Installation and operating instructions Wilo VR System

21

Signal lamps/LEDs

(layout Fig. 1, item 4)

Green LED run signal

 indicates the system's operational readiness. It lights up even if no pump is running.

Red LED

 for 

low water

 indicates by going on continuously whether the system has shut down after the detection 

of a low water level. Flashing indicates that a low-water signal applied; however, there is currently no fault. Flashing 
stops when the fault is acknowledged by turning the rotary knob.

Red LED

 for 

overpressure

 indicates a fault if the system has shut down due to a system pressure being too high. If this 

light flashes, that indicates a previous overpressure fault that no longer applies. Flashing stops when the fault is 
acknowledged by turning the rotary knob.

Green LED 

for 

run signal of pumps 

(pump status) indicates that at least one pump is being controlled

Red LED

 for 

pump malfunction

 (pump status) indicates that a fault is indicated by at least one pump. This LED does 

not light up in the event of a sensor fault or controller fault.

4.2.2 Menu structure 

The complete menu structure consists of the fol-
lowing elements:

• Standard display 
• Operating modes menu
• Controller setting menu (with operation indicator 

and error memory)
The current system pressure is displayed on the 

standard display

. In addition, the 

 symbol 

indicates whether standby pump mode was set. 
A flashing symbol indicates that no standby pump 
is available (e.g. due to a pump fault). 
(1) By briefly pressing (< 2 seconds) the red rotary 

knob, the standard display switches to the 

Operating modes menu

. In this menu, the 

corresponding pump (P1, P2, P3, P4) is selected 
by turning the rotary knob. Only the number of 
pumps that were configured via the DIP switches 
appears on the display (see Section 4.2.3).
After selecting the pump, this selection must 
be confirmed by briefly pressing the rotary knob. 
Then, the current operating mode of the pump 
is displayed:

(The key symbol 

 indicates any error 

message of the pump. It also indicates the 
“Ext.Off” status or a sensor fault.)
The operating mode of the pump can be set by 
turning the rotary knob to the left or right. 
Then, pressing it briefly takes you back to the 
standard display.

(2) By continuously pressing (> 2 seconds) the red 

rotary knob, the standard display switches back 
to the 

Controller setting menu

. A menu item 

(Tab. 1) can be selected by turning the knob. 
To be able to change the values, the rotary 
knob needs to be pressed briefly at the corre-
sponding point of the menu. That displays the 
previously set parameter on the display and it 
can be adjusted by turning the rotary knob.
Pressing the rotary knob briefly takes you back 
to the selection of menu items and pressing it 
continuously takes you back to the standard 
display.

auto

Automatic mode

(speed, activation and deacti-
vation of the pump is control-
led by the controller)

on

Manual mode

(maximum pump speed)

off

Off

(pump stopped)

Содержание Wilo-VR-System

Страница 1: ...D Einbau und Betriebsanleitung GB Installation and operating instructions F Notice de montage et de mise en service NL Inbouw en bedieningsvoorschriften Wilo VR System 2 040 503 Ed 02 2011 08 Wilo...

Страница 2: ...Fig 1 Fig 2 1 2 3 4...

Страница 3: ...Fig 3 8...

Страница 4: ...Fig 4 Fig 5...

Страница 5: ...Fig 6 Fig 7...

Страница 6: ......

Страница 7: ...pare parts 18 2 8 Improper use 18 3 Transport and interim storage 18 4 Description of the product and accessories 19 4 1 Description of the control device 19 4 1 1 Function description 19 4 1 2 Design...

Страница 8: ...ure 40 C Pressure sensor P 0 6 bar 0 10 bar 0 16 bar 0 25 bar I 4 20 mA Mains side fuse protection according to wiring diagram included Further electrical technical data can be found on the technical...

Страница 9: ...g against touching moving com ponents suchasthecoupling mustnotberemoved whilst the product is in operation Leakages e g from the shaft seals of hazardous fluids which are explosive toxic or hot must...

Страница 10: ...low water protection see also Fig 5 Chapter 5 provides more information 4 1 3 Operating modes of the system Normal operation An electronic pressure transducer provides the actual system pressure valu...

Страница 11: ...ement is only possible if the fault no longer applies Overpressure An overpressure threshold can be set to protect the building installation If the system pressure rises above this threshold for a per...

Страница 12: ...bol indicates whether standby pump mode was set A flashing symbol indicates that no standby pump is available e g due to a pump fault 1 By briefly pressing 2 seconds the red rotary knob the standard d...

Страница 13: ...otary knob Pressing the rotary knob continuously takes you back to the standard display 4 The Error memory menu E r r is described in more detail in Section 8 3 Error memory for faults NOTE It is only...

Страница 14: ...structure Operation menu Error memory menu Anticlockwise rotation press rotary knob Delete turn rotary knob Back Press rotary knob 2 sec Press rotary knob 2 sec Turn rotary knob Press rotary knob Del...

Страница 15: ...ion The VR Control control device is delivered as a com pletely assembled unit The wall mounted instal lation of the devices is performed using 4 screws 8mm e g on abaseframeorthewall Install the cont...

Страница 16: ...the Sensor terminal Fig 6 Use a shielded cable place the shield on one side in the control device CAUTION Risk of damage to the product Do not connect any external voltage to the ter minals External...

Страница 17: ...water LED Is on At least one pump is running Low water signal is applied however period of time below the delay time T1 Is on Pumps off Low watersignalactive pumpsstoppedoncethedelaytime T1 passed Fl...

Страница 18: ...ctuates severely Diaphragm vessel closed or filled incorrectly Volume flow too high Suction side pressure switch faulty or connected incorrectly Check controller parameters Check dry running protectio...

Страница 19: ...sed to control the pumps directly with an ana logue voltage between 0 10 V that is set via the potentiometer item 5a DANGER Risk of fatal injury Use suitably insulated screwdrivers in accord ance with...

Страница 20: ...English Installation and operating instructions Wilo VR System 29...

Страница 21: ...ctive Compatibilit lectromagn tique directive Niederspannungsrichtlinie 2006 95 EG Low voltage directive Directive basse tension und entsprechender nationaler Gesetzgebung and with the relevant nation...

Страница 22: ...m Niniejszym deklarujemy z pe n odpowiedzialno ci e dostarczony wyr b jest zgodny z nast puj cymi dokumentami Sm rnice o elektromagnetick kompatibilit 2004 108 ES dyrektyw dot kompatybilno ci elektro...

Страница 23: ...23 889500 wilo wilo hu India WILO India Mather and Platt Pumps Ltd Pune 411019 T 91 20 27442100 service pun matherplatt co in Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 citra...

Страница 24: ...gartenstra e 1 3 95030 Hof T 09281 974 550 F 09281 974 551 Werkskundendienst Geb udetechnik Kommune Bau Bergbau Industrie WILO SE Nortkirchenstra e 100 44263 Dortmund T 0231 4102 7900 T 01805 W I L O...

Страница 25: ...0 1...

Страница 26: ......

Отзывы: