Maintenance and repair
en
Installation and operating instructions DrainLift S
25
10
Maintenance and repair
WARNING
Warning: danger of infection!
Bacteria can form in sewage which can lead to infections. Wear the following pro-
tective equipment while performing the work:
• Closed safety goggles
• Breathing mask
• Protective gloves
For reasons of safety, and thus to guarantee correct function of the lifting unit, it must
always be maintained and repaired by professional service providers (e.g. customer ser-
vice). The maintenance intervals for lifting units must be carried out in accordance with
EN 12056‑4:
▪ ¼ year in the case of commercial companies
▪ ½ year for multi-family houses
▪ 1 year for single-family houses
A log must be kept of all maintenance and repair work. The service provider and oper-
ator must sign the log.
10.1
Personnel qualifications
▪ Electrical work: Electrical work must be carried out by a qualified electrician (in accord-
ance with EN 50110-1).
▪ Maintenance tasks: The technician must be familiar with the lifting unit. The technician
must also meet the requirements of EN 12056 (including the individual parts).
11
Spare parts
Spare parts are ordered via customer service. To avoid return queries and incorrect or-
ders, the serial or article number must always be supplied.
Subject to change without
prior notice.
12
Disposal
12.1
Protective clothing
Used protective clothing must be disposed off in accordance with the locally applicable
guidelines.
12.2
Information on the collection of
used electrical and electronic
products
Proper disposal and appropriate recycling of this product prevents damage to the envir-
onment and dangers to your personal health.
NOTICE
Disposal in domestic waste is forbidden!
In the European Union, this symbol can appear on the product, the packaging or the
accompanying documentation. It means that the electrical and electronic products
in question must not be disposed of along with domestic waste.
To ensure proper handling, recycling and disposal of the used products in question,
please note the following points:
▪ Only hand over these products at designated, certified collecting points.
▪ Observe the locally applicable regulations!
Please consult your local municipality, the nearest waste disposal site, or the dealer who
sold the product to you for information on proper disposal. For further information on
recycling, go to www.wilo-recycling.com.
13
Appendix
13.1
Electrical connection diagram
1
Motor contactor
2
Earth terminal
3
Terminal strip for signal transmitter and alarm signal