background image

English

Installation and operating instructions Wilo VR System

25

Mains connection 1~230 V:

The 3-wire cable (L1, N, PE) is to be provided onsite. 
The connection is established at the main switch 
(Fig. 2, item 1), the PE is connected to the earth 
bar.

Mains connection 3~400 V:

The 4-wire cable (L1, L2, L3, PE) is to be provided 
onsite. The connection is established at the main 
switch (Fig. 2, item 1) or for systems of higher 
power at the terminal strips in accordance with 
the wiring diagram, the PE is connected to the 
earth bar.

Pump mains connections:
CAUTION! Risk of damage to the product!
Observe the installation and operating instruc-
tions for the pumps!

The connection of the pumps with integrated fre-
quency converter is to be established directly at 
the circuit breakers (2, 4, 6), or for systems of 
higher power at the terminal strips in accordance 
with the wiring diagram enclosed (Fig. 2, item 4). 
The PE is to be connected to the earth bar. If exter-
nal frequency converters are used, shielded cables 
must always be used. To achieve the best shield-
ing effect, fit the shield on both sides! 

Pump control signals:
CAUTION! Risk of damage to the product!
Observe the installation and operating instruc-
tions for the pumps!

Connect them to the base board at terminal 

“Pumps 1...4”

 (Fig. 6) and to the terminal strips of 

the pumps.
Use a shielded cable, place the shield on one side 
in the control device.
If a three-wire cable is used (as shown in Fig. 6) 
an “SBM” terminal must be bridged with the earth 
terminal of the 0...10 V input in the pump terminal 
box. 
If a four-wire cable is used, this bridging may also 
be performed in the control device.

CAUTION! Risk of damage to the product!
Do not connect any external voltage to the ter-
minals!

Pressure sensor 4...20 mA:

Connect the sensor according to the installation 
and operating instructions correctly to the base 
board at the 

“Sensor”

 terminal (Fig. 6).

Use a shielded cable, place the shield on one side 
in the control device.

CAUTION! Risk of damage to the product!
Do not connect any external voltage to the ter-
minals!

External On/Off switching:

Remote On/Off switching by means of a poten-
tial-free contact (NC contact) can be connected 
via the 

“Ext. Off”

 terminals of the base board (Fig. 3) 

after removing the jumper (premounted at the 
factory). That gives you the option of switching 
the system on and off (Fig. 6).

Contact closed:

Automatic On

Contact open:

Automatic Off, “OFF” signal on 
the display

Contact load:

24 V DC/10 mA

CAUTION! Risk of damage to the product!
Do not connect any external voltage to the ter-
minals!

Protection against low water level:

Protection function against low water level by 
means of a potential-free contact (NC contact) 
can be connected via the 

“dry”

 terminals of the 

base board (Fig. 3) after removing the jumper 
(premounted at the factory). (Fig. 6).

Contact closed:

No low water

Contact open:

Low water

Contact load:

24 V DC/10 mA

CAUTION! Risk of damage to the product!
Do not connect any external voltage to the ter-
minals!

Collective run/collective fault signals SBM/SSM:

Potential-free contacts (changeover contacts) for 
external signals are available via the 

“Failure”

 

(collective fault signal) and 

“Operation”

 (collective 

run signal) terminals. 
Potential-free contacts, max. contact load (see 
Fig. 6)

• 250 V ~/1 A ohmic load,
• 30 V-/1 A ohmic load

Actual pressure indication:

A 0 ... 10 V voltage signal for an external display 
option of the current actual pressure is available 
via the 

“Pout”

 terminal. 0 ... 10 V corresponds to 

the pressure sensor signal 0 ... pressure sensor 
limit value.

For 
example:

Sensor

Display 
range

Voltage/
pressure

16 bar

0 … 16 bar

1 V = 1.6 bar

CAUTION! Risk of damage to the product!
Do not connect any external voltage to the ter-
minals!

Optional individual run and fault signals of the 
pumps and low water protection system:

EBM 1 ... EBM 4, ESM 1 ... ESM 4, WM
Potential-free contacts (changeover contacts), 
max. contact load (see Fig. 5) 

• 250 V ~/1 A ohmic load, 
• 30 V-/1 A ohmic load

Содержание Wilo-VR-System

Страница 1: ...D Einbau und Betriebsanleitung GB Installation and operating instructions F Notice de montage et de mise en service NL Inbouw en bedieningsvoorschriften Wilo VR System 2 040 503 Ed 02 2011 08 Wilo...

Страница 2: ...Fig 1 Fig 2 1 2 3 4...

Страница 3: ...Fig 3 8...

Страница 4: ...Fig 4 Fig 5...

Страница 5: ...Fig 6 Fig 7...

Страница 6: ......

Страница 7: ...pare parts 18 2 8 Improper use 18 3 Transport and interim storage 18 4 Description of the product and accessories 19 4 1 Description of the control device 19 4 1 1 Function description 19 4 1 2 Design...

Страница 8: ...ure 40 C Pressure sensor P 0 6 bar 0 10 bar 0 16 bar 0 25 bar I 4 20 mA Mains side fuse protection according to wiring diagram included Further electrical technical data can be found on the technical...

Страница 9: ...g against touching moving com ponents suchasthecoupling mustnotberemoved whilst the product is in operation Leakages e g from the shaft seals of hazardous fluids which are explosive toxic or hot must...

Страница 10: ...low water protection see also Fig 5 Chapter 5 provides more information 4 1 3 Operating modes of the system Normal operation An electronic pressure transducer provides the actual system pressure valu...

Страница 11: ...ement is only possible if the fault no longer applies Overpressure An overpressure threshold can be set to protect the building installation If the system pressure rises above this threshold for a per...

Страница 12: ...bol indicates whether standby pump mode was set A flashing symbol indicates that no standby pump is available e g due to a pump fault 1 By briefly pressing 2 seconds the red rotary knob the standard d...

Страница 13: ...otary knob Pressing the rotary knob continuously takes you back to the standard display 4 The Error memory menu E r r is described in more detail in Section 8 3 Error memory for faults NOTE It is only...

Страница 14: ...structure Operation menu Error memory menu Anticlockwise rotation press rotary knob Delete turn rotary knob Back Press rotary knob 2 sec Press rotary knob 2 sec Turn rotary knob Press rotary knob Del...

Страница 15: ...ion The VR Control control device is delivered as a com pletely assembled unit The wall mounted instal lation of the devices is performed using 4 screws 8mm e g on abaseframeorthewall Install the cont...

Страница 16: ...the Sensor terminal Fig 6 Use a shielded cable place the shield on one side in the control device CAUTION Risk of damage to the product Do not connect any external voltage to the ter minals External...

Страница 17: ...water LED Is on At least one pump is running Low water signal is applied however period of time below the delay time T1 Is on Pumps off Low watersignalactive pumpsstoppedoncethedelaytime T1 passed Fl...

Страница 18: ...ctuates severely Diaphragm vessel closed or filled incorrectly Volume flow too high Suction side pressure switch faulty or connected incorrectly Check controller parameters Check dry running protectio...

Страница 19: ...sed to control the pumps directly with an ana logue voltage between 0 10 V that is set via the potentiometer item 5a DANGER Risk of fatal injury Use suitably insulated screwdrivers in accord ance with...

Страница 20: ...English Installation and operating instructions Wilo VR System 29...

Страница 21: ...ctive Compatibilit lectromagn tique directive Niederspannungsrichtlinie 2006 95 EG Low voltage directive Directive basse tension und entsprechender nationaler Gesetzgebung and with the relevant nation...

Страница 22: ...m Niniejszym deklarujemy z pe n odpowiedzialno ci e dostarczony wyr b jest zgodny z nast puj cymi dokumentami Sm rnice o elektromagnetick kompatibilit 2004 108 ES dyrektyw dot kompatybilno ci elektro...

Страница 23: ...23 889500 wilo wilo hu India WILO India Mather and Platt Pumps Ltd Pune 411019 T 91 20 27442100 service pun matherplatt co in Indonesia WILO Pumps Indonesia Jakarta Selatan 12140 T 62 21 7247676 citra...

Страница 24: ...gartenstra e 1 3 95030 Hof T 09281 974 550 F 09281 974 551 Werkskundendienst Geb udetechnik Kommune Bau Bergbau Industrie WILO SE Nortkirchenstra e 100 44263 Dortmund T 0231 4102 7900 T 01805 W I L O...

Страница 25: ...0 1...

Страница 26: ......

Отзывы: