English
34
WILO SE 04/2009
6.2.6 Priority of the specified setpoint
• Tab. 12 shows the order of priority of the specified setpoint
• The setpoint via the RS 485/PLR interface overwrites the setpoint set at the
“setpoint” knob.
DIP switch no.
Significance
1
2
7
(=128)
2
2
6
(=64)
3
2
5
(=32)
4
2
4
(=16)
5
2
3
(=8)
6
2
2
(=4)
Resultant
pump address
No. of the pump/
No. of the DigiCon
Pump 1/1
0
0
0
0
0
0
0
Pump 2/1
1
Pump 3/1
2
Pump 4/1
3
...
...
...
...
...
...
...
...
Pump 1/12
0
0
1
0
1
1
44
Pump 2/12
45
Pump 3/12
46
Pump 4/12
47
...
...
...
...
...
...
...
...
Pump 1/26
0
1
1
0
0
1
100
Pump 2/26
101
Pump 3/26
102
Pump 4/26
103
...
...
...
...
...
...
...
...
Pump 1/64
1
1
1
1
1
1
252
Pump 2/64
253
Pump 3/64
254
Pump 4/64
255
0: DIP switch “off”
1: DIP switch “on”
Tab. 11
DigiCon/DigiCon-A
Manual operation level Analogue input “0-10V”
Highest priority
“Setpoint” knob
Bus level RS 485/PLR
Bus level RS 485/PLR
Lowest priority
Tab. 12