8 Operating faults

De-energise the pump before each
intervention and secure against non-
authorised restarts!

All of the incidents listed below will lead to 
a switch-off via the error relay.

De-energise the pump before each intervention.
If the fluid is toxic, corrosive or hazardous for
personnel, then WILO or the authorised repair
company must be informed of the situation.
Clean the pump in such cases in order to ensure
absolute safety for the craftsmen performing
the repairs.

If the pump is at a complete standstill and an intervention is required, disconnect the power supply, wait until the LEDs have gone out completely, eliminate the fault
and reconnect the power supply. If a major fault is present, then an after-sales service employee must be called in.

If the operating fault cannot be rectified, then please
contact your local professional tradesmen or the Wilo
after-sales service in your vicinity.

ATTENTION!

Display

Frequency converter
behaviour

Fault/possible causes

Elimination

Green
LED

Red
LED

Reaction time
up to standstill
Frequency
converter

Waiting time
before
switching
back on

Relay status

Contact

Off

On

No standstill

/

Open

a) Frequency converter sup-

ply has undervoltage.

- Check voltage at the

terminals of the
frequency converter.

Off

On

Immediate

No switching
back on

Open

b) Frequency converter 

supply has overvoltage.

- Check voltage at the

terminals of the
frequency converter.

Off

On

Immediate

No switching
back on

Open

c) The motor has a short-

circuit.

- Dismantle motor/

frequency converter
of the pump and have
it checked or replace
it.

Off

On

<10 s

No switching
back on

Open

d) The pump is overloaded.

- excessive density and/

or viscosity of the
pumped fluid.

Off

On

<60 s

No switching
back on

Open

e) The sensor cable 

(4-20 mA) is disconnected
(only Mode 2).

- Check correct current

supply and cabling of
the sensor.

Содержание MHIE 1ph

Страница 1: ...operating instructions F Notice de montage et de mise en service NL Inbouw en bedieningsvoorschriften E Instrucciones de instalaci n y funcionamiento I Istruzioni di montaggio uso e manutenzione P Man...

Страница 2: ...Fig 1 Fig 3 Fig 2 Fig 4 Fig 5 or ou or ou...

Страница 3: ...Fig 6 Fig 8 Fig 7 or ou or ou...

Страница 4: ...Fig 9 Fig 10...

Страница 5: ...operating instructions 15 F Notice de montage et de mise en service 26 NL Inbouw en bedieningsvoorschriften 38 E Instrucciones de instalaci n y funcionamiento 50 I Istruzioni di montaggio uso e manut...

Страница 6: ...ticular the failure to observe these instruc tions could lead to the following hazards Failure of important functions of the pump instal lation Hazards to personnel resulting from electrical mechanica...

Страница 7: ...ssel Pos 9 or potable water network Pos 10 5 1 Installation Install the pump at a readily accessible location which is protected against external influences excessive rain or sunlight frost and which...

Страница 8: ...fications The electrical properties frequency voltage nominal current of the motor frequency convert er are indicated on the name plate of the motor of the pump A check is to be made as to whether the...

Страница 9: ...remove upper cover of the frequency converter Mains connection Connect three lines of the cable to the 3 connection terminals of the board Phase Neutral Earth Connecting the inputs outputs 3 operating...

Страница 10: ...3 cores 0 V 0 10 V 24 V 1 1 10 V 0 V 24 V 24 V 2 3 4 5 6 7 8 9 10 11 12 13 14 0 V 4 20 mA 24 V 0 V 0 10 V 24 V 2 Connection of the potentiometer Connection terminals Inputs outputs of the frequency co...

Страница 11: ...12 13 14 4 Possible connections It is possible to start or stop the pump with the external control potential free contact this function takes precedence over the other functions This external control...

Страница 12: ...Diagrams 2 4 3 6 3 2 1 4 2 1 5 3 1 6 3 1 4 3 1 7 3 1 5 4 ATTENTION Operating modes Mode 1 Mode 3 0 20 mA Mode 3 0 10 V Mode 2 PI control sensor 4 20 mA Mode 2 PI control sensor 0 10 V Mode 2 PI contro...

Страница 13: ...0 10 Sensor 0 10 V Input voltage V Pressure in of the sensor measurement range 100 0 2 20 Setpoint 0 20 mA Range in which the frequency converter stops Input current level mA Pressure in of the senso...

Страница 14: ...ons concerning commissioning see instruction manual for the pressure boosting sys tem During normal operation the status of the LEDs is as follows see Fig 9 Pos 17 18 6 2 Preparatory flushing Because...

Страница 15: ...he specification on the pump shield 7 Maintenance The pump s must be de energised and all non authorised restarts must be pre vented before any maintenance work is done Never undertake maintenance wor...

Страница 16: ...cannot be rectified then please contact your local professional tradesmen or the Wilo after sales service in your vicinity ATTENTION Display Frequency converter behaviour Fault possible causes Elimina...

Страница 17: ...as not been maintained b The suction line has a smaller circ umference than that of the pump c Suction strainer and suction line are partially blocked a Check correct setting of the nominal values set...

Страница 18: ...1008 EG Electromagnetic compatibility directive Compatibilit lectromagn tique directive Niederspannungsrichtlinie 2006 95 EG Low voltage directive Direction basse tension Angewendete harmonisierte No...

Страница 19: ...EMV Elektromagnetisk kompatibilitet 2004 1008 EG EG Lavspenningsdirektiv 2006 95 EG Anvendte harmoniserte standarder s rlig 1 FIN CE standardinmukaisuusseloste Ilmoitamme t ten ett t m laite vastaa s...

Страница 20: ...lint Budapest T 36 23 889500 wilo wilo hu Ireland WILO Engineering Ltd Limerick T 353 61 227566 sales wilo ie Italy WILO Italia s r l 20068 Peschiera Borromeo Milano T 39 25538351 wilo italia wilo it...

Страница 21: ...63 Dortmund T 0231 4102 7900 T 01805 W I L O K D 9 4 5 6 5 3 F 0231 4102 7126 Erreichbar Mo Fr von 7 17 Uhr Wochenende und feiertags 9 14 Uhr elektronische Bereitschaft mit R ckruf Garantie Kundendien...

Отзывы: