Commissioning
zh-CHS
安装及操作说明 Wilo-Atmos TERA-SCH
75
小心
Risk of property damage due to condensation formation!
When using the pump in air-conditioning or cooling applications, condensate can
form, which could damage the motor.
• Open the condensate drainage holes in the motor housing at regular intervals and
drain the condensate.
7.1
Personnel qualifications
ƒ
Electrical work: A qualified electrician must carry out the electrical work.
ƒ
Operation/control: Operating personnel must be instructed in the functioning of the
complete system.
7.2
Filling and venting
注意
The standard version of the Atmos TERA-SCH pump has an air vent valve on the top
of the casing, next to the air cock. The suction line and pump are vented via a
suitable venting device on the pressure flange of the pump. An optional air vent
valve is available.
警告
Risk of personal injury and property damage due to extremely hot or
extremely cold pressurised fluid!
Depending on the temperature of the fluid, when the venting screw is opened
completely, extremely hot or extremely cold fluid in liquid or vapour form may
escape or shoot out at high pressure. Fluid may shoot out at high pressure
depending on the system pressure.
• Make sure the venting screw is in a suitable, secure position.
• Always exercise caution when opening the venting screw.
Procedure for venting systems where the fluid level lies above the suction port of
the pump:
ƒ
Open the isolating valve on the pressure side of the pump.
ƒ
Slowly open the isolating valve on the suction side of the pump.
ƒ
To vent, open the air cock on the top of the pump.
ƒ
Close the air cock as soon as fluid escapes at the top of the housing.
Procedure for filling/venting systems with a non-return valve, where the fluid level
lies below the suction port of the pump:
ƒ
Close the isolating valve on the pressure side of the pump.
ƒ
Open the the isolating valve on the suction side of the pump..
ƒ
Fill fluid in via a funnel until the suction line and the pump are completely filled.
ƒ
Vent the pump opening the venting cock on the top of the pump.
ƒ
Close the air cock as soon as fluid escapes at the top of the casing.
7.3
Checking the direction of rotation
小心
Risk of property damage!
Danger of damage to the pump parts that rely on the fluid supply for lubrication.
• Before checking the direction of rotation and commissioning, the pump must be
filled with fluid and vented.
• Do not operate the pump with the isolating valves closed.
The motor can be placed on the right or left side of the pump.
The check of the
rotation direction of the motor is a mandatory step in the commissioning procedure
of the pump set!
An arrow on top part of the pump housing indicates the correct
direction of rotation.
Содержание Atmos TERA SCH 150-230
Страница 2: ......
Страница 3: ...3 English 4 Chinese simplified 50...
Страница 48: ...en Appendix 48 WILO SE 2020 10 13 Appendix 13 1 Examples for typical installation layouts Fig 31...
Страница 94: ...zh CHS Appendix 94 WILO SE 2020 10 13 Appendix 13 1 Examples for typical installation layouts Fig 31...
Страница 95: ...Appendix zh CHS Wilo Atmos TERA SCH 95 13 2 Examples for proper and inappropriate pipework 2x Fig 32...
Страница 96: ......
Страница 97: ......
Страница 98: ......
Страница 99: ......