Installation and operating instructions Wilo-Control DigiCon/DigiCon-A
27
English
6. 2 Functions and operation of the interface converter/manual operation level
6.2.1 Signal lamps
DigiCon
DigiCon-A
“Stand-by Interface
Converter” signal lamp
Fig. 1, 2, item 1
LED lights up green
continuously:
• 24 VDC supply voltage
available.
LED is off:
• 24 VDC supply voltage not
available.
LED lights up green
continuously:
• Supply voltage via DigiCon
available.
LED is off:
• Supply voltage via DigiCon
not available.
“Pump communica-
tion” signal lamp
Fig. 1, item 2
LED is off:
• Pump has not logged on.
LED lights up green
continuously:
• “Pump – Interface
Converter” communication
working perfectly.
LED lights up red continuously:
• Communication problem
between pump and interface
converter
“Pump fault” signal
lamp
Fig. 2, item 3
LED is off:
• Pump not faulty.
LED lights up red
continuously:
• Pump is faulty.
“Single pump or dou-
ble pump operation
ma” signal lamp
(ma = Master)
Fig. 2, item 4
LED is off:
• Single pump or double
pump ma stationary.
LED lights up green continu-
ously:
• Single pump or double
pump ma is operating.
“Double pump opera-
tion sl”
signal lamp
(sl = Slave)
Fig. 2, item 5
LED is off:
• Double pump sl stationary.
LED lights up green
continuously:
• Double pump sl is operating.
Tab. 5