 8 9a 5 5 9b 10 5 5 11 12 13 14 15 16 5 6 6 6 6 3 6 6 7 2 20...

Страница 3: ...ble place at all times Observe instructions and labelling on the pump Observe local regulations where the pump is installed Observe details instructions on the Internet page 2 1 2 Original instruction...

Страница 4: ...nce on the delivery rate 2 1 Type key Example Yonos MAXO D 32 0 5 11 Yonos MAXO Pump designation D Double pump 32 Flange connection DN 32 0 5 11 0 5 Minimum delivery head in m 11 Maximum delivery head...

Страница 5: ...uthorised conversions Use exclusively authorised accessories and authorised spare parts Never operate with phase angle control 3 2 Operator responsibilities Keep children and people with reduced physi...

Страница 6: ...only for heating applications 4 3 Transport inspection Following delivery immediately check for damage and in tegrity Where necessary make a complaint immediately 4 4 Transportation and storage Only c...

Страница 7: ...lling outdoor observe detailed instructions on the Internet page 2 5 4 Align The motor head must be aligned according to installation position Check permissible installation positions Fig 5 Dismantle...

Страница 8: ...power supply or IT networks During external connection of the pump deactivate a pulse of the voltage for example phase angle control Switching the pump via triacs solid state relays must be examined...

Страница 9: ...ntrol module has failed DANGER Danger to life through voltage transmission if mains and SSM pipe are led together through a 5 wire cable Do not connect SSM pipe to protective low voltage Use 5 x 1 5 m...

Страница 10: ...caighde in chomhchuibhithe na hEorpa d dtagra tear sa leathanach roimhe seo HR Hrvatski HU Magyar EZ IZJAVA O SUKLADNOSTI EK MEGFELEL S GI NYILATKOZAT i uskla enim europskim normama navedenim na preth...

Страница 11: ...rupa y netmeliklerine ve ulusal kanunlara uygun oldu unu beyan etmektedir 2006 42 2014 30 2009 125 Machines 2006 42 EG Elektromagnetische Compatibiliteit 2014 30 EG Energiegerelateerde producten 2009...

Страница 12: ...tirilmesini isteme haklar ndan birini kullanabilir 4 T keticinin bu haklardan cretsiz onar m hakk n se mesi durumunda sat c i ilik masraf de i tirilen par a bedeli ya da ba ka herhangi bir ad alt nda...

Страница 13: ......

Страница 14: ...wilo it Kazakhstan WILO Central Asia 050002 Almaty T 7 727 312 40 10 info wilo kz Korea WILO Pumps Ltd 20 Gangseo Busan T 82 51 950 8000 wilo wilo co kr Latvia WILO Baltic SIA 1019 Riga T 371 6714 522...

Страница 15: ...WILO SE Nortkirchenstra e 100 D 44263 Dortmund Germany T 49 0 231 4102 0 F 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: