EN
Installation
19
5.3
Preparing the installation
◾
Branch off the safety feed ahead of the pump when
installing in feed of open systems (EN 12828).
◾
Complete all welding and brazing tasks.
◾
Flush unit.
◾
Arrange shut-off devices in front of and behind the
pump. Laterally align the shut-off device above the pump
so that the leakage water does not drip on the control
module.
◾
Make sure that the pump can be installed free of me-
chanical stresses.
◾
Allow a 10 cm distance around the control module so that
it does not overheat.
◾
Observe permissible installation position
➜
Fig.
.
When installing outdoor observe detailed
instructions on the Internet
➜
page 2.
5.4
Align
The motor head must be aligned according to installation
position.
◾
Check permissible installation positions
➜
Fig.
.
◾
Dismantle motor head and carefully turn
➜
Fig.
.
Do not remove motor from pump housing.
ATTENTION
Damage to the gasket causes leakage.
◾
Do not remove gasket.
5.5
Installation
➜
Fig.
to
Flange-end pump PN 6
DN 32
DN 40
DN 50
Screw diameter
M12
Strength class
≥ 4.6
Tightening torque
40 Nm
Screw length
≥ 55 mm
≥ 60 mm
DN 65
DN 80
DN 100
Screw diameter
M12
M16
Strength class
≥ 4.6
Tightening torque
40 Nm
95 Nm
Screw length
≥ 60 mm
≥ 70 mm
Flange-end pump PN 10 and PN 16
(no combination flange)
DN 32
DN 40
DN 50
Screw diameter
M16
Strength class
≥ 4.6
Tightening torque
95 Nm
Screw length
≥ 60 mm
≥ 65 mm