background image

 

Installation

 

 

14 

 

 

 

 

 

 

Gas Supply and Piping 

The  gas  control  valve is  shipped  with  a  sealed cover over  the 
gas  inlet  tapping.  Do  not  remove  seal  until  you  are  ready  to 
connect piping. 

WARNING: 

Danger  of  property  damage,  bodily 

injury  or  death.  Make  sure  the  furnace  is 
equipped to operate on the type of gas available. 
Models designated as natural gas are to be used 
with  natural  gas  only.  Furnaces  designated  for 
use  with  liquefied  petroleum  gas  (L.P.G.)  have 
orifices sized for commercially pure propane gas. 
They cannot be used with butane or a mixture of 
butane and propane. 

 

Gas Supply 

Minimum  gas  supply  pressure  for  natural  gas  to  the  furnace 
control  valve  is  5  inches  water  column  and  must  not  be  more 
than 7 inches water column. 

Minimum  gas  supply  pressure  for  L.P.  gas  to  the  furnace 
control  valve  must  be  at  least  11  inches  water  column  and 
must not exceed 13 inches water column. 

Gas  pressures  and  pressures  to  the  burners must  not  exceed 
the  rated  input  and  pressure  shown  on  the  rating  plate.  For 
natural gas, the manifold pressure should be 3.2 inches water 
column.  The  manifold  pressure  should  be  10  inches  water 
column for L.P. gas. An orifice change may be required to suit 
the gas supplied. 

 

 

Orifice Sizes 

The  efficiency  rating  of  these  appliances  is  a  product  thermal 
efficiency  rating  determined  under  continuous  operating 
conditions  and  determined  independently  of  any  installed 
system.  

The correct orifice sizes for the different input ratings when 
using natural or L.P. gas are:  

 

 

MODEL 

NUMBER 

GAS 

TYPE 

INPUT 

RATING 

Btu/hr. 

HEATING 

CAPACITY 

RATING 

Btu/hr. 

Main Burner Orifice 

DRILL 

DEC  QTY 

17035 Series 

Nat. 

17,500 

16,400 

#47 

.0780 

17035 Series 

L.P. 

17,500 

16,400 

N/A 

.0500 

 

Btu/hr. = British Thermal Units per hour. 

 

Gas Piping 

The gas supply line must be of an adequate size to handle the 
Btu/hr.  requirements  and  length  of  the  run  for  the  unit  being 
installed. 
 
Determine  the  minimum  pipe  size  from  Figure  16,  basing  the 
length of the run from the gas meter or source to the unit. 
 

CAPACITY AND ORIFICE SIZING 

FIGURE 24 

FIGURE 25 

Содержание 1753012

Страница 1: ...l switch Do not use any phone or cell phone in your building Extinguish any open flame Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot r...

Страница 2: ...improper installation 4 This warranty does not cover claims which do not involve defective workmanship or materials DUTIES OF THE CONSUMER 1 The heating equipment must be installed by a qualified inst...

Страница 3: ...llation 6 17 Locating Your Wall Furnace 6 Thermostat Installation 9 Cabinet Installation 11 Vent Installation 11 Gas Supply and Piping J 14 Operating Your Furnace 18 20 Operating Instructions 18 Start...

Страница 4: ...pecified 9 BE SURE to provide for adequate combustion and ventilation air The flow of this air to the furnace must not be blocked 10 NEVER vent flue gases into another room a fireplace or any space in...

Страница 5: ...d Hand drill or properly grounded electric drill 6 ft folding rule or tape measure Screwdrivers Phillips Head Pliers wire cutting Stud locator or small finishing nails Tin snips 8 and 12 inch adjustab...

Страница 6: ...lectrical outlet can be brought to the furnace 6 Select a location that will provide adequate accessibility clearance for servicing and proper operation Interior Clearances Figure 2 1 The unit is desi...

Страница 7: ...g center mark all the way through to the outside Cut the 2 1 2 inch diameter hole through the inside wall Using the 1 4 inch hole as center cut a matching hole in the outside wall It may be better to...

Страница 8: ...fter cutting the vent and gas openings place the rear panel back onto the wall and screw into place using the supplied mounting screws The screws should go into the wall studs as there are enough clea...

Страница 9: ...drilling a hole in the wall at the selected location drive a small finishing nail through the ceiling in the comer of the wall and ceiling above the thermostat location Pull the nail out and push a s...

Страница 10: ...3 Push any excess wire back through hole in the wall and plug the hole with insulation to prevent drafts from affecting thermostat operation 4 Being sure to level thermostat for the best appearance F...

Страница 11: ...VC meeting ASTM Standard D1784 For Canada ULC S636 approved duct must be used Use a 45 elbow as the vent termination for the exhaust pipe vent terminations are not counted towards the overall vent len...

Страница 12: ...Installation 12 FIGURE 16 FIGURE 17 FIGURE 18 FIGURE 19...

Страница 13: ...to attach the PVC pipe to the inducer fan and tighten the hose clamps shown in Fig 21 If PVC pipes will be exposed to freezing temperatures the pipes must be insulated using Armaflex or similar insul...

Страница 14: ...burners must not exceed the rated input and pressure shown on the rating plate For natural gas the manifold pressure should be 3 2 inches water column The manifold pressure should be 10 inches water...

Страница 15: ...On L P gas installations use a compound resistant to action of liquefied petroleum gases 3 Use ground joint unions 4 Install a drip leg sediment trap to trap dirt and moisture before it can enter the...

Страница 16: ...cified pressures for testing Higher pressures may damage the gas valve and cause over firing which may result in combustion chamber failure Liquefied petroleum gas L P G is heavier than air and it wil...

Страница 17: ...you have a question regarding the amount of fuel consumed call your local gas utility or gas supplier WARNING DO NOT TAMPER WITH THE REGULATOR OR BURNER ORIFICES AS PROBLEMS RESULTING FROM THERE MAY C...

Страница 18: ...safety information above 2 Make sure there is power to the unit the furnace is supplied with a 3 prong 120VAC power cord The internal switches must be on see fig 31 and 32 3 The furnace has 3 modes of...

Страница 19: ...level The display panel will show the word SET on the top right corner After this sequence the display panel will show heat level 6 Local Mode After setting a desired room temperature on the display...

Страница 20: ...re To measure the input using the gas meter proceed as follows 1 Turn off the gas supply to all other appliances except the furnace 2 With the furnace operating time the smallest dial on the meter for...

Страница 21: ...t panel Using a low profile tray to collect water place underneath the trap and unscrew the bottom of the trap After condensate is collected replace the bottom of the trap replace front panel and rest...

Страница 22: ...er Description Qty 1 6H24 Inner Frame 1 2 6H03 Bottom Support Cover 1 3 6H01 Heat Exchanger Support 1 4 P323702 17 5K Heat Exchanger Asy 1 5 6H13 Blower Housing Support Right 1 6 6H12 Blower Housing D...

Страница 23: ...Replacement Parts List 34 6H31 Front Panel 1 35 P323465 Nylon PCB Standoff 4 36 P323481 Inducer Fan Mounting Screw 4 37 P323459 Fan Motor 1 38 P323460 Blower Wheel 1...

Страница 24: ...24 Page left blank intentionally...

Страница 25: ...Page left blank intentionally...

Страница 26: ...Wiring Diagram 26...

Страница 27: ...eing fastened to an uneven wall Vent tube and air inlet tube may be in a bind with a vent cap assembly Be sure the hole through the wall is correct and parts fit without binding 5 Noisy Blower A Housi...

Страница 28: ...liance Do not touch any electrical switch Do not use any phone or cell phone in your building Extinguish any open flame Immediately call your gas supplier from a neighbor s phone If you cannot reach y...

Отзывы: