Menu Key:
Code
Default Range
Definition
Explanation
ON
-58 ~ 230
Temperature at which the unit
supplies output power.
OFF
-58 ~ 230
Temperature at which the unit
shuts off output power.
CA
0
-9~9
Calibrate the reading
Optional
. If displayed temperature is 3 degree
higher than the actual temperature, set CA to -3.
PT***
0
0~30
Compressor Time Delay
(unit: minute)
Optional
. It defines the time interval of 2
compressor cycles(On-Off)
AH
230
-58 ~ 230
High temperature alarm
Optional
. It will beep once if temperature exceeds
AH.
Press any key to stop alarm.
AL
-58
-58 ~ 230
Low temperature alarm
Optional
. It will beep once temperature is below
AL.
Press any key to stop alarm.
AT
0
0~999
Auto shut off timer
(unit: minute)
*
Please
refer
to
advanced
settings
To shut off the device plugged in the controller
rather than the controller itself.
This parameter only appears after you enable
timer in
advanced menu
by setting dL=ON.
Trouble Shooting:
A. The output device won’t power on.
Check that the controller and the output device are securely plugged in and the
value for
power on temperature “ON” is set correctly.
B
.
The controller displays EEE while beeping.
The probe is not inserted completely into the jack or it may be defective. Email
us at [email protected] for a free probe replacement.
C. The display shows LLL or HHH.
The
temperature is outside the unit’s measurement range either too high (HHH)
or too low (LLL)
D. The unit keeps beeping at a certain temperature.
The
alarm function can be disabled by setting “AH” to 230 and “AL” to -58.
E. The display shows “---“, or there is some other malfunction.
Restore factory default settings by powering off the unit then powering it on
and holding SET and UP buttons for 10 seconds while the unit cycles through
showing “888” and “---“.