Installation and electrical connection

en

Installation and operating instructions Wilo-Atmos TERA-SCH

21

Fig. 12: 

Levelling screws on the base surface

NOTICE
The anchor bolts must fit in the fastening bores of the base frame.

They must meet the relevant standards and be sufficiently long, so that a firm fit in
the base is guaranteed.

Fig. 13: 

Levelling and aligning the base frame

Fig. 14: 

Anchor bolt

ƒ

Pour in anchor bolts with concrete. After the concrete has set, tighten the anchor
bolts evenly and firmly.

ƒ

Align the unit so that the pipes can be connected to the pump stress-free.

6.5.3

Pouring out the base frame

The base frame can be poured out after fixing. The process of pouring out reduces vi-
brations to a minimum.

ƒ

Wet the base surface before pouring out the concrete.

ƒ

Use a suitable, non-shrink mortar for pouring out.

ƒ

Pour the mortar through the openings in the base frame. Be sure to avoid hollow
spaces.

ƒ

Plank the base and base frame.

ƒ

After curing, check the anchor bolts for a tight fit.

ƒ

Coat the unprotected surfaces of the base to protect from moisture.

6.6

Pipework

The pipe connections of the pump are fitted with dust caps so that no foreign objects
can penetrate during transport and installation.

ƒ

These caps must be removed before connecting pipes.

Содержание Atmos TERA SCH 150-230

Страница 1: ...Pioneering for You Wilo Atmos TERA SCH 6088794 Ed 01 2020 10 en Installation and operating instructions zh CHS...

Страница 2: ......

Страница 3: ...3 English 4 Chinese simplified 50...

Страница 4: ...of delivery 14 4 8 Accessories 14 4 9 Anticipated noise levels 14 4 10 Permissible forces and torques on the pump flanges 15 5 Transport and storage 16 5 1 Delivery 16 5 2 Transport 16 5 3 Storage 18...

Страница 5: ...omponents 38 9 7 Installation 39 10 Faults causes and remedies 42 10 1 Faults 42 10 2 Causes and remedies 43 11 Spare parts 44 12 Disposal 46 12 1 Oils and lubricants 46 12 2 Water glycol mixture 47 1...

Страница 6: ...information for the individual phases of the life cycle Fail ure to observe this information carries the following risks Injury to persons from electrical mechanical and bacteriological factors as we...

Страница 7: ...must Be instructed about locally applicable regulations governing accident prevention Have read and understood the installation and operating instructions Personnel must have the following qualificati...

Страница 8: ...orts discharge ports or other openings Avoid the penetration of foreign objects To this end leave the protective covers or packaging on until they have to be removed for installation Packaging and cov...

Страница 9: ...to noise Observe the sound pressure specifications on the motor rating plate The sound pres sure value of the pump is generally about the same value as that of the motor 2 dB A Observe the applicable...

Страница 10: ...he pumps are only approved for the fluids specified in the Technical data section Refer pump data sheet and order confirmation For any change in pumped fluid refer Wilo beforehand Intended use also in...

Страница 11: ...frequency con verter Operation on the frequency converter is permitted Refer to the documentation from the motor manufacturer for the relevant requirements and observe its contents 4 3 Type key Exampl...

Страница 12: ...I 2035 CH SWKI BT 102 01 fix leaky spots 4 5 Connection Details LVFKDUJH 3 Q 6 3 7 9 30 6XFWLRQ Fig 1 Additional connections on the housing Connection Details No Pump CG PG PM AC CDS CDD GD VG TG 1 SC...

Страница 13: ...ve nut 27 Dowel pin for wear ring 33 Bearing housing Non Drive End 37 Gland cover 14 Impeller key Table 2 Rotating element of gland pack version 2 3 4 5 6 7 8 9 10 26 26 25 24 14 27 21 27 25 26 26 10...

Страница 14: ...e End Table 4 Rotating element of mechanical seal version with sleeves 4 7 Scope of delivery Complete unit Atmos TERA SCH pump Base frame Coupling and coupling guard With or without electric motor Ins...

Страница 15: ...nd pressure levels within a cube shaped measuring area at a distance of 1 m from the surface of the motor Table 5 Anticipated noise levels for standard pump 50 Hz 4 10 Permissible forces and torques o...

Страница 16: ...in the compensation equation 5 Transport and storage 5 1 Delivery The pump is secured to a pallet ex works and is protected against dirt and moisture Check the shipment immediately on receipt for defe...

Страница 17: ...g transport Use the original packaging for this or choose equival ent packaging 5 2 1 Attaching the pump CAUTION Incorrect lifting can damage the pump Risk of falling Never lift the pump with slings e...

Страница 18: ...must be ensured during operation When using hoisting gears ensure that a second person is present to coordinate the procedure if necessary For example if the operator s field of vision is blocked The...

Страница 19: ...of the op erating space inflow conditions are complete and correct 6 3 Preparing the installation WARNING Risk of personal injury and property damage due to improper handling Never set up the pump uni...

Страница 20: ...ckness for manufactur ing This would prevent vibrations from being transmitted The base must be able to accommodate the forces vibrations and impact that occur Guidance values for dimensioning the bas...

Страница 21: ...he pipes can be connected to the pump stress free 6 5 3 Pouring out the base frame The base frame can be poured out after fixing The process of pouring out reduces vi brations to a minimum Wet the bas...

Страница 22: ...he pump connecting pieces The expansion of the pipes in the event of a temperature rise is to be compensated by suitable means Avoid air pockets in piping by means of appropriate installations NOTICE...

Страница 23: ...6 7 Aligning the unit CAUTION Incorrect alignment can result in property damage The transport and installation of the pump can affect the alignment The motor must be aligned to the pump not vice versa...

Страница 24: ...taken from the table Maximum per missible shaft displacement Radial displacement is dependent on the speed The nu merical values in the table and their interim values can be calculated as follows Krpe...

Страница 25: ...ly check the distance between the two coupling halves A Fig 21 Adjusting screw A for axial safeguard B B Fig 22 Fastening screws B of coupling halves Connect the coupling halves once correctly aligned...

Страница 26: ...This requirement applies to every operating status including operating temper ature and inlet pressure 6 7 2 Alignment of the pump unit Any deviations in the measuring results indicate a misalignment...

Страница 27: ...must also be fitted with a residual current circuit breaker Observe the manufacturer s installation and operating instructions for the mo tor and accessories During installation and connection work o...

Страница 28: ...correct insulation The discharge cover and the bearing bracket must not be insulated 7 Commissioning WARNING Risk of injury due to missing protective equipment Serious injuries can occur due to missin...

Страница 29: ...a suitable secure position Always exercise caution when opening the venting screw Procedure for venting systems where the fluid level lies above the suction port of the pump Open the isolating valve...

Страница 30: ...turning in the right direction The coupling guard is attached correctly and is screwed tightly Pressure gauges with a suitable measurement range are installed on the suction and pressure side of the p...

Страница 31: ...ropriate level CAUTION Risk of property damage due to frost If there is a danger of frost Drain the pump completely to avoid damage Close the shut off device in the pressure pipe If a non return valve...

Страница 32: ...here is danger of limbs being severed Pro tective gloves must be worn to protect against cuts 9 1 Personnel qualifications Electrical work A qualified electrician must carry out the electrical work Ma...

Страница 33: ...Daily 10 120 drops min are normal Gland Packing Check for leakage Half yearly If necessary replace with new packings Bearings Check temperature Weekly Bearings are greased for life and are maintenance...

Страница 34: ...ane chain pulley block suitable for handling the weight of pumping unit A selection of ring and open ended spanners in British and Metric sizes Eye bolts in British and Metric sizes Cotton rope wire r...

Страница 35: ...e 13 Exploded view of Atmos TERA SCH hydraulic mechanical seal version without sleeves Fig 26 Exploded view of Atmos TERA SCH hydraulic mechanical seal version with sleeves No Part description No Part...

Страница 36: ...lts 30 Bearing cover Non Drive End Table 15 Exploded view of Atmos TERA SCH hydraulic mechanical seal version with sleeves 9 5 2 Disassembling the top housing Close the isolating valves in suction and...

Страница 37: ...ase the reposition it while reassembling Remove the impeller 21 carefully Avoid damage to the impeller key 14 Further steps for mechanical seal version with sleeves Remove bolts 28 for the mechanical...

Страница 38: ...ine the impeller For damage For corrosive erosion pitting For Cavitations pitting for Bent or cracked vanes For inlet and outlet vane end wear If damage is extensive impeller replacement recommended B...

Страница 39: ...s for the pump motor and other accessories Reinstall any uninstalled safety devices such as terminal box covers once the work is complete NOTICE Never bring sealing elements O rings made of EP rubber...

Страница 40: ...e marked position Place the grab screw 13 at its position on the adjusting ring but do not tighten it now keep it loose When pressing in stationery seats make sure that the pressure distribution is un...

Страница 41: ...rings see accompanying figures Press in the logging ring 39 and stuff in remaining gland pack rings Place the gland cover 37 at its position and tighten its bolts 40 hand tight Check for free rotatio...

Страница 42: ...ectric shock Electrical work must be carried out by a qualified electrician in accordance with the locally applicable regulations WARNING No persons are allowed to be present inside the working area o...

Страница 43: ...g gap too large due to wear Exchange worn wear ring X Incorrect direction of rotation Change the motor connection phases X Pump sucks air or the suction line is leaky Replace gasket Check suction line...

Страница 44: ...pare parts documentation and the following in formation in these installation and operating instructions CAUTION Risk of property damage Trouble free pump operation can only be guaranteed when origina...

Страница 45: ...seal housing guard 4 13 Seal housing guard 4 14 Impeller key 1 15 Bolts for split flange 16 Lifting bolts 2 17 Air cock 1 18 Jack screws for opening top housing 2 19 Hose Pipe 2 20 Top pump housing 1...

Страница 46: ...1 21 Impeller 1 22 Bottom pump housing 1 23 Dowel pin for location 24 Shaft 1 25 Wear ring 2 26 Impeller nut 2 27 Dowel pin for wear ring 2 28 Bolts for mechanical seal cover 2 29 Bolts for bearing co...

Страница 47: ...c products Proper disposal and appropriate recycling of this product avoid environmental damage and dangers to your personal health NOTICE Do not dispose in domestic waste This symbol means do not dis...

Страница 48: ...en Appendix 48 WILO SE 2020 10 13 Appendix 13 1 Examples for typical installation layouts Fig 31...

Страница 49: ...Appendix en Installation and operating instructions Wilo Atmos TERA SCH 49 13 2 Examples for proper and inappro priate pipework 2x Fig 32...

Страница 50: ...7 Scope of delivery 60 4 8 Accessories 60 4 9 Anticipated noise levels 60 4 10 Permissible forces and torques on the pump flanges 61 5 Transport and storage 62 5 1 Delivery 62 5 2 Transport 62 5 3 Sto...

Страница 51: ...nstallation 85 10 Faults causes and remedies 88 10 1 Faults 88 10 2 Causes and remedies 89 11 Spare parts 90 12 Disposal 92 12 1 Oils and lubricants 93 12 2 Water glycol mixture 93 12 3 Protective clo...

Страница 52: ...tains basic information for the individual phases of the life cycle Failure to observe this information carries the following risks Injury to persons from electrical mechanical and bacteriological fac...

Страница 53: ...d about locally applicable regulations governing accident prevention Have read and understood the installation and operating instructions Personnel must have the following qualifications Electrical wo...

Страница 54: ...n ports discharge ports or other openings Avoid the penetration of foreign objects To this end leave the protective covers or packaging on until they have to be removed for installation Packaging and...

Страница 55: ...the sound pressure specifications on the motor rating plate The sound pressure value of the pump is generally about the same value as that of the motor 2 dB A Observe the applicable health and safety...

Страница 56: ...ures The pumps are only approved for the fluids specified in the Technical data section Refer pump data sheet and order confirmation For any change in pumped fluid refer Wilo beforehand Intended use a...

Страница 57: ...eration on the frequency converter is permitted Refer to the documentation from the motor manufacturer for the relevant requirements and observe its contents 4 3 Type key Example Wilo Atmos TERA SCH 2...

Страница 58: ...th VDI 2035 CH SWKI BT 102 01 fix leaky spots 4 5 Connection Details LVFKDUJH 3 Q 6 3 7 9 30 6XFWLRQ Fig 1 Additional connections on the housing Connection Details No Pump CG PG PM AC CDS CDD GD VG TG...

Страница 59: ...wel pin for wear ring 33 Bearing housing Non Drive End 37 Gland cover 14 Impeller key 2 Rotating element of gland pack version 2 3 4 5 6 7 8 9 10 26 26 25 24 14 27 21 27 25 26 26 10 9 8 7 6 30 4 3 31...

Страница 60: ...Drive End 4 Rotating element of mechanical seal version with sleeves 4 7 Scope of delivery Complete unit Atmos TERA SCH pump Base frame Coupling and coupling guard With or without electric motor Inst...

Страница 61: ...els within a cube shaped measuring area at a distance of 1 m from the surface of the motor 5 Anticipated noise levels for standard pump 50 Hz 4 10 Permissible forces and torques on the pump flanges Fi...

Страница 62: ...ation in the compensation equation 5 Transport and storage 5 1 Delivery The pump is secured to a pallet ex works and is protected against dirt and moisture Check the shipment immediately on receipt fo...

Страница 63: ...al packaging for this or choose equivalent packaging 5 2 1 Attaching the pump Incorrect lifting can damage the pump Risk of falling Never lift the pump with slings engaged below the bearing housing Th...

Страница 64: ...pment must be ensured during operation When using hoisting gears ensure that a second person is present to coordinate the procedure if necessary For example if the operator s field of vision is blocke...

Страница 65: ...gn of the operating space inflow conditions are complete and correct 6 3 Preparing the installation Risk of personal injury and property damage due to improper handling Never set up the pump unit on u...

Страница 66: ...rink concrete of an adequate thickness for manufacturing This would prevent vibrations from being transmitted The base must be able to accommodate the forces vibrations and impact that occur Guidance...

Страница 67: ...t the pipes can be connected to the pump stress free 6 5 3 Pouring out the base frame The base frame can be poured out after fixing The process of pouring out reduces vibrations to a minimum Wet the b...

Страница 68: ...es on the pump connecting pieces The expansion of the pipes in the event of a temperature rise is to be compensated by suitable means Avoid air pockets in piping by means of appropriate installations...

Страница 69: ...ng the unit Incorrect alignment can result in property damage The transport and installation of the pump can affect the alignment The motor must be aligned to the pump not vice versa Check the alignme...

Страница 70: ...m can be taken from the table Maximum permissible shaft displacement Radial displacement is dependent on the speed The numerical values in the table and their interim values can be calculated as follo...

Страница 71: ...nce between the two coupling halves A Fig 21 Adjusting screw A for axial safeguard B B Fig 22 Fastening screws B of coupling halves Connect the coupling halves once correctly aligned The tightening to...

Страница 72: ...m This requirement applies to every operating status including operating temperature and inlet pressure 6 7 2 Alignment of the pump unit Any deviations in the measuring results indicate a misalignment...

Страница 73: ...fitted with a residual current circuit breaker Observe the manufacturer s installation and operating instructions for the motor and accessories During installation and connection work observe the cir...

Страница 74: ...incorrect insulation The discharge cover and the bearing bracket must not be insulated 7 Commissioning Risk of injury due to missing protective equipment Serious injuries can occur due to missing prot...

Страница 75: ...Always exercise caution when opening the venting screw Procedure for venting systems where the fluid level lies above the suction port of the pump Open the isolating valve on the pressure side of the...

Страница 76: ...motor is turning in the right direction The coupling guard is attached correctly and is screwed tightly Pressure gauges with a suitable measurement range are installed on the suction and pressure sid...

Страница 77: ...property damage due to frost If there is a danger of frost Drain the pump completely to avoid damage Close the shut off device in the pressure pipe If a non return valve is installed in the pressure...

Страница 78: ...There is danger of limbs being severed Protective gloves must be worn to protect against cuts 9 1 Personnel qualifications Electrical work A qualified electrician must carry out the electrical work M...

Страница 79: ...120 drops min are normal Gland Packing Check for leakage Half yearly If necessary replace with new packings Bearings Check temperature Weekly Bearings are greased for life and are maintenance free Su...

Страница 80: ...chain pulley block suitable for handling the weight of pumping unit A selection of ring and open ended spanners in British and Metric sizes Eye bolts in British and Metric sizes Cotton rope wire rope...

Страница 81: ...of Atmos TERA SCH hydraulic mechanical seal version without sleeves Fig 26 Exploded view of Atmos TERA SCH hydraulic mechanical seal version with sleeves No Part description No Part description No Pa...

Страница 82: ...ng bolts 30 Bearing cover Non Drive End 15 Exploded view of Atmos TERA SCH hydraulic mechanical seal version with sleeves 9 5 2 Disassembling the top housing Close the isolating valves in suction and...

Страница 83: ...while reassembling Remove the impeller 21 carefully Avoid damage to the impeller key 14 Further steps for mechanical seal version with sleeves Remove bolts 28 for the mechanical seal cover 7 Slide out...

Страница 84: ...xamine the impeller For damage For corrosive erosion pitting For Cavitations pitting for Bent or cracked vanes For inlet and outlet vane end wear If damage is extensive impeller replacement recommende...

Страница 85: ...nd other accessories Reinstall any uninstalled safety devices such as terminal box covers once the work is complete Never bring sealing elements O rings made of EP rubber into contact with mineral oil...

Страница 86: ...ts pre marked position Place the grab screw 13 at its position on the adjusting ring but do not tighten it now keep it loose When pressing in stationery seats make sure that the pressure distribution...

Страница 87: ...nying figures Press in the logging ring 39 and stuff in remaining gland pack rings Place the gland cover 37 at its position and tighten its bolts 40 hand tight Check for free rotation of the shaft Pum...

Страница 88: ...lectric shock Electrical work must be carried out by a qualified electrician in accordance with the locally applicable regulations No persons are allowed to be present inside the working area of the p...

Страница 89: ...to wear Exchange worn wear ring X Incorrect direction of rotation Change the motor connection phases X Pump sucks air or the suction line is leaky Replace gasket Check suction line X Supply line or i...

Страница 90: ...installer and or Wilo customer service List of original spare parts Refer to the Wilo spare parts documentation and the following information in these installation and operating instructions Risk of p...

Страница 91: ...aring housing Drive End 1 3 Bearing 2 4 Supporting ring 1 5 Bearing end cover Drive End 1 6 Water thrower 1 11 Hexagon plug 12 Bolts for seal housing guard 4 13 Seal housing guard 4 14 Impeller key 1...

Страница 92: ...15 Bolts for split flange 16 Lifting bolts 2 17 Air cock 1 18 Jack screws for opening top housing 2 19 Hose Pipe 2 20 Top pump housing 1 21 Impeller 1 22 Bottom pump housing 1 23 Dowel pin for locatio...

Страница 93: ...8 EC 12 4 Information on the collection of used electrical and electronic products Proper disposal and appropriate recycling of this product avoid environmental damage and dangers to your personal hea...

Страница 94: ...zh CHS Appendix 94 WILO SE 2020 10 13 Appendix 13 1 Examples for typical installation layouts Fig 31...

Страница 95: ...Appendix zh CHS Wilo Atmos TERA SCH 95 13 2 Examples for proper and inappropriate pipework 2x Fig 32...

Страница 96: ......

Страница 97: ......

Страница 98: ......

Страница 99: ......

Страница 100: ...Pioneering for You Local contact at www wilo com contact WILO SE Wilopark 1 44263 Dortmund Germany T 49 0 231 4102 0 T 49 0 231 4102 7363 wilo wilo com www wilo com...

Отзывы: