PLB-098 

Oil Furnaces

 – 

Furnace Manual

 

11/13  

3

 

1.

 

INSTALLATION 

The unit is shipped with a burner and its controls. It requires a 
115VAC power supply to the control panel and thermostat hook-up 
as shown on the wiring diagram, one or more oil line connections, 
suitable ductwork and connection to a properly sized vent.  
All local and national code requirements governing the installation of 
oil burning equipment, wiring and the flue connection MUST be 
followed. Some of the codes that may apply are: 
CSA B139:

  

Installation code for oil burning 
equipment. 

ANSI/NFPA 31:

 

Installation of oil burning equipment. 

ANSI/NFPA 90B:

 

Warm air heating and air conditioning 
systems. 

ANSI/NFPA 211:

 

Chimneys, Fireplaces, Vents and solid 
fuel burning appliances.

 

ANSI/NFPA 70:

 

National Electrical Code. 

CSA C22.1:

  

Canadian Electrical Code.

 

or CSA C22.10

Only the latest issues of these codes may be used. 

1.1.

 

POSITIONING THE FURNACE 

Fire and explosion hazard. 
The furnace must be installed in a level position, 
never where it will slope toward the front. 
Do not store or use gasoline or any other 
flammable substances near the furnace. 
Non-observance of these instructions will 
potentially result in death, bodily injury and/or 
property damage. 

This furnace is not watertight and is not designed 
for outdoor installation. It must be installed in 
such a manner as to protect its electrical 
components from water. Outdoor installation will 
lead to a hazardous electrical condition and to 
premature failure of the equipment. 

The minimum clearances from combustible material for each of 
the positions are specified in Table 1. 

If the furnace is installed in a basement or on a dirt floor, in a crawl 
space for example, it is recommended to install the unit on a cement 
base 2.5 cm to 5.0 cm (1" to 2") thick. 

The unit must be installed in an area where the ambient and return 
air temperatures are above 15°C (60°F). In addition, the furnace 
should be installed as closely as possible to the vent, so that the 
connections are direct and kept to a minimum. The heater should 
also be located close to the centre of the air distribution system. 

1.1.1.

 

Installation in an enclosure 

The unit can be installed in an enclosure such as a closet. However, 
2 ventilation openings are required for combustion air. The openings 
should be located in front of the furnace approximately 15 cm (6") 
above the floor and 15 cm (6") below the ceiling. Figure 1 indicates 
the minimum dimensions required and the location of the openings. 

Figure 1: Location and dimensions of ventilation air 

openings in a closet door 

 

Table 1: Minimum clearances from combustible materials 

LOCATION

 APPLICATION

CLEARANCES

(combustible materials)

RECOMMANDED ACCESS

FOR SERVICE

FURNACE

2.54 cm (1")

0.6 m (24")

SUPPLY PLENUM WITHIN 6 FEET OF FURNACE

2.54 cm (1")

BACK

ACCESS PANEL TO BLOWER

10.16 cm (4")

0.6 m (24")

FURNACE OR PLENUM

5.08 cm (2")

HORIZONTAL WARM AIR DUCT WITHIN  6 FEET OF FURNACE

5.08 cm (2")

BOTTOM

FURNACE (COMBUSTIBLE FLOOR)

0 cm (0")

FLUE PIPE

AROUND FLUE PIPE

22.86 cm (9")

FRONT

FURNACE

20.32 cm (8")

0.6 m (24")

SIDES

TOP

 

Содержание PLB-098 LOW-BOY

Страница 1: ...y could result in severe personal injury death or substantial property damage When calling or writing about the furnace Please indicate furnace model number and serial number from rating label You may...

Страница 2: ...bows 20 Always connect and seal a return air duct to the furnace unless the furnace is located in a large space such as an unpartitioned basement Route the return air duct to an adjacent room if no re...

Страница 3: ...to a hazardous electrical condition and to premature failure of the equipment The minimum clearances from combustible material for each of the positions are specified in Table 1 If the furnace is inst...

Страница 4: ...to the burner manufacturer s instructions Also the burner must be installed always in the same way independently of the furnace orientation 1 Position the mounting gasket between the mounting flange a...

Страница 5: ...re the draft is either high or variable due to external conditions Follow the instructions provided with the regulator 1 5 4 Side wall Venting The heating unit is approved for side wall venting This s...

Страница 6: ...xposure to the following substances a Permanent wave chemicals for hair b Chlorinated waxes and cleaners c Chlorine based swimming pool chemicals d Water softening chemicals e De icing salts or chemic...

Страница 7: ...furnace installed with a 4 tons air conditioning evaporator coil Heating mode airflow is still 1050 CFM Cooling mode air flow use Equation 3 4 CFM 4 x 400 1600 CFM The larger number is 1600 CFM cooli...

Страница 8: ...7 6 6 900 14 58 41 31 25 21 19 17 14 12 11 10 9 8 8 7 7 7 1000 16 64 45 34 28 23 20 18 15 13 11 10 9 9 8 8 7 7 1100 16 72 49 38 30 25 22 19 16 14 12 11 10 9 9 8 8 7 1200 16 54 41 33 27 24 21 17 15 13...

Страница 9: ...600 12 59 38 28 22 19 16 15 13 700 12 69 44 32 25 21 18 16 15 13 800 14 50 36 29 24 20 18 16 14 900 14 56 41 32 26 22 20 18 15 1000 16 63 45 35 29 24 22 19 17 15 1100 16 69 49 38 31 26 23 21 18 16 120...

Страница 10: ...he position of the wires on the electronic board of the unit and consult the wiring diagrams If the heating and air conditioning speeds are the same the RED wire must be moved to UNUSED LEADS on the e...

Страница 11: ...BVSO is installed according to instructions for chimney venting 4 The oil supply valve is open 5 The burner Reset button is well pushed in or re armed 6 The preliminary air adjustments on the burner...

Страница 12: ...ise is lower or exceeds the temperature specified in Table 10 change to the next lower or higher blower speed tap until the temperature rise falls to the target If the excessive temperature rise canno...

Страница 13: ...6 Re mount lock and fasten the control box with the 2 screws removed in step 4 7 Re attach the assembly cover with the screws removed in step 2 8 Re establish power to the unit 3 3 CLEANING OF THE BUR...

Страница 14: ...rough furnace checked not to exceed 85 F and the blower speed adjusted if necessary 19 Was the thermostat heat anticipator set per wiring diagram 20 Was the burner started and tested per burner manual...

Страница 15: ..._____________________________Date installed_____________________________ Installation instructions have been followed Checkout sequence has been performed Above information is certified to be correct...

Страница 16: ...000 0 70 MED HIGH HIGH 1255 1180 77 000 65 000 0 55 98 000 81 000 0 70 Model Input BTU h Blower motor HP Blower motor Speed adjustment 3 0 1 2 HP ECM 1 3 HP 4 speeds PLB098 DD PLB098 VS 10 x 10 Outpu...

Страница 17: ...h Firing rate USGPH AFUE Nozzle Delavan Pump pressure PSIG Burner tube insertion length Inch Combustion air adjustment Turbulator Damper 77 000 0 55 86 6 0 50 70A 150 0 2 0 98 000 0 70 85 2 0 60 70A...

Страница 18: ...1 ON 2 ON 1 5 600 660 540 SW4 DELAY DIP switch position HEAT INPUT USGPH PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time A 1 OFF 2 OFF 0 7 13 45 sec 19 30 sec...

Страница 19: ...PLB 098 Oil Furnaces Furnace Manual 11 13 19 5 DIMENSIONS AND RATINGS continued Figure 9 Wiring Diagram 4 Speed Motor PSC...

Страница 20: ...PLB 098 Oil Furnaces Furnace Manual 20 11 13 5 DIMENSIONS AND RATINGS continued Figure 10 Wiring Diagram Variable Speed Motor ECM...

Страница 21: ...PLB 098 Oil Furnaces Furnace Manual 11 13 21 6 COMPONENTS AND REPLACEMENT PARTS Figure 11 Parts List With 4 Speed motor PSC B50126A...

Страница 22: ...B03549 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B03118 01 ELECTRICAL KIT BVSO EXT 32 B03596 BURNER WIRE CHANEL 33 Z06G001 BLOCKED VENT SHUT OF...

Страница 23: ...PLB 098 Oil Furnaces Furnace Manual 11 13 23 6 COMPONENTS AND REPLACEMENT PARTS continued Figure 12 Parts List With variable speed motor ECM B50127A...

Страница 24: ...AL BOX SPACER 28 B03534 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B03118 01 ELECTRICAL KIT BVSO EXT 32 B03596 BURNER WIRE CHANEL 33 Z06G001 BLOC...

Страница 25: ...f the furnace oil burner should shut down on flame failure the burner primary control will lock out Ask your service technician to show you the correct procedure to reset the primary control button NE...

Страница 26: ...PLB 098 Oil Furnaces Furnace Manual 26 X40205 Rev B 11 13...

Отзывы: